Loading...
Ordinance Number 772331 ORDINANCE NO. 772 AMENDMENT TO TITLE 4 OF THE MUNICIPAL CODE— ADOPTING UNIFORM FIRE CODE, 1994 EDITION AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF SAN JUAN CAPISTRANO, CALIFORNIA, AMENDING CHAPTER 2 "FIRE PREVENTION" OF TITLE 4 "PUBLIC SAFETY" RELATING TO ADOPTION BY REFERENCE OF THE UNIFORM FIRE CODE, 1994 EDITION, WITH APPENDICES; THE UNIFORM FIRE CODE STANDARDS 1994 EDITION, WITH APPENDICES; AND AMENDMENTS THERETO THE CITY COUNCIL OF THE CITY OF SAN JUAN CAPISTRANO, CALIFORNIA, DOES HEREBY ORDAIN AS FOLLOWS: SECTION 1. Findings. The following changes and modifications to the 1994 Uniform Fire Code, as recommended by the city building official, are hereby found to be reasonably necessary due to the following local conditions for housing. A. UFC Section 1003.2.2 Required Installation of Automatic Fire - Extinguishing Systems, All Occupancies except Group R, Division 3, and Group U (impacts corresponding Title 24 Section 904.2) is amended by deleting the words "Division 3, and Group U," and adding an item 6 and adding Group U Occupancies to this section as follows: Section 1003.2.2 Required Installation of Automatic Fire -Extinguishing Systems, All Occupancies except Group R. 6. In all new buildings or structures when the gross square footage thereof exceeds 6,000 square feet (588 m2) or more than 2 stories in height. For the purpose of this section, area separation walls shall not define separate buildings. B. UFC Section 1003.2.8 Group R Occupancies (impacts corresponding Title 24 Section 904.2) is hereby deleted and the following substituted: Section 1003.2.8.1 Group R Occupancies, other than Group R, Division 3 Detached One- and Two -Family Dwellings. All new Group R Occupancies, other than Group R, Division 3 detached one- and two-family dwellings shall be equipped with an approved automatic sprinkler system. Residential or quick -response standard sprinkler heads shall be used in the dwelling unit and guest room portions of the building. 1 332 For the purposes of this section, area or occupancy separation walls shall not define separate buildings. Section 1003.2.8.2 Group R, Division 3, One- and Two -Family Dwellings. All new Group R, Division 3 detached one- and two-family dwellings 5,500 square feet (511 m2) or larger in area shall be equipped with an approved automatic residential fire sprinkler system. Residential or quick -response standard sprinkler heads shall be used in the dwelling portion of the building. For the purposes of this section, area or occupancy separation walls shall not define separate buildings. EXCEPTION: In reconstruction or remodeling of existing Group R, Division 3, detached one- and two-family dwellings where the cost of installing an approved automatic residential sprinkler system exceeds 5 percent of the reconstruction or remodeling cost, with the approval of the chief, the required sprinkler system may be omitted. C. UFC Section 1003.2 Required Installations (impacts corresponding Title 24 Section 904.2) is hereby amended by adding Section 1003.2.9 as follows: Section 1003.2.9 All Occupancies, Very High Fire Hazard Severity Zones. In addition to all other relevant provisions of this code and amendments thereto, all new construction and reconstructed structures located in Very High Fire Hazard Severity Zones shall be equipped with an approved automatic fire sprinkler system. These amendments are reasonably necessary because of the following conditions: Climatic conditions: 1. The City of San Juan Capistrano is located in a semi -arid Mediterranean type climate. It annually experiences extended periods of high temperatures with little or no precipitation. Hot, dry foehn (Santa Ana) winds, which may reach speeds of 70 m.p.h. or greater, are also common to the area. These climatic conditions cause extreme drying of vegetation and common building materials and predispose the area to large destructive fires (conflagration). 2. The climate alternates between extended periods of drought and brief flooding conditions. Water demand in this densely populated area far exceeds the quantity supplied by natural precipitation; and although population continues to grow, the already taxed water supply does not. 3. These dry climatic conditions and winds contribute to the rapid spread 2 I WN of even small fires originating in high density housing or vegetation. These fires spread very quickly and create a need for increased levels of fire protection. The added protection of fire sprinkler systems will supplement normal fire department response by providing immediate protection for the building occupants and by containing and controlling the fire spread to the area of origin. Fire sprinkler systems will. -Aso reduce the use of water for firefighting by as much as 50 to 75 percent. Topographical conditions: 1. Traffic and circulation congestion is an artificially created, obstructive topographical condition, which is common in the City of San Juan Capistrano and throughout Orange County. 2. These topographical conditions combine to create a situation which places fire department response time to fire occurrences at risk, and makes it necessary to provide automatic on-site fire -extinguishing systems to protect occupants and property. Geological conditions: 1. The City of San Juan Capistrano is located in an area of high seismic activity. The Newport -Inglewood Fault, located west of the city, poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the degree of city's urbanization and close proximity to a major fault, the risk of structural damage and loss of life due to ground shaking is considerable. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake, fire department resources would be extremely taxed, and the ability to respond to fires would be complicated and in some cases impossible. On-site fire -extinguishing systems would provide a degree of protection from fires even if water mains are damaged or destroyed. D. UFC Section 1004 - STANDPIPES (impacts corresponding Title 24 Section 904.5) is hereby amended by deleting Section 1004.2 Required Installation and substituting the following: Section 1004.2 Required Installations. Standpipe systems shall be provided as set forth in Table No. 1004-A and the provisions of this section. Every new building with any horizontal dimension greater than 300 feet (91 440 mm) shall be provided with either access doors or hose outlets located so that all portions of the building can be reached with 150 feet (45 720 mm) of hose from an access door or hose outlet. 9 334 Required access doors shall be located in the exterior wall of the building and shall be accessible without the use of a ladder. The door dimensions shall be not less than 3 feet (914 mm) in width nor 6 feet 8 inches (2032 mm) in height. The hose outlets shall be 2-1/2 inches (63 mm) in size with an approved valve. The water supply for the hose outlets shall be provided: 1. By a separate main supplied from the system side of the check valve at the fire department connection, or 2. From an adjacent section of the sprinkler system arranged to allow the hose outlets to deliver water when the sprinklered system, or a portion of the system that protects the area served by the hose outlet, is shut off. These amendments are reasonably necessary because of the following conditions: Topographical conditions: 1. Traffic and circulation congestion is an artificially created, obstructive topographical condition, which is common in the City of San Juan Capistrano and Orange County. 2. Large commercial/ industrial buildings, with a horizontal dimension of 300 feet or greater, create an unusual topographical condition. Portions of these buildings cannot be reached with a fire hose line on initial attack. 3. These topographical conditions combine to create a situation which places fire department response time to fire occurrences at risk and makes it necessary to provide additional on-site fire fighting resources. E. UFC Section 1008 - SPECIAL PROVISIONS FOR HIGH-RISE BUILDINGS (impacts corresponding Title 24 Section 403) is hereby amended as follows: Section 1008.1 Scope. In addition to other applicable requirements of these regulations, the provisions of this section have been amended to identify high-rise buildings as any structure 55 feet or greater in height above the lowest level of fire department vehicle access. This section also requires a roof -top emergency access and evacuation facility on all buildings 75 feet or greater in height with an occupancy classification of Group B, or Group R, Division 1. Optional provisions are provided for buildings with a roof slope greater than 4 in 12. These amendments are reasonably necessary because of the following conditions: Topographical conditions: El 335 1. The City of San Juan Capistrano has an urban atmosphere which is reflected in building and building complex design and features. Landscaping and other building features often preclude or greatly limit approach or operational access by fire department vehicles. The UBC high-rise provisions were developed to provide for fire department laddering capabilities and response time in a downtown Los Angeles or New York City setting. These older cities typically have high-rise buildings which are constructed close to the street, but in San Juan Capistrano and Orange County, high-rise buildings typically have side yards and landscaping. 2. The high-rise building itself creates an unusual topographical condition. High-rise building firehistory shows that many people evacuate to the roof area, especially if they are above the fire floor. Utilization of helicopters is very common in these types of fires and is often the only method which can be used for evacuation or access to the fire. F. Article 11 - GENERAL SAFETY PRECAUTIONS (impacts corresponding Title 24 Section 3102). Section 1109 - CONTROL OF SOURCES OF IGNITION has been amended to require chimney spark arresters on all new devices that burn any solid or liquid fuel. This protection is necessary because of the area climatic conditions. Climatic conditions: 1. The City of San Juan Capistrano is located in a semi -arid Mediterranean type climate. It annually experiences extended periods of high temperatures with little or no precipitation, which causes extreme drying of vegetation and common building materials. 2. The City of San Juan Capistrano is also subject to extreme foehn (Santa Ana) wind conditions which further contribute to drying and rapid spread of fire. 3. These climatic conditions combine to create a unique situation where vegetation and building materials are the driest during the winter months. Fireplaces are most frequently used during this time, and flying embers become a hazard for building materials or vegetation in the general area. G. UFC Section 5202 Flammable and Combustible Liquid Motor Vehicle Fuel -Dispensing Stations is amended to let the chief approve temporary aboveground fuel tanks within certain guidelines which are consistent with motor vehicle fuel dispensing from exterior storage aboveground tanks. 5 SSb These amendments are reasonably necessary because of the following conditions: Geological conditions: 1. The City is located in an area of high seismic activity. The Newport - Inglewood Fault is close to the City, and poses the greatest hazard to life and property. 'It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the degree of the City's urbanization and close proximity to a major fault, the risk of a potential spill of flammable/ combustible liquids at these locations is considerable. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake, fire department resources would be extremely taxed, and the ability to respond to fires and spills of flammable combustible liquids would be complicated and in some cases impossible. TopoUaphical conditions: 1. The City has an urban atmosphere which is reflected in building and building complex design and features. Landscaping and other building features often preclude or greatly limit approach or operational access by fire department vehicles. With the dense urban areas close together, the chance of a spill or spread of such chemicals is a considerable threat. H. UFC Article 64 Stationary Lead -acid Battery Systems is added to be consistent with the 1995 Uniform Fire Code Supplement. These amendments are reasonably necessary because of the following conditions: Geological conditions: 1. The City is located in an area of high seismic activity. The Newport - Inglewood Fault is close to the City, and poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the City's urbanization and close proximity to a major fault, the risk of a potential hazardous spill of battery acid is considerable at these locations, along with power interruptions which could affect the safety and operations of such sites. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake, fire department resources would JJ/ be extremely taxed, and the ability to respond to fires and spills of battery acid at such sites would be complicated and in some cases impossible. I. UFC Article 80 Hazardous Materials, Section 8001 Exterior Storage is added to be consistent with the 1995 Uniform Fire Code Supplement.. These amendments are reasonably necessary because of the following conditions: Geological conditions: 1. The City is located in an area of high seismic activity. The Newport - Inglewood Fault is close to the City, and poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the City's urbanization and close proximity to a major fault, the risk of a potential hazardous materials spill is considerable. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake, fire department resources would be extremely taxed, and the ability to respond to fires and spills of hazardous materials would be complicated and in some cases impossible. Topographical conditions: 1. The City has an urban atmosphere which is reflected in building and building complex design and features. Landscaping and other building features often preclude or greatly limit approach or operational access by fire department vehicles. With the dense urban areas close together, the chance of a spill or spread of hazardous materials is a considerable threat. J. UFC Article 90 Standards, UFC Standard 52-1, Section 9002.2 is amended and is consistent with the 1995 Uniform Fire Code Supplement and provides for residential fueling of compressed natural gas vehicles. These amendments are reasonably necessary because of the following conditions: Geological conditions: 1. The City is located in an area of high seismic activity. The Newport - Inglewood Fault is close to the City, and poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the degree of 7 338 the City's urbanization and close proximity to a major fault, the risk of a potential leak of compressed natural gas at various locations throughout the City is considerable. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake, fire department resources would be extremely taxed, and the ability to respond to fires and leaks as a result of compressed natural gas would be complicated and in some cases impossible. j Topographical conditions: 1. The City has an urban atmosphere which is reflected in building and building complex design and features. Landscaping and other building features often preclude or greatly limit approach or operational access by fire department vehicles. With the dense urban area, the chance of a leak and ensuing fire from compressed natural gas is considerable after a major earthquake. Density of residential occupancies increases the threat if a leak or fire occurs. K. Appendix I -B Life -safety Requirements for Existing High-rise Buildings the Scope and Section 6.1 item 2 Special Provisions and Alternatives, Automatic Sprinklers is hereby deleted and replaced with the following: Section 6.1, item 2 Automatic Sprinklers. An approved automatic fire - extinguishing system shall be installed throughout the building in accordance with the requirements of NFPA 13 as adopted in Appendix V of this code. In addition to the main water supply, a secondary on- site supply of water equal to the hydraulically calculated sprinkler design demand plus 100 gallons (378.5 L) per minute additional for the total standpipe system shall be provided. This supply shall have a duration of 30 minutes and shall be automatically available if the principal supply fails. Sprinkler control valves and waterflow detecting devices shall be provided at the lateral connection to the riser on each floor. These amendments are reasonably necessary because of the following conditions: Climatic conditions: 1. The City of San Juan Capistrano is located in a semi -arid Mediterranean type climate. It annually experiences extended periods of high temperatures with little or no precipitation. Hot, dry foehn (Santa Ana) winds, which may reach speeds up to 70 m.p.h, are also 11 339 common to the area. These climatic conditions cause extreme drying of vegetation and common building materials and predispose the area to large destructive fires (conflagration). 2. The climate alternates between extended periods of drought and brief flooding conditions. Water demand in this densely populated area far exceeds the quantity supplied by natural precipitation; and although the population continues to grow, the already taxed water supply does not. California is projected to increase in population by nearly 10 million over the next quarter of a century with 50 percent of that growth centered in southern California. 3. These dry climatic conditions and winds contribute to the rapid spread of even small fires originating in high density housing or vegetation. These fires spread very quickly and create a need for increased levels of fire protection. The added protection of fire sprinkler systems will supplement normal fire department response by providing immediate protection for the building occupants and by containing and controlling the fire spread to the area of origin. Fire sprinkler systems will also reduce the use of water for firefighting by as much as 50 to 75 percent. Topographical conditions: 1. Traffic and circulation congestion is an artificially created, obstructive topographical condition, which is common in the City of San Juan Capistrano and throughout Orange County. 2. These topographical conditions combine to create a situation which places fire department response time to fire occurrences at risk, and makes it necessary tm provide automatic on-site fire -extinguishing systems to protection occupants and property. Geological conditions: 1. The City of San Juan Capistrano is located in an area of high seismic activity. The Newport -Inglewood Fault, located north of the city, poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the city's degree of urbanization and close proximity to a major fault, the risk of structural damage and loss of life due to ground shaking is considerable. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake, fire department resources would be extremely taxed, and the ability to respond to fires would be complicated and in some cases impossible. On-site fire -extinguishing E 340 systems would provide a degree of protection from fires even if water mains are damaged or destroyed. L. Appendix V, Adopted Standards Section 2 (impacts corresponding Section 3503 of Title 24) 1. NFPA 13,1994 Edition, Installation of Sprinkler Systems is amended (as adopted in UBC Standards 9-1), to address Buildings of Undetermined Use, and Concealed Spaces. 2. NFPA 13D, 1994 Edition, Installation of Sprinkler Systems in One and Two Family Dwellings and Mobile Homes is amended to address Valves and Drains, Pressure Gauges, Alarms, and Locations of Sprinklers. 3. NFPA 13R, 1994 Edition, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to Four Stories in Height is amended to cover areas where sprinklers may be omitted. These amendments are reasonably necessary because of the following conditions: Climatic conditions: 1. The City of San Juan Capistrano is located in a semi -arid Mediterranean type climate. It annually experiences extended periods of high temperatures with little or no precipitation. Hot, dry foehn (Santa Ana) winds, which may reach speeds up to 70 m.p.h, are also common to the area. These climatic conditions cause extreme drying of vegetation and common building materials and predispose the area to large destructive fires (conflagration). 2. The climate alternates between extended periods of drought and brief flooding conditions. Water demand in this densely populated area far exceeds the quantity supplied by natural precipitation; and although the population continues to grow, the already taxed water supply does not. California is projected to increase in population by nearly 10 million over the next quarter of a century with 50 percent of that growth centered in southern California. 3. These dry climatic conditions and winds contribute to the rapid spread of even small fires originating in high density housing or vegetation. These fires spread very quickly and create a need for increased levels of fire protection. The added protection of fire sprinkler systems will supplement normal fire department response by providing immediate protection for the building occupants and by containing and controlling the fire spread to the area of origin. Fire sprinkler systems will also 341 reduce the use of water for firefighting by as much as 50 to 75 percent. Tovographical conditions: 1. Traffic and circulation congestion is an artificially created, obstructive topographical condition which is common in the City of San Juan Capistrano and throughout Orange County. 2. These topographical conditions combine to create a situation which places fire department response time to fire occurrences at risk, and makes it necessary to provide automatic on-site fire -extinguishing systems to protection occupants and property. Geological conditions: 1. The City of San Juan Capistrano is located in an area of high seismic activity. The Newport -Inglewood Fault, located west of the city, poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the city's degree of urbanization and close proximity to a major fault, the risk of structural damage and loss of life due to ground shaking is considerable. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake fire department resources would be extremely taxed, and the ability to respond to fires would be complicated and in some cases impossible. On-site fire -extinguishing systems would provide a degree of protection from fires even if water mains are damaged or destroyed. 4. NFPA 14, 1993 Edition, Standard for the Installation of Standpipe and Hose Systems is amended to cover Fire Department Connections, and Minimum Pressure for System Design and Sizing of Pipe. These amendments are reasonably necessary because of the following conditions: Climatic conditions: 1. The City of San Juan Capistrano is located in a semi -arid Mediterranean type climate. It annually experiences extended periods of high temperatures with little or no precipitation. Hot, dry foehn (Santa Ana) winds, which may reach speeds up to and exceeding 70 m.p.h, are also common to the area. These climatic conditions cause extreme drying of vegetation and common building materials and predispose the area to large destructive fires (conflagration). 11 342 -I. The climate alternates between extended periods of drought and brief flooding conditions. Water demand in this densely populated area far exceeds the quantity supplied by natural precipitation; and although the population continues to grow, the already taxed water supply does not. California is projected to increase in population by nearly 10 million over the next quarter of a century with 50 percent ofthat growth centered in southern California. 3. These dry climatic conditions and winds contribute to the rapid spread of even small fires originating in high density housing or vegetation. These fires spread very quickly and create a need for increased levels of fire protection. The added protection of fire sprinkler systems will supplement normal fire department response by providing immediate protection for the building occupants and by containing and controlling the fire spread to the area of origin. Fire sprinkler systems will also reduce the use of water for firefighting by as much as 50 to 75 percent. Tonogranhical conditions: 1. Traffic and circulation congestion is an artificially created, obstructive topographical condition which is common in the City of San Juan Capistrano and throughout Orange County. 2. These topographical conditions combine to create a situation which places fire department response time to fire occurrences at risk, and makes it necessary to provide automatic on-site fire -extinguishing systems to protection occupants and property. 3. The increased pressure is necessary for the system to function utilizing the standard Orange County Fire Authority equipment. It is also necessary to compensate for the design factors which created the inadequate standpipe system design at the fatal fire in Philadelphia, Pennsylvania, on February 23, 1991. The amendments address the issues which were brought forth in this fire. They are consistent with the Los Angeles City and County Fire Departments' requirements and reflect changes which are proposed to the national standard for standpipe design, NFPA 14. Geological conditions: 1. The City of San Juan Capistrano is located in an area of high seismic activity. The Newport -Inglewood Fault, located northwest of the City, poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the city's degree of urbanization and close proximity to a major fault, the risk of structural damage and loss of life 12 - 343 due to ground shaking is considerable. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake fire department resources would be extremely taxed, and the ability to respond to fires would be complicated and in some cases impossible. On-site fire -extinguishing systems would provide a degree of protection from fires even if water mains are damaged or destroyed. 5. NFPA 24, 1992 Edition, Standard for Private Fire Service Mains and Their Appurtenances is amended to cover Installation Work, Public Water Systems, Fire Department Connections, Post Indicator Valves, Valves in Pits, Sectional Valves, Coating and Lining of Pipe, Pipe Joint Assembly, and Testing Underground Systems. These amendments are reasonably necessary because of the following conditions: Climatic conditions: 1. The City of San Juan Capistrano is located in a semi -arid Mediterranean type climate. It annually experiences extended periods of high temperatures with little or no precipitation. Hot, dry foehn (Santa Ana) winds, which may reach speeds up to 70 m.p.h, are also common to the area. These climatic conditions cause extreme drying of vegetation and common building materials and predispose the area to large destructive fires (conflagration). 2. The climate in the City of San Juan Capistrano alternates between extended periods of drought and brief flooding conditions. Water demand in this densely populated area far exceeds the quantity supplied by natural precipitation; and although the population continues to grow, the already taxed water supply does not. California is projected to increase in population by nearly 10 million over the next quarter of a century with 50 percent of that growth centered in southern California. 3. These dry climatic conditions and winds contribute to the rapid spread of even small fires originating in high density housing or vegetation. These fires spread very quickly and create a need for increased levels of fire protection. The added protection of fire sprinkler systems will supplement normal fire department response by providing immediate protection for the building occupants and by containing and controlling the fire spread to the area of origin. Fire sprinkler system will also reduce the use of water for firefighting by as much as 50 to 75 percent. This is the only method of water conservation available for firefighting activities. IN 344 ••T .• 1. Traffic and circulation congestion is an artificially created, obstructive topographical condition which is common in the City of San Juan Capistrano and throughout Orange County. 2. These topographical conditions combine to create a situation which places fire department response time to fire occurrences at risk, and makes it necessary to provide additional on-site fire fighting resources to protect occupants and property. 1. The City of San Juan Capistrano is located in an area of high seismic activity. The Newport -Inglewood Fault, located west of the city, poses the greatest hazard to life and property. It is believed that this fault is capable of generating a maximum credible 7.5 magnitude earthquake. Because of the city's degree of urbanization and close proximity to a major fault, the risk of structural damage and loss of life due to ground shaking is considerable. This threat is compounded by the city's location on the Norwalk fault. 2. Major earthquakes are always accompanied by disruption of traffic flow and fires. During a major earthquake fire department resources would be extremely taxed, and the ability to respond to fires would be complicated and in some cases impossible. On-site fire -extinguishing systems would provide a degree of protection from fires even if water mains are damaged or destroyed. 3. Soil conditions throughout the Orange County area and the City are extremely corrosive and have an adverse effect on underground fire sprinkler system piping, joints, and valves. SECTION 2. Amendments—Chapter 2 "Fire Prevention" of Title 4 "Public Safety" of the Municipal Code is amended in its entirety. Chapter 2, Fire prevention, of Title 4, Public Safety, of the Municipal Code is amended in its entirety to read as follows: "Chapter 2, FIRE PREVENTION Sec. 4-2.01. Adoption of the Uniform Fire Code. There is hereby adopted by the San Juan Capistrano City Council for the purpose of prescribing regulations governing conditions hazardous to 14 345 life and property from fire or explosion, that certain code and standards known as the "Uniform Fire Code 1994 edition, as published by the International Fire Code Institute, and the whole thereof, including Appendices I -B through V-A, VI -A, VI -E, and VI -G thereof, excluding Appendix II -H and IV -A, and the 1994 Uniform Fire Code Standards, including Appendix A -II -F, save and except such portions as are herein after added, deleted, modified, or amended of which Code and Standards, one copy is now on file in the office of the City Clerk, and the same are hereby adopted and incorporated as fully as if set forth at length herein; and the provisions thereby shall be controlling within the limits of the incorporated area of the City of San Juan Capistrano. Sec. 4-2.02 Enforcement—Inspections. 1. The Uniform Fire Code shall be enforced by the Orange County Fire Authority which shall be operated under the supervision of the Director of Fire Services of the Orange County Fire Authority. 2. The Director of Fire Services of the Fire Authority may detail such members of the fire authority as inspectors as shall be necessary from time to time. AMENDMENTS The 1994 Uniform Fire Code and Uniform Fire Code Standards adopted by this Ordinance are hereby amended as follows: Sec. 4-2.03. Article 1 amended. ARTICLE 1—ADMINISTRATION is hereby amended as follows: Section 103.2.1.1 General is hereby amended by adding a final paragraph as follows: Section 103.2.1.1 General. The building official and fire official shall work in cooperation to enforce the amendments to the following sections: Section 901.4.4 Premises Identification Section 1003 Required Installations of Automatic Fire -extinguishing Systems Section 1004 Standpipes, Where Required Section 1008 High-rise Buildings Section 1109.7 Sparks from Chimneys 346 Section 103.3.2 New construction and alterations is hereby amended by adding new Sections 103.3.2.3 and 103.3.2.4 as follows: with the code provisions for new construction. Section 103.3.2.4 Fire Protection Information on Plans and show the following: 1. 2. prior to the plan shall street width dimensions as per Section 902.2.2.7 of this code. proposed development. 3. The location, occupancy classification, and use of structures and buildings on properties abutting the proposed development. concurrent with the submittal for approval of any tentative map. Modification Plan Guidelines For High Fire Hazard Areas. this section. Section 103.4.4 Citations is hereby deleted and the following substituted: Section 103.4.4 Penalty for violation R1 347 Section 103.4.4.1 Infraction. Except as provided in Section 103.4.4.2, persons operating or maintaining any occupancy, premises or vehicle subject to this code who shall permit any fire or life safety hazard to exist on premises under their control shall be guilty of an infraction. Section 103.4.4.2 Misdemeanor. Persons who fail to take immediate action to abate a fire or life safety hazard when ordered or notified to do so by the chief or a duly authorized representative, or who violate the following sections of this code, shall be guilty of a misdemeanor: 103.4.3 Compliance with Orders, Notices and Tags 104.1.2 Interference 1001.6 Tampering with Fire -protection Equipment, Site Barriers, Security Devices, Signs and Seals 1109.5 Burning Objects 1302.3 False Alarms 2501.16 & 3215 Maximum Occupant Load 7701.7 Prohibited and Limited Acts Section 103.4.4.3 Separate Offense. Each violation will be deemed a separate offense for each and every day or portion thereof during which any violation of any of the provisions of this chapter or of the code adopted hereby is committed, continued or permitted by such person, firm, partnership or corporation and shall be deemed punishable therefor as provided in this code. Section 105.8 Permit Required is hereby amended by adding the following ending sentence to the first paragraph and by adding new and deleting permit categories as follows: Section 105.8 Permit Required. Permit fees to the City shall be in an amount established by resolution of the City Council. j A new Subsection b.l Battery systems is added as follows: -I! b2. Renumber existing b.l Bowling pin or alley refinishing to b.2. f.1. Subsection f.l. Fire hydrants and water -control valves is deleted without substitution. 17 348 f.5. Subsection f.5. Fumigation or thermal insecticidal fogging is hereby deleted without substitution. g.l. A new Subsection g.l. General use permit is added as follows: g.l. General use permit. To conduct an activity or operation=that is not specifically addressed by other permits, but which is likely to produce conditions hazardous to life or property. o.l. Subsection o.l Open burning is amended by adding the following sentence: Open burning permits shall include: 1. Bonfires/ rubbish fires, including construction sites. 2. Recreational fires/burning in a public place. 0.4. New Subsection o.4 Open flame devices in marinas is added as follows: 0.4 Open flame devices in marinas. To use any open flame devices for repair or maintenance in marinas, or for lighting or decoration on the exterior of any boat, slip or wharf. 0.5. New Subsection o.5 Oil and natural gas wells is added as follows: 0.5 Oil and natural gas wells. To drill, own, operate, or maintain an oil or natural gas well. r.l. New Subsection r.1 Rifle range is added as follows: r.1 Rifle range. To establish, maintain, or operate a rifle range. Sec. 4-2.04 Article 2 amended. ARTICLE 2—DEFINITIONS AND ABBREVIATIONS is hereby amended by adding the following new definitions: SECTION 203—B ••• •• .... • a_e... • • vMT-Te •U11PI @I• I I • •• t•n •. • t• •CZMMM-tV-JW1JWM-9JM4 cells determines the discharge .. of battery. 19 349 SECTION 205—D DIRECTOR OF FIRE SERVICES is the chief. SECTION 207—F SECTION 216-0 SECTION 219—R SECTION 223—V VEHICLE FUELING APPLIANCE is a listed natural gas compressor ., .n . .. .. .. s topography, density which potentially increases the possibility of w-ildland conflagration Sec. 4-2.05. Article 9 amended. ARTICLE 9—FIRE DEPARTMENT ACCESS AND WATER SUPPLY is hereby amended as follows: 19 SSU Section 901.4.2 Fire Apparatus Access Roads is hereby deleted and the following substituted: • 1.• • •• . • •.� 1 •• �• •. �• • e• . •• �. •. a• 1 • •• Il•< -• •q •• • �' • • •• . • • • • . s • • • • • • . on • •• Section 901.4.4 Premises Identification is hereby deleted and the following substituted: Section 901.4.4 Premises Identification. Approved numbers or addresses shall be placed on all new and existing buildings in such a position that is plainly visible and legible from the street or road fronting the property. Said numbers shall be of non-combustible materials and shall contrast with their background. All multi -unit residential and commercial buildings shall have numbers or addresses placed above or immediately adjacent to all doors that would allow fire department access in an emergency situation. In no case shall the numbers be less than 4 inches (102 mm) in height for residential and 6 inches (152 mm) in height for commercial with a 1 inch (25 mm) stroke. Multiple residential and commercial units having entrance doors not visible from the street or road shall, in addition, have approved numbers grouped for all units within each structure and positioned to be plainly visible from the street or road. Said numbers may be grouped on the wall of the structure or on a substantial mounting post independent of the structure. Illumination shall be provided as required by the City. Section 902.2.1 Required Access is hereby amended by adding the following to the beginning of the first paragraph after the exceptions: Section 902.2.1 Required access. A minimum of two fire apparatus access mark shall be provided in residential developments containing 150 or more dwelling units. 20 351 Section 902.2.2 Specifications is hereby amended by deleting Sections 902.2.2.3 and 902.2.2.6 and replacing them with three new sections as follows: 38 feet (11 582 mml outside radius. larggr turning radii as approved by the chief. shall not exceed 1 percent. dwellings and not exceeding 150 feet (45 720 mm) in length shall not be less than 24 feet (Z, 15 m in width. Section 902.2.4 Obstruction and Control of Fire Apparatus Access is hereby amended by adding Section 902.4.3 as follows: SECTION 903—WATER SUPPLIES AND FIRE HYDRANTS is hereby amended by adding an ending paragraph to Sections 903.2 and 903.4.1.2 as follows: Section 903.2 Required Water Supply for Fire Protection. Private dwellings exceeding 3,600 square feet (335 m2) in total area shall be evaluated for fire flow requirements by the chief. i •1 t: u t , •• . :•• • II .•• •• • s ••_. Sec. 4-2.06. Article 10 amended. ARTICLE 10—FIRE-PROTECTION SYSTEMS AND EQUIPMENT is hereby amended as follows: 21 percent when all structures served by the access road are protected by an anproved automatic fire si2rinklprsystem. dwellings and not exceeding 150 feet (45 720 mm) in length shall not be less than 24 feet (Z, 15 m in width. Section 902.2.4 Obstruction and Control of Fire Apparatus Access is hereby amended by adding Section 902.4.3 as follows: SECTION 903—WATER SUPPLIES AND FIRE HYDRANTS is hereby amended by adding an ending paragraph to Sections 903.2 and 903.4.1.2 as follows: Section 903.2 Required Water Supply for Fire Protection. Private dwellings exceeding 3,600 square feet (335 m2) in total area shall be evaluated for fire flow requirements by the chief. i •1 t: u t , •• . :•• • II .•• •• • s ••_. Sec. 4-2.06. Article 10 amended. ARTICLE 10—FIRE-PROTECTION SYSTEMS AND EQUIPMENT is hereby amended as follows: 21 35'2 Section 1001.1 Scope is hereby amended by adding a paragraph as follows: Section 1001.1 Scope. The regulations of the State Fire Marshal apply to the testing, service, maintenance and licensing of service personnel for automatic fire extinguishing systems, portable fire extinguishers and standpipes (19 CCR Chapters 3 and 5). Section 1001.5 Maintenance is hereby amended by adding Section 1001.5.5 Installation and maintenance as follows: Section 1001.5.5 Installation and Maintenance. It shall be the responsibility of the owner of an occupancy to supply, install and maintain all required smoke detectors. The owner shall be responsible for the annual testing of all required smoke detectors. SECTION 1003—FIRE EXTINGUISHING SYSTEMS is hereby amended as follows: Section 1003.1.2 Standards is hereby deleted and the following substituted: Section 1003.1.2 Standards. Automatic fire -extinguishing systems shall be installed in accordance with the NFPA standards as adopted in Appendix V of this code. An approved automatic sprinkler system required by Section 1003 and installed as per NFPA 13- as adopted in Appendix V this code, may be used for fire -resistive substitution as specified in the provisions of Section 508 of the adopted Uniform Building Code. ON 3S"s When an approved residential sprinkler system is provided as specified in NFPA 13D or 13R as adopted in Appendix V of this code, exceptions to, or reductions in, code requirements allowed as a result thereof by Section 508 of the adopted Uniform Building Code shall not be permitted. Section 1003.2.2 Required Installations of Automatic Fire -extinguishing Systems, All Occupancies except Group R, Division 3, and Group U is amended by deleting the words 'Division 3, and Group U," and adding an item 6 and adding Group U Occupancies to this section as follows: Section 1003.2.2 Required Installation of Automatic Fire - extinguishing Systems, All Occupancies except Group R. 6. In all new buildings or structures when the gross square footage thereof exceeds 6,000 square feet (588 m2) or more than 2 stories in height. For the purposes of this section, area separation walls shall not define separate buildings. Section 1003.2.3.1 Drinking establishments is hereby deleted without substitution and the section number left open. Section 1003.2.3.3 Exhibition and display rooms is hereby deleted without substitution and the section number left open. Section 1003.2.7 Group M Occupancies is hereby deleted without substitution and the section number left open. Section 1003.2.8 Group R Occupancies is hereby deleted and the following substituted: Section 1003.2.8 Group R Occupancies. Section 1003.2.8.1 Group R, Division 1 Occupancies. All new Group R, Division 1 Occupancies shall be equipped with an approved automatic sprinkler system. Residential or quick - response standard sprinkler heads shall be used in the dwelling unit and guest room portions of the building. For the purposes of this section, area or occupancy separation walls shall not define separate buildings. 23 354 161M IMMMAIVIRMIR Met • 11 19 Eor the purposes of this section. area or occupancy separatio walls shall not define sei2arate [of MW MoM Section 1003.2 Required Installations is hereby amended by adding Section 1003.2.9 as follows: SECTION 1004 — STANDPIPES is hereby amended by deleted Section 1004.2 Required Installation and substituted with the following: Section 1004.2 Required Installations. Standpipe systems shall be provided as set forth in Table No. 1004—A and the provisions of this section. Every new building with any horizontal dimension greater than 300 feet (91 440 mm) shall be provided with either access doors or hose outlets located so that all portions of the building can be reached with 150 feet (45 720 mm) of hose from an access door or hose outlet. Required access doors shall be located in the exterior wall of the building and shall be accessible without the use of a ladder. The door dimensions shall be not less than 3 feet (914 mm) in width nor 6 feet 8 inches (2032 mm) in height. The hose outlets shall be 2-1/2 inches (63 mm) in size with an approved valve. The water supply for the hose outlets shall be provided: 24 355 1. By a separate main supplied from the system side of the check valve at the fire department connection, or 2. From an adjacent section of the sprinkler system arranged to allow the hose outlets to deliver water when the sprinkler system, or a portion of the system that protects the area served by the hose outlet, is shut off. SECTION 1007 — FIRE ALARM SYSTEMS is hereby amended by adding two sections as follows: Section 1007.1.5 Voltage Drop. Fire alarm systems shall be designed so that the maximum voltage loss is not greater than 10 percent. Section 1007.1.6 Other Requirements. Fire alarm equipment shall comply with the regulations of the State Fire Marshal (19 CCR Chapter 4, 24 CCR). SECTION 1008 — SPECIAL PROVISIONS FOR HIGH-RISE BUILDINGS is hereby amended as follows: Section 1008.1 Scope. In addition to other applicable requirements of these regulations, the provisions of this section shall apply to every new building of any type of construction or occupancy having floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department access. Such buildings shall be provided with an automatic sprinkler system installed in accordance with Section 1008.3 of this code. EXCEPTIONS: The following structures, while classified as high-rise buildings, shall not be subject to the provisions of this section but shall conform to all other applicable provisions of these regulations: 25 356 1. Buildings used exclusively as open parking garages. 2. Buildings where all floors above the 55 -foot (16 764 mm) level are used exclusively as open parking garages. 3. Floors of buildings used exclusively as open parking garagesand located above all other floors used for human occupancy. 4. Buildings such as power plants, lookout towers, steeples, grain houses and similar structures with noncontinuous human occupancy, when approved by the chief. For the purpose of this section, "building access" shall mean an exterior door opening conforming to all of the following: 1.1 Suitable and available for fire department use. 1.2 Located not more than 2 feet (610 mm) above the adjacent ground level. 1.3 Leading to a space, room or area having foot traffic communication capabilities with the remainder of the building. 1.4 Designed to permit access through the use of the Orange County Fire Authority's Emergency Access Lock Box Program. Section 1008.2 Certificate of Occupancy. All mechanical and electrical equipment and other required life safety systems shall be approved and installed in accordance with approved plans and specifications pursuant to this section and shall be tested and proved to be in proper working condition to the satisfaction of the Building Official before issuance of the Certificate of Occupancy. Such systems shall be maintained in accordance with Title 19 CCR, and the Fire Code. Section 1008.3 Automatic Sprinkler System. The provisions of Section 403.2 of the adopted Uniform Building Code and the provisions contained in this section shall apply to buildings described in Section 1008.1. Sprinkler Control Valves. Sprinkler control valves, shutoff valves and a water -flow detecting device shall be provided at the lateral connection to the riser for each floor. Such valves and devices shall be electrically supervised to automatically sound an appropriate signal transmitted to locations in accordance with Section 1008.5. W. 3S7 Section 1008.4 Smoke Detection. The provisions of Section 403.3 of the adopted Uniform Building Code and the provisions contained in this section shall apply to buildings described in Section 1008.1. Indicating Lights. All smoke detectors connected to the alarm s stem shall have a light that indicates the status of the detector. When a detector is located in a space above a drop ceiling, the indicating light shall be located on or below the ceiling grid. Section 1008.5 Alarm and Communications Systems. Every high-rise building shall be provided with a State Fire Marshal -approved and listed fire alarm system. The alarm and communication systems shall be designed and installed so that damage to any one speaker will not render any paging zone of the system inoperative. The voice alarm and public address system may be a combined system. When approved by the fire department, communication systems may be combined with the voice alarm system and the public address system. The fire alarm system shall include visual indicators for the hearing impaired in all public areas of the building, including but not limited to elevators, elevator lobbies, rest rooms, corridors, exit stairways, rooms and tenant spaces exceeding 1,000 square feet (93 m2) in area. 5.1. Voice alarm system. The operation of any smoke detector, sprinkler, water flow device or manual fire alarm station shall automatically sound an alert signal to the desired areas, followed by voice instructions giving appropriate information and direction to the occupants. Upon activation of the automatic sprinkler system, any automatic fire -detection device required by this section or any special hazard fire -protection or extinguishing system, an automatic voice alarm signal shall sound on the floor where activated and on the floor above and below. An audible and visual signal shall be transmitted to the central control station and the fire department central control station status board. The content of the voice alarm in each instance shall be determined by the fire department in cooperation with the building owner or manager. The central control station shall contain controls for the voice alarm system so that a selective or general voice alarm may be manually initiated. 27 M The system shall be supervised to cause the activation of an audible trouble signal in the central control station upon interruption or failure of the audio path, including amplifiers, speaker wiring, switches and electrical contacts and shall detect opens, shorts and grounds which might impair the function of the system. The alarm shall be designed to be heard clearly by all occupants within the building or designated portions thereof, as required for the public address system. EXCEPTION: In lieu of a voice alarm signal and when approved by the fire department, the local alarm system may employ any sounding device or devices which are approved and listed by the State Fire Marshal. The sounding devices of such alternate systems shall have a distinctive tone and shall be arranged to emit intermittent, prolonged or continuous sound signals for a full period of 10 seconds, to be immediately followed by an intermission or period of silence of 5 seconds before the signal is repeated. Such signal shall continue to sound until manually terminated at the central control station, but in no case shall such manual operation be arranged to cause termination in less than 3 minutes. 5.2. Public address system. Speakers or signaling devices used to sound the voice or fire alarm shall be so located as to be clearly heard on the floor where activated, except as may be otherwise found necessary or acceptable by the chief. A public address communication system designed to be clearly heard by all occupants of the building shall operate from the central control station. It shall be established on a selective or general basis, as approved by the chief, to the following paging areas: 5.2.1 Elevators 5.2.2 Elevator lobbies 5.2.3 Corridors 5.2.4 Exit stairways 5.2.5 Rooms and tenant spaces exceeding 1,000 square feet (93 m2) in area 5.2.6 Dwelling units in apartment houses 5.2.7 Hotel guest rooms or suites EI3 359 5.3. Fire department communication systems. A two-way fire department communication system shall be provided for fire department use. It shall operate between the central control station and elevators, elevator lobbies, emergency and standby power rooms and on the stairway side of entries to every enclosed exit stairway. The communication system shall also comply with the following: 5.3.1 Alarm transmission. Unless the central control station is constantly staffed by competent and experienced operating personnel conforming to Chapter 9 of NFPA 72 as adopted in Appendix V of this code, voice or fire alarm and trouble signals shall be automatically retransmitted to one of the following: 5.3.1.1. An approved central station conforming to NFPA 71 as adopted by the State Building Standards Commission. 5.3.1.2. A supervisory station or an approved remote station conforming to NFPA 72 as adopted by the State Building Standards Commission. 5.3.2 Special provisions. In Group R, Division 1 occupancies: 5.3.2.1. When a building conforms to the provisions of this section, the manually operated fire alarm system otherwise specified by Section 1007.2.9 shall not be required. 5.3.2.2. Single -station detectors installed in dwelling units and hotel or lodging house guest rooms, as specified in Section 1007.2.9.2, need not be interconnected to the fire alarm system required by this section. Section 1008.6 Central Control Station. A central control station for fire department operations shall be provided in a location approved by the fire department. The central control station shall be separated from the 09 36U remainder of the building by not less than one-hour fire -resistive construction with all openings protected by assemblies having a fire - resistive rating of not less than 45 minutes. It shall have a minimum of one door which is accessible directly from the exterior portion of the building and shall be able to be opened with a fire department master key. The central control station shall have a minimum of 100 square feet (9.3 m2) with a minimum dimension of 8 feet (2438 mm). It shall contain the following as a minimum: 6.1 The voice alarm and public address system panels. 6.2 The fire department communications panel, a cabinet containing 8 portable firefighter phones and 1 headset with sufficient cord to reach all portions of the room. 6.3 Fire detection and fire alarm system annunciator panels. 6.4 Annunciator visually indicating the location of the elevators and their operational status. 6.5 Status indicators and controls for air -handling systems. 6.6 Controls for unlocking all stairway doors simultaneously. 6.7 Sprinkler valve and water -flow detector display panels. 6.8 Emergency and standby power controls and status indicators. 6.9 A wall -mounted telephone, with sufficient cord to reach all portions of the room and with an outside dedicated private line, installed in the fire control room for exclusive fire department use. 6.10 Elevator control switches for switching to emergency power. 6.11 Fire pump status panel and controls. 6.12 Other fire -protection equipment and systems' controls as required by the fire department. 6.13 Schematic building plans in clearly labeled approved containers, indicating the typical floor plan and detailing the building core, fire resistive separations, exit facilities, on-site water supply, fire -protection systems, firefighting equipment and fire department access. 30 361 6.14 One 3 foot (914 mm) by 5 foot (1524 mm) table and 2 chairs. 6.15 An approved locked and labeled cabinet containing labeled keys for emergency access and elevator control. All control panels in the central control station shall be permanently identified as to function. Alarms, supervisory and trouble signals as required by Items 3 and 7 above shall be annunciated in compliance with this code in the central control station by means of an audible and visual indicator. For purposes of annunciation, zoning shall be in accordance with the following: 6.16 When the system serves more than one building, each building shall be considered separately. 6.17 Each floor shall be considered a separate zone. When one or more sprinkler risers serve the same floor, each riser shall be considered a separate zone. EXCEPTION: When more than one riser serves the same system on the floor. 6.18 Each section of floor separated by area separation walls or by horizontal exits shall be considered as a separate zone. Central control stations shall not be used for the housing of any boiler, heating unit, generator or similar hazardous equipment. No storage shall be permitted in the central control station room. Section 1008.7 Smoke Control. The provisions of Section 905 Smoke Control of the adopted Uniform Building Code shall apply to buildings described in Section 1008. Section 1008.8 Elevators. The provisions of Sections 403.7 and 1005.10 of the adopted Uniform Building Code shall apply to buildings described in Section 1008.1. Section 1008.9 Standby Power, Light and Emergency Systems. Section 403.8.2 of the adopted Uniform Building Code and Sections 1008.9.1 and 1008.9.3 of this code shall apply to buildings described in Section 1008.1. 31 362 Section 1008.9.1 Standby Power. A standby power -generating system, as approved by the building official and chief and conforming to Section 403.8.1 of the adopted Uniform Building Code, shall be provided. The system shall be equipped with suitable means for automatically starting the generator upon failure of the normal electrical supply systems and for automatic transfer of all functions required by this section at full power within 60 seconds of such normal service failure. System supervision with manual start and transfer override features shall be provided at the central control station. An on -premises fuel supply sufficient for not less than 6 hours at full -demand operation of the system shall be provided. Where fire pumps are required, an 8 -hour fuel supply shall be provided. The standby system shall have a capacity and rating that would supply all equipment required to be operational at the same time. The generating capacity need not be sized to operate all the connected electrical equipment simultaneously. All power, lighting, signal and communication facilities specified in Sections 1008.4, 1008.5, 1008.6, 1008.7, 1008.8, 1008.9, and 1008.10, as applicable; fire pumps, required to maintain pressure; stair pressurization fans; standby lighting; and normal circuits supplying exit signs and exit illumination shall be transferable to the standby source. Section 1008.9.2 Standby Lighting. See the adopted Uniform Building Code. Section 1008.9.3 Emergency Systems. The following are classified as emergency systems and shall operate within 10 seconds of failure of the normal power supply: 3.1. Required exit sign and exit illumination 3.2. Elevator car lighting 3.3. Fire alarm system 3.4. Fire -detection system 3.5. Sprinkler alarm system When the standby power -operation system reaches full operating capacity, the emergency electrical systems and equipment shall be transferred thereto. Section 1008.10 Exits. Exits shall comply with the requirements of the adopted Uniform Building Code and the following: 32 563 Section 1008.10.1. All stairway doors which are locked from the stairway side shall have the capability of being unlocked simultaneously without unlatching upon a signal from the central control station. Upon failure of electrical power, the locking mechanisms shall be retracted to the unlocked position. Section 1008.10.2. When stairway doors are locked from the stairway side, a telephone or other two-way communications system, connected to an approved emergency service which operates continuously, shall be provided at not less than every fifth floor in each stairway. Section 1008.10.3. All enclosed exit stairways shall be equipped with a barometric dampered relief opening at the top. The stairway shall be supplied mechanically with sufficient air to discharge a minimum of 2,500 cubic feet per minute (1180 L/s) through the relief opening while maintaining a minimum positive pressure of 0.05 -inch water column (12.44 Pa) in the stairway relative to atmospheric pressure with all doors closed. Activation of the mechanical equipment shall be initiated by a smoke detector installed outside the stair enclosure and within 5 feet (1524 mm) of the enclosure door. Such equipment shall also be activated by actuation of the automatic sprinkler system. Operation of ventilating equipment shall also be in accordance with the adopted Uniform Building Code, Section 1009.7. Section 1008.11 Seismic Considerations. The provisions of Section 403.10 of the adopted Uniform Building Code shall apply to buildings described in Section 1008.1. Section 1008.12 Emergency Access and Evacuation Facility. This section shall apply to any Group B or Group R occupancies having floors used for human occupancy located 75 feet (22 860 mm) or more above the lowest level of fire department access. Such structures shall be equipped with a fire department -approved emergency helicopter landing pad for use by police, fire and emergency medical helicopters only. EXCEPTION: Buildings with a roof slope greater than 4 in 12 and having all exits provided with smokeproof enclosures in accordance with Section 1008.13 as adopted in this code. 33 364 Section 1008.12.1 Heli -pad. The roof area shall include an emergency access and evacuation facility for helicopters of not less than 15,000 pounds (6803.8 Kg) gross weight. This facility shall have a touchdown pad of at least 50 feet (15 240 mm) by 50 feet (15 240 mm) and a clear unobstructed landing and takeoff area with a minimum dimension of 100 feet (30 480 mm) by 100 feet (30 480 mm). Section 1008.12.2 Construction. The landing pad shall be designed per Section 1609.3 of the adopted Uniform Building Code. Helicopter landing areas and supports shall be of noncombustible construction. Section 1008.12.3 Approach -departure Paths. The emergency evacuation facility shall have 2 approach -departure paths at a slope of no greater than 8 to 1. Section 1008.12.4 Restricted Use. Any use of this emergency access and evacuation facility for purposes other than emergency access and evacuation shall require prior approval by the Federal Aviation Administration, as well as by the building official and the chief. Section 1008.12.5 Wind Direction Device. A wind indicating device shall be provided. Section 1008.12.6 Special Markings. The roof top shall be marked by an emergency marker as required by the chief. Section 1008.12.7 Communications. The building emergency communication system shall extend to the roof. Section 1008.13 Smokeproof Enclosures. This section shall apply as required by Section 1008.12. Section 1008.13.1 General. A smokeproof enclosure shall consist of a vestibule and continuous stairway enclosure from the highest point to the lowest point by walls of 2 -hour fire -resistive construction. There shall be no openings into the stairway portion of the smokeproof enclosure other than those permitted by the first paragraph of Section 1009.3 of the adopted Uniform Building Code. The supporting frame shall be protected as set forth in Table 6-A of the adopted Uniform Building Code. In buildings with air-conditioning systems or pressure air supply serving more than one story, an approved smoke detector shall be placed in the return -air duct or plenum prior to exhausting from 34 Sbb the building or being diluted by outside air. Upon activation, the detector shall cause the return air to exhaust completely from the building without any recirculation through the building. Such devices may be installed in each room or space served by a return - air duct. Section 1008.13.2 Where Required. Smokeproof enclosures shall be required as per Section 1008.12. Section 1008.13.3 Outlet. A smokeproof enclosure shall exit into a public way or into an exit passageway leading to a public way. The exit passageway shall be without other openings and shall have walls, floors and ceiling of 2 -hour fire -resistive construction. Section 1008.13.4 Barrier. A stairway in a smokeproof enclosure shall not continue below the grade level unless an approved barrier is provided at the ground level to prevent persons from accidentally continuing into the basement. Section 1008.13.5 Access. Access to stairways in smokeproof enclosures shall be by way of a vestibule or open exterior exit balcony constructed of noncombustible materials. Section 1008.13.6 Smokeproof Enclosure by Natural Ventilation Section 1008.13.6.1 Doors. When a vestibule is provided, the door assembly into the vestibule shall have a 1-1/2 hour fire - protection rating, and the door assembly from the vestibule to the stairs shall be a smoke- and draft -control assembly having not less than a 20 -minute fire -protection rating. Doors shall be equipped with an automatic closing device activated by a smoke detector. When access to the stairway is by means of an open exterior exit balcony, the door assembly to the stairway shall have a 1-1/2 hour fire -protection rating and shall be maintained automatic closing by actuation of a smoke detector. Section 1008.13.6.2 Open-air Vestibule. The vestibule shall have a minimum dimension of 44 inches (1118 mm) in width and 72 inches (1829 mm) in direction of exit travel. The vestibule shall have a minimum of 16 square feet (1.48 m2) of opening in a wall facing an exterior court, yard or public way at least 20 feet (6096 mm) in width. 35 366 Section 1008.13.7 Smokeproof Enclosure by Mechanical Ventilation 1008.13.7.1 Doors. The door assembly from the building into the vestibule shall have a 1-1/2 hour fire -protection rating, and the door assembly from the vestibule to the stairway shall be a smoke- and draft -control assembly having not less than,,,a 20 minute fire -protection rating. The door to the stairways shall be provided with a drop sill or other provisions to minimize the air leakage. Doors shall be maintained automatic closing by activation of a smoke detector or in the event of a power failure. 1008.13.7.2 Vestibule Size. Vestibules shall have a minimum dimension of 44 inches (1118 mm) in width and 72 inches (1829 mm) in direction of exit travel. 1008.13.7.3 Vestibule Ventilation. The vestibule shall be provided with not less than one air change per minute, and the exhaust shall be 50 percent of the supply. Supply air shall enter and exhaust air shall discharge from the vestibule through separate tightly constructed ducts used only for that purpose. Supply air shall enter the vestibule within 6 inches (152 mm) of the floor level. The top of the exhaust register shall be down from the top of the smoke trap and shall be entirely within the smoke trap area. Doors, when in the open position, shall not obstruct duct openings. Duct openings may be provided with controlling dampers if needed to meet the design requirements, but are not otherwise required. 1008.13.7.4 Smoke Trap. The vestibule ceiling shall be at least 20 inches (508 mm) higher than the door opening into the vestibule to serve as a smoke and heat trap and to provide an upward -moving air column. The height may be decreased when justified by engineering design and field testing. 1008.13.7.5 Stair Shaft Air Movement System. The stair shaft shall be provided with a dampered relief opening at the top and supplied mechanically with sufficient air to discharge a minimum of 2,500 cubic feet per minute (1180 L/s) through the relief opening while maintaining a minimum positive pressure of 0.05 inches (12.44 Pa) of water column in the shaft relative to atmosphere with all doors closed and a minimum of 0.10 -inch (24.88 Pa) water column difference between the stair shaft and the vestibule. 36 1008.13.7.6 Operation of Ventilating Equipment. The activation of the ventilating equipment shall be initiated by a smoke detector installed outside the vestibule door in an approved location. The activation of the closing device on any door shall activate the closing devices on all doors of the smokeproof enclosure at all levels. When the closing device for the stair shaft and vestibule doors is activated by a smoke detector or power failure, the mechanical equipment shall operate at the levels specified in Sections 1008.13.7.3 and 1008.13.7.5. 1008.13.7.7 Standby Power. Standby power for the mechanical ventilation equipment shall be provided by an approved self- contained generator set to operate whenever there is a loss of power in the normal house current. The generator shall be in a separate room having a minimum fuel supply adequate to operate the equipment for 2 hours. See Section 403.8 of the adopted Uniform Building Code for standby power requirements for high-rise Group B offices and Group R, Division 1 occupancies. 1008.13.7.8 Acceptance Testing. Before the mechanical equipment is accepted by the code -enforcing authority, it shall be tested to confirm that the mechanical equipment is operating in compliance with these requirements. 1008.13.7.9 Emergency Lighting. The stair shaft and vestibule shall be provided with emergency lighting. A standby generator which is installed for the smokeproof enclosure mechanical ventilation equipment may be used for such stair shaft and vestibule power supply. See Section 403.8 of the adopted Uniform Building Code for emergency lighting requirements for high-rise Group B offices and Group R, Division 1 occupancies. Sec. 4-2.07. Article 11 amended. ARTICLE 11—GENERAL SAFETY PRECAUTIONS is hereby amended as follows: SECTION 1109—CONTROL OF SOURCES OF IGNITION is hereby amended by deleting Section 1109.7 Sparks from Chimneys and substituting a new Section 1109.7 as follows: 37 S0 All incinerator chimneys shall terminate in a substantially constructed spark arrester having an iron, heavy wire mesh not exceeding 1/2 inch (12.5 mm). SECTION 1111—CHANGES IN USE OR OCCUPANCY OF BUILDINGS OR STRUCTURES is hereby amended by identifying the existing paragraph as Section 1111.1 and adding a new Section 1111.2 as follows: 1 1. • 1, �.111 vartmM013. Olin�• ... • -IS- 1 We l •1wl 1Ell. .- • •. .. •1 1 •S.••. • 1114m, R• S- MR.. S. • 1 l• •• •• 1• ••1 • • • •. ARTICLE 11—GENERAL SAFETY PRECAUTIONS is hereby amended by adding new SECTION 1115—DEVELOPMENT ON OR NEAR LAND CONTAINING OR EMITTING TOXIC, COMBUSTIBLE OR FLAMMABLE LIQUIDS, GASES OR VAPORS as follows: SECTION 1115—DEVELOPMENT ON OR NEAR LAND CONTAINING OR EMITTING TOXIC, COMBUSTIBLE OR FLAMMABLE LIQUIDS, GASES OR VAPORS m 369 I gas well operation, petroleum or chemical refining facility, petroleum or chemical storage, or 2. May contain or give off toxic, combustible or flammable liquids. gases or vapors. Sec. 4-2.08. Section 1212.6 amended. Section 1212.6 Floor -level Exit Signs is hereby amended by adding a beginning paragraph as follows: Section 1212.6 Floor -level Exit Signs. The regulations and bulletins of the State Fire Marshal for floor -level exit sign requirements shall also apply. Sec. 4-2.09. Article 13 amended. ARTICLE 13 --EMERGENCY PROCEDURES is hereby deleted and the following substituted: Sec. 4-2.10. Section 2501 amended. SECTION 2501—GENERAL is hereby amended by adding an ending paragraph to Section 2501.5 Decorative Materials and by adding two new sections as follows: Section 2501.5 Decorative Materials. Records of fire -retardant treatment, as per the requirements of C.C.R. Title 19, shall be maintained on the premises by the owner. agent. proprietor or occupant. Section 2501.16.4 Occupant Count. The supervisor of each place of assembly shall have an effective system to keep count of the number of occupants present in the assembly area. If the chief determines at any 39 370 time that an accurate count of occupants is not being maintained, the occupancy shall be cleared until an accurate count can be made. Section 2501.20 Temporary Heaters. No person shall place or operate fire department permit. Sec. 4-2.11. Article 32 amended. ARTICLE 32—TENTS, CANOPIES AND TEMPORARY MEMBRANE STRUCTURES is hereby amended as follows: SECTION 3201—SCOPE is hereby amended by adding a paragraph as follows: The regulations of the State Fire Marshal for large and small tents, awnings and other fabric enclosures also apply (19 CCR Chapter 2). SECTION 3207—FLAME-RETARDANT TREATMENT AND STANDARDS is hereby amended by adding a paragraph as follows: The regulations of the State Fire Marshal for flame resistance and labeling of all tents also apply (19 CCR Chapter 2, Article 4). SECTION 3210—STANDBY PERSONNEL is hereby amended by adding a paragraph to read as follows: The regulations of the State Fire Marshal for standby personnel in tents with an occupant load of 500 or more also apply (19 CCR 320). SECTION 3219—HOUSEKEEPING is hereby amended by deleting "30 feet" (9144 mm) and substituting "50 feet" (15 240 mm) in its place at each occurrence (19 CCR 326). TABLE 3205-A—LOCATION, ACCESS AND PARKING FOR TENTS, CANOPIES AND TEMPORARY MEMBRANE STRUCTURES is hereby amended by adding footnote 4 as follows: 4. Table 3205-A applies to vehicles necessary to the operation of a tent establishment. All other vehicles shall be parked at least 100 feet (30 480 mm) from any tent, except vehicles parked on a public street, which shall park at least 20 feet (6096 mm) from any tent, per the regulations of the State Fire Marshal (19 CCR 312). 40 J/1 Sec. 4-2.12. Article 47 amended. ARTICLE 47—FUMIGATION AND THERMAL INSECTICIDAL FOGGING is hereby deleted and substituted as follows: ARTICLE 47—FUMIGATION AND THERMAL INSECTICIAAL FOGGING SECTION 4701—SCOPE Fumigation and thermal insecticidal fogging operations shall be in accordance with Divisions 6 and 7 of the Food and Agriculture Code of the State of California. SECTION 4702—NOTIFICATION OF FUMIGATION The chief shall be notified in writing at least 24 hours before any building, structure or ship is to be closed in connection with the use of toxic or flammable fumigants. Sec. 4-2.13. Section 5103 amended. SECTION 5103—FABRICATION AREAS is hereby amended by adding the following ending sentence to Section 5103.5.2 Piping and tubing installation: Section 5103.5.2 Piping and tubing installation. Signage Guidelines. Sec. 4-2.14. Section 5202 -amended. SECTION 5202—FLAMMABLE AND COMBUSTIBLE LIQUID MOTOR VEHICLE FUEL -DISPENSING STATIONS is hereby amended by deleting Section 5202.3.6 Special enclosures and substituting with a new Section 5202.3.6 and by adding the following ending sentence to item 1 of Section 5202.4.4 Supervision as follows: Section. 5202.3.6 Special enclosures. When installation of tanks in accordance with Section 7902.6 is impractical, or because of property or building limitations, tanks for Class I, II, or III -A liquids may be approved by the chief for installation aboveground in buildings in special enclosures. The capacity of permanent or temporary aboveground tanks containing Class I, II, or III -A liquids shall not exceed 2,000 gallons (7570 L) aggregate, and shall conform to the requirements of Appendix II -F as ::-- amended in this code. 41 372 Section 5202.4.4 Supervision. 1. The amount of fuel being dispensed shall be limited in quantity by a pre-programmed card as approved by the chief. Sec. 4-2.15. Section 6319 amended SECTION 6319—EMERGENCY SIGNS AND LABELS is hereby amended as follows: SECTION 6319—EMERGENCY SIGNS AND LABELS. Refrigeration units or systems shall be provided with approved emergency signs, charts and labels in accordance with the Mechanical Code, I, I: r c._ a _a ;Z0 3 the OrangeCounty Fire Authority Signage Guidelines and the Mechanical Code (See U.M.C. Standard 11-2). See also Appendix VI -F. Sec. 4-2.16. Article 64 added. The Uniform Fire Code is amended by adding ARTICLE 64—STATIONARY LEAD -ACID BATTERY SYSTEMS as follows: ARTICLE 64—STATIONARY LEAD -ACID BATTERY SYSTEMS power or uninterrupted power supply shall be in accordance with this Article 80 of this code. Section 6403.1 General For a permit to install or operate battery 42 KvAl i and R Occupancies. battery systems shall be located in a room • _ • _•. }. • l• ll •!S • { •• • • 1• • 1' • �� II i• to a 12H between 7.0 and 9.0. 11 1' { 1 { • •' • • •'• • • • • • tm • • vswvm�-Ml we • It WT T Tom, of not less than I cubic foot per minute per square •• (0.0283 • per 0.0929 ._ floor area of the room. Section 6404.7 Signs. Doors into rooms or buildings containing 43 374 electrical circuits and that the battery electrolyte solutions are corrosive liquids. Sec. 4-2.17. Section 7401 amended. SECTION 7401—GENERAL is hereby amended by amending Section 7401.5.2 Stationary compressed gas containers, cylinders and tanks as follows: Section 7401.5.2 Stationary compressed gas containers, cylinders and tanks. Stationary compressed gas containers, cylinders and tanks shall be marked in accordance with r, r Standard 79 3 Orange County Fire Authority Signage Guidelines. Markings shall be visible from any direction of approach. Sec. 4-2.18. Article 77 amended. ARTICLE 77—EXPLOSIVE MATERIALS is hereby amended as follows: SECTION 7701—GENERAL is hereby amended by adding a new section as follows: Section 7701.9 Other Regulations. The regulations of the State Fire Marshal for explosives also apply (19 CCR Chapter 10 and 24 CCR Part 2). Appendix VI -E of the UFC is adopted and shall be used for determining the location of magazines. Whenever the words "See Appendix VI -E" appear, it shall mean "Apply Appendix VI -E." Section 7702.1.1 Magazines required is hereby amended by adding a sentence as follows: Section 7702.1.1 Magazines required. The regulations of the State Fire Marshal for magazine quantity limitations also apply (19 CCR 1566.4). 44 3/b Section 7702.1.9 Storage with other materials is hereby amended by adding a sentence as follows: Section 7702.1.9 Storage with other materials. Blasting caps, electric blasting caps, detonating primers and primed cartridges shall not be stored in the same magazine with other explosives (19 CCR 1566.1). Section 7702.1.15 Yard maintenance is hereby amended by deleting "25 feet" (7620 mm) and substituting "50 feet" (15 240 mm) in its place (19 CCR 1566.2). Section 7702.2 Retail Sales is hereby amended by adding a second paragraph to Section 7702.2.1 General as follows: Section 7702.2.1 General. The regulations of the State Fire Marshal for magazines within buildings also apply (19 CCR 1566.6). Section 7702.3 Storage Magazines is hereby amended by adding the following paragraphs to Sections 7702.3.1 General and 7702.3.10 Indoor magazines: Section 7702.3.1 General. The regulations of the State Fire Marshal for magazine classification, quantity limitations and construction also apply. The provisions of this section may be used in place of the State Fire Marshal regulations for classification and construction of magazines, if determined to provide an acceptable alternative protection by the chief (19 CCR Chapter 10, Subchapters 3 and 5). Section 7702.3.10 Indoor magazines. The regulations of the State Fire Marshal for magazines within buildings also apply (19 CCR 1566.6). Section 7703.1 Use and Handling is hereby amended by adding the following paragraphs to Sections 7703.1.7 Other regulations and 7703.1.9 Premature detonation safeguards: Section 7703.1.7 Other regulations. The regulations of the State Fire Marshal for use and handling of explosives also apply (19 CCR Chapter 10, Subchapter 4). Section 7703.1.9 Premature Detonation Safeguards. The regulations of the State Fire Marshal for precautions against accidental discharge also apply (19 CCR 1568.8). Section 7703.2.1 Public Conveyance is hereby amended by adding a beginning paragraph as follows: 45 5/b Section 7703.2.1 Public Conveyance. The regulations of the State Fire Marshal for transportation of explosives, including transportation in private passenger vehicles, also apply (19 CCR Chapter 10, Subchapter 4, Article 12). Section 7703.3.5 Explosive materials terminals is hereby amended by adding a beginning paragraph as follows: Section 7703.2.5 Explosive materials terminals. The regulations of the State Fire Marshal for explosives at terminals also apply (19 CCR Chapter 10, Subchapter 4, Article 9). Section 7703.5 Safety Precautions for Blasting Agents is hereby amended by adding the following paragraphs to Sections 7703.5.3 Construction and 7703.5.4 Compounding and mixing, and by adding a new Section 7703.5.7 Requirements: Section 7703.5.3 Construction. Buildings or other facilities used for the mixing of blasting agents shall be designed and constructed in accordance with the regulations of the State Fire Marshal (19 CCR Chapter 10 and 24 CCR Part 2). Section 7703.5.4 Compounding and mixing. The regulations of the State Fire Marshal for mixer design and blasting agent composition also apply (19 CCR 1572.2 and 1572.3). Section 7703.5.7 Requirements.' The regulations of the State Fire Marshal for blast hole loading, explosive initiation, and water gels, or slurry explosives also apply (19 CCR Chapter 10, Subchapter 4, Articles 7, 8, 10 and 11; and Subchapter 5, Article 17). Section 7704.6.1 Construction is hereby deleted and the following substituted: Section 7704.6.1 Construction. Operating buildings or rooms shall be constructed in accordance with the regulations of the State Fire Marshal (19 CCR Chapter 10 and 24 CCR Part 2) when quantities of explosives exceed the exempt amounts as specified in the adopted Uniform Building and Fire Codes. Section 7704.7 Operations is hereby amended by adding a beginning paragraph as follows: Section 7704.7 Operations. The regulations of the State Fire Marshal for on-site or remote processing and storage of explosives, including electrical regulations, also apply (19 CCR Chapter 10, Subchapter 4). 46 3377 Sec. 4-2.19. Section 7802 amended. SECTION 7802—FIREWORKS is hereby amended by deleting TABLE 7802.3- A—MINIMUM MORTAR SEPARATION DISTANCES without substitution, amending thefirst sentence of Section 7802.3 Prohibition, deleting Section 7802.4 Display and replacing with a new Section 7802.4 Displays, and adding a new Section 7802.5 Model Rocketry as follows: Section 7802.3 Prohibition. The storage, use, handling, possession, sale, or discharge of fireworks is prohibited. Section 7802.4 Displays. Fireworks displays shall be in accordance with the Orange County Fire Authority Guidelines for Public Fireworks Displays, with the regulations of the State Fire Marshal, and the conditions of the permit as approved by the chief (19 CCR 982). Section 7802.5 Model Rocketry. All model rocket activities shall comply with the Orange County Fire Authority Guidelines for Model Rocketry and requires a permit from the chief. Sec. 4-2.20. Article 79 amended. ARTICLE 79—FLAMMABLE AND COMBUSTIBLE LIQUIDS is hereby amended as follows: Section 7902.2.6.3.4 Reductions in required venting for stable liquids is hereby amended by deleting sub -sections 2.0.3 and 4.0.15. Section 7903.1.3 Liquid transfer is hereby amended by adding the following new section: for such extraction from the chief. Sec. 4-2.21. Article 80 amended. ARTICLE 80—HAZARDOUS MATERIALS is hereby amended as follows: Section 8001.3.3 Hazardous Materials Inventory Statement is hereby amended by adding the following paragraph: 47 378 premises. Section 8001.7 Identification Signs is hereby amended by deleting the words "T T.T .r . sstan "a 79 3" and replacing with the words "Orange County Fire Authority Signage Guidelines." Section 8001.13 Exempt Amounts is hereby amended by adding Section 8001.13.1.1 Exterior Storage as follows: Section 8001.13.1.1 Exterior Storage. section excelt as follows: 2_1 Outdoor control areas shall be protected against tampering or trespassers by fencing or other control measures. 2_2 Outdoor control areas shall be kept free of weeds, debris and common combustible materials not necessary to the storage. The area surrounding an outdoor control area shall be kept clear of such materials for a minimum of 15 feet (4572 mm). 2.3 Outdoor control areas shall be located not closer than 20 feet (6096 mm) to a prolerty line that can be built upon street alley or public way. 2.4 2.5 distance of 50 feet (15 240 mm). approved by the chief and when each group is separated by a minimum distance of 300 feet (91 440 mm). 379 TABLE 8001.13-C—EXEMPT AMOUNTS OF HAZARDOUS MATERIALS PRESENTING A PHYSICAL HAZARD—MAXIMUM QUANTITIES PER OUTDOOR AREA PER SINGLE PROPERTY UNDER SAME OWNERSHIP OR CONTROL1,2 is hereby amended by title as follows: EXEMPT AMOUNTS OF HAZARDOUS MATERIALS PRESENTING A PHYSICAL HAZARD—MAXIMUM QUANTITIES ALLOWED IN A N OUTDOOR CONTROL AREA 1,2 TABLE 8001.13-D—EXEMPT AMOUNTS OF HAZARDOUS MATERIALS PRESENTING A HEALTH HAZARD—MAXIMUM QUANTITIES PER OUTDOOR AREA PER SINGLE PROPERTY UNDER SAME OWNERSHIP OR CONTROL1,2 is hereby amended by title as follows: MATERIALS PRESENTING A HEALTH HAZARD—MAXIMUM QUANTITIES ALLOWED IN AN OUTDOOR CONTROL AREA PEV� 1,2 Section 8003.1 General is hereby amended by changing the wording of Section 8003.1.2 Signs, adding an ending paragraph to Section 8003.1.5 Maximum quantity on site, and adding a paragraph between the first and second sentence in Section 8003.1.13 Standby power as follows: Section 8003.1.2 Signs is hereby amended by deleting the words " and replacing them with the words "Orange County Fire Authority Signage Guidelines." Section 8003.1.5 Maximum quantity on site. No person shall use or store acutely hazardous materials within a residential zoned or any residential developed property. Section 8003.1.13 Section 8003.14 Corrosives is hereby amended by adding the following sentence to the end of Section 8003.14.1.1 General: Section 8003.14.1.1 General. Stationary lead -acid battery systems with individual batteries of 20 gallons (75.7 L) or less and used for standby Section 8004.1 Use, Dispensing and Handling, General is hereby amended by adding the following sentence to the end of Section 8004.1.1 Applicability and modifying Section 8004.1.9 Signs as follows: 49 3bu Section 8004.1.1 Applicability. Section 8004.1.9 Signs is hereby amended by deleting the words "U.P. - Standard 79.1" and replacing them with the words "Orange County Fire Authority Signage Guidelines." Sec. 4-2.22. Section 8704 amended. SECTION 8704—FIRESAFETY DURING CONSTRUCTION is hereby amended by deleting the existing exception in Section 8704.2 Access Roads and replacing it with the following: Section 8704.2 Access Roads. Sec. 4-2.23. Article 90 amended. ARTICLE 90—STANDARDS is hereby amended as follows: SECTION 9002—U.F.C. STANDARDS 1. U.F.C. Standards are hereby amended as follows: 9-1 Whenever UBC Standard 9-1 is referenced in this code or the UFC Standards, it shall mean UBC Standard 9-1 as adopted in the California Building Code, and further amended and adopted as NFPA 13, 1994 Edition in Appendix V. 9-2 Whenever UBC Standard 9-2 is referenced in this code or the UFC Standards, it shall mean NFPA 14, 1993 Edition, as amended and adopted in Appendix V. 9-3 Whenever UBC Standard 9-3 is referenced in this code or the UFC Standards, it shall mean UBC Standard 9-3 as adopted in the California Building Code, and further amended and adopted as NFPA 13R, 1994 Edition in Appendix V. 10-2 UFC Standard 10-2 is deleted and whenever it is referenced in this code or the UFC Standards, it shall mean NFPA 72, 1993 50 381 Edition, as adopted by the State Building Standards Commission. 10-3 UFC Standard 10-3 is deleted and whenever it is referenced in this code or the UFC Standards, it shall mean NFPA 72, 1993 Edition, as adopted by the State Building Standards Commission. 74-1 UFC Standard 74-1 Part I is adopted as specified in Appendix V; Part II is deleted and whenever it is referenced in this code or the UFC Standards, it shall mean NFPA 50, 1990 Edition, as adopted in Appendix V. 81-1 UFC Standard 81-1 Part I is adopted as specified in Appendix V; Part II is deleted and whenever it is referenced in this code or the UFC Standards, it shall mean NFPA 231, 1990 Edition, as adopted in Appendix V. 81-2 UFC Standard 81-2 Part I is adopted as specified in Appendix V; Part II is deleted and whenever it is referenced in this code or the UFC Standards, it shall mean NFPA 231C, 1991 Edition, as adopted in Appendix V. 2. U.F.C. Standard 52-1 is hereby amended by deleting Chapter 5 Residential Fueling Facilities and Chapter 6 Referenced Publications and substituting with a new Chapter 5 Residential Fueling Facilities as follows: Chapter 5 Residential Fueling Facilities 5-1 Vehicle Fueling Appliances Article 52, the Mechanical Code and the Plumbing Code as adopted. 5-1.2 For vehicle fueling permits see Section 105 of the adopted Uniform Fire Code. 51 382 l l l ming", 21 General 5-2.1.1 Vehicle fueling appliances shall be installed outside of buildings. The appliance shall be a minimum of 3 feet (914 blockage of ventilation. 1 : - t result of the opgration of a relief valve or device, restricted. accordance with the following minimum requirements: 1 Relief valves or devices shall terminate a minimum of 3 inches (914 mm) from sources of ignition. ? Relief valves or devices shall terminate a minimum of 36 inches (914 mm) horizontally and 12 inches (305 mm) 52 vertically above openings or vents into buildings or a space where flammable vapors are likely to accumulate. .. 3 Relief valves or devices shall not terminate within 5 feet (1524 mm) of sidewalks or l2aths pathsof egress, 5-2.2.4 Relief valves or devices shall be terminated so as to }prevent the entry of water insectc ice or other material 5-2.3 Hoses Me mo wq;m MMIUMMMEM Wit . . .. accordance with the following minimum requirements: PA 4. The vehicle disl2ensing hose shall be equipped with a 5-2.4 Signage IM 383 5254 e r • r . • S . . (. (. • r electrical disconnect switch. 5-3.1 The exterior and interior dispensing of natural gas into motor vehicles shall be in accordance with Section 5-3. MAMIMMm-S' . m- ItmMs S. .. . . . r. 11. -! MWIMETUMMMETTIT-Mum M-1 MIT �¢,l Installation and maintenance of vehicle fueling appliances shall be in accordance with the manufacturers' instructions and listing. 54 KKR manufacturer's instructions. SECTION 9003 is hereby amended by identifying existing SECTION'9003 RECOGNIZED STANDARDS as 9003.1, amending Section 9003.1 a.2 American National Standards Institute—ANSI Standards by adding new subsections a.2.10. ANSI/IEEE 484 and a.2.11. ANSI/IEEE 937, and adding a new Section 9003.2 Adopted NFPA Standards as follows: RMT .���/fly C • u a� Mm r 6nnii " IS Section 9003.2 Adopted NFPA Standards. See Appendix V of this code for a list of National Fire Protection Association Standards and amendments thereto, which are adopted as a part of this code. Sec. 4-2.24. Appendix I -B amended. APPENDIX I -B LIFE -SAFETY REQUIREMENTS FOR EXISTING HIGH-RISE BUILDINGS, SECTION 1—SCOPE And Section 6.1, item 2 Special Provisions and Alternatives, Automatic Sprinklers are hereby deleted and the following substituted: SECTION 1—SCOPE. These provisions apply to all existing high-rise buildings constructed prior to the adoption of this appendix, each having floors used for human occupancy located 75 feet (22 860 mm) or more above the lowest level of fire department vehicle access. Section 6.1, item 2 Automatic Sprinklers. An approved automatic fire - extinguishing system shall be installed throughout the building in accordance with the requirements of NFPA 13 as adopted in Appendix V of this code. In addition to the main water supply, a secondary on-site supply of water equal to the hydraulically calculated sprinkler design demand plus 100 gallons (378.5 L) per minute additional for the total standpipe system shall be provided. This supply shall be automatically available if the principal supply fails and shall have a duration of 30 minutes. 55 RM Sprinkler control valves and waterflow detecting devices shall be provided at the lateral connection to the riser on each floor. Sec. 4-2.25. Appendix II -A amended. APPENDIX II -A SECTION 18—UNUSUAL CIRCUMSTANCES is hereby deleted and the following substituted: SECTION 18—UNUSUAL CIRCUMSTANCES The chief may suspend enforcement and require reasonable alternative measures designed to advance the purposes of this article if he determines in any specific case that any of the following conditions exist: 18.1. Difficult terrain. 18.2. Danger of erosion. 18.3. Presence of plants included in any state and federal resources agencies, California Native Plant Society and county - approved list of wildlife, plants, rare, endangered and/or threatened species. 18.4. Stands or groves of trees or heritage trees. 18.5. Other unusual circumstances that make strict compliance with the clearance of vegetation provisions of Sections 15, 16 or 17 of this appendix undesirable or impractical. Sec. 4-2.26. Appendix II -A, Section 25 added. APPENDIX II -A SUPPRESSION AND CONTROL OF HAZARDOUS FIRE AREAS is hereby amended by adding a new SECTION 25—USE OF EQUIPMENT as follows: SECTION 25—USE OF EQUIPMENT 25.1 Except as otherwise provided in this section, no person shall use, operate, or cause to be operated, in, upon or adjoining any hazardous fire area any internal combustion engine which uses hydrocarbon fuels, unless the engine is equipped with a spark arrester as defined in Section 25.3 maintained in effec- tive working order, or the engine is constructed, equipped and maintained for the prevention of fire pursuant to Section 25.3. 60 387 25.2 Spark arresters affixed to the exhaust system of engines or vehicles subject to this section shall not be placed or mounted in such a manner as to allow flames or heat from the exhaust system to ignite any flammable material. 25.3 A spark arrester is a device constructed of nonflammable material specifically for the purpose of removing and retaining carbon and other flammable particles over 0.0232 of an inch (0.58 mm) in size from the exhaust flow of an internal combustion engine that uses hydrocarbon fuels or which is qualified and rated by the United States Forest Service. 25.4 Engines used to provide motor power for trucks, truck tractors, buses, and passenger vehicles, except motorcycles, are not subject to this section if the exhaust system is equipped with a muffler as defined in the Vehicle Code of the State of California. 25.5 Turbocharged engines are not subject to this section if all exhausted gases pass through the rotating turbine wheel, there is no exhaust bypass to the atmosphere, and the turbocharger is in effective mechanical condition. Sec. 4-2.27. Appendix II -A, Section 26 added. APPENDIX II -A SUPPRESSION AND CONTROL OF HAZARDOUS FIRE AREAS is hereby amended by adding a new SECTION 26—NOTICE OF SPARK ARRESTER REQUIREMENT as follows: SECTION 26—NOTICE OF SPARK ARRESTER REQUIREMENT No person shall sell, offer for sale, lease, or rent to any person any internal combustion engine subject to the provisions of Section 25 and not subject to the provisions of Section 13005 of the Health and Safety Code, unless he provides a written notice to the purchaser or bailee, at the time of sale or at the time of entering into the lease or rental contract, stating that it is a violation of the UFC to use or operate the engine in, upon or adjoining any hazardous fire area, unless the engine is equipped with a spark arrester as defined in Section 25, maintained in effective working order, or the engine is constructed, equipped and maintained for the prevention of fire pursuant to Section 27. Sec. 4-2.28. Appendix II -A, Section 27 added. 57 Km APPENDIX II -A SUPPRESSION AND CONTROL OF HAZARDOUS FIRE AREAS is hereby amended by adding a new SECTION 27—FUEL MODIFICATION REQUIREMENTS FOR NEW CONSTRUCTION as follows: SECTION 27—FUEL MODIFICATION REQUIREMENTS FOR NEW CONSTRUCTION All new buildings to be built or installed in areas containing combustible vegetation shall comply with the following: approved by t1e %kief cortzurrext--w6* fle-sub-nittaL for approval of any tentative map. 27.2 WMIENTSMEM• • • . • •< ot- •'areni 27.4 The fuel modification plan may be altered if conditions change. Any alterations to the fuel modification shall be approved by the chief. 27.5 All elements of the fuel modification plan shall be maintained in accordance with the approved plan. Sec. 4-2.29. Appendix II -D, Section 1 amended. APPENDIX II -D RIFLE RANGES is hereby amended by adding a second paragraph to SECTION 1—PERMITS as follows: Sec. 4-2.30. Appendix II -E amended. APPENDIX II -E HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOUS MATERIALS INVENTORY STATEMENTS is hereby deleted and the following is substituted: APPENDIX II -E CHEMICAL CLASSIFICATION PACKET. Hazardous 339 Sec. 4-2.31. Appendix H -F amended. APPENDIX II -F PROTECTED ABOVEGROUND TANKS FOR MOTOR VEHICLE FUEL -DISPENSING STATIONS OUTSIDE BUILDINGS is hereby deleted and the following is substituted: Sec. 4-2.32. Appendix III -A amended.. APPENDIX III -A FIRE -FLOW REQUIREMENTS FOR BUILDINGS is hereby amended by deleting the exception in 5.2 Buildings Other than One- and Two -Family Dwellings and substituting the following: Sec. 4-2.33. Appendix III -B, Section 5 amended. APPENDIX III -B FIRE HYDRANT LOCATIONS AND DISTRIBUTION is hereby amended by adding the following ending paragraph to SECTION 5 DISTRIBUTION OF FIRE HYDRANTS and deleting TABLE NO. A -III -B-1 NUMBER AND DISTRIBUTION OF FIRE HYDRANTS and substituting the following: SECTION 5—DISTRIBUTION OF FIRE HYDRANTS. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems, fire hydrants shall be provided at spacing not to exceed 1.000 feet (304 800 mml to provide for transportation hazards. Where such streets are provided 59 390 TABLE NO. A -III -B-1 DISTRIBUTION OF FIRE HYDRANTS roo�5�a:..a. .""a' ..r Tb x-a.x>...p ..,iQ"..0.:.:.... ..: :.. ,y .y..:.:p.;,w.u:,::.v,:yra::o:..,.g.•.;:;.;::;.: :...:<., COMMERCIAL AND INDUSTRIAL2 300 feet (91440 mm) 150 feet (45 720 mm) RESIDENTIAL OTHER THAN DETACHED ONE- AND TWO-FAMILY DWELLINGS2 300 feet (91 440 mm) 150 feet (45 720 mm)3 DETACHED ONE- AND TWO-FAMILY DWELLINGS 300 feet (91 440 mm)4 250 feet (76 200 mm)5,6 t. 2. 3. Exception: In one- and two-story Group R, Division 1 residential occupancies containing 15 or less dwelling units, 19 or less guest rooms, or congregate residences with an occupant load of 49 or less, and protected by an approved automatic fire sprinkler system, the distance from a hydrant to any point of the exterior of the structure may be increased to 300 feet (91440 mm). In three story Group R, Division 1 residential occupancies containing 24 or less dwelling units, 29 or less guest rooms, or congregate residences with an occupant load of 64 or less, and protected by an approved automatic fire sprinkler system, the distance from a hydrant to any point of the exterior of the structure may be increased to 300 feet (91440 mm). 4. In subdivisions when all homes and attached garages are protected with automatic fire sprinkler systems, the spacing may be increased to 600 feet (182 880 mm). 5. Exception In detached one- and two-family dwellings, the maximum distance shall be measured from a hydrant to any point on the street or road frontage. 6. In detached one- and two-family dwellings protected with an approved automatic fire sprinkler system, the distance may be increased to 300 feet (91440 mm). 391 TABLE NO. A -III -B-2 REQUIRED NUMBER OF FIRE HYDRANTS I. One hydrant for each 1,000 gallons per minute (3785 L/min.) or fraction thereof. Sec. 4-2.34. Appendix III -C amended. APPENDIX III -C TESTING AUTOMATIC SPRINKLER AND STANDPIPE SYSTEMS is hereby amended as follows: 1. Add the following opening statement: 2. Section 3.1. Class I Systems is hereby amended by adding the word "dry" to the beginning of the sentence in Sections 3.1.1, 3.1.2, and 3.1.3: Section 3.1.1 Air test. I21y Class I systems shall be air tested... . Section 3.1.2 Hydrostatic test. Dry Class I systems shall be filled.... Section 3.1.3 Flow test. D-qy Class I systems shall be flow tested.... 61 392 3. Section 3.3 Class III Systems is hereby amended as follows: Section 3.3 Class III Systems is hereby amended to read as follows: Section 3.3 Class III Systems and Systems Formerly Classified as 'Wet Class I Systems." Section 3.3.1 Flow Test is hereby amended to read as follows: Section 3.3.1 Flow test. Class III systems and systems formerly classified as "Wet Class I Systems" shall be flow tested.... Section 3.3.2 Pump test is hereby amended to read as follows: Section 3.3.2 Pump test. Fire pumps shall annually be tested.... Section 3.3.3 Outlets is hereby amended by deleting the last sentence and substituting the following: Section 3.3.3 Outlets. 4. APPENDIX III -C TESTING AUTOMATIC SPRINKLER AND STANDPIPE SYSTEMS is hereby amended by adding a new Section 4 as follows: MY Lei . Ir M;iq1-■rd101 LA61 z 0 vV4.2 y u Section 41 Inspection and Testing. Private hydrant systems shall be inspected and serviced annually, and the owner shall correct any Sec. 4-2.35. Appendix V amended. APPENDIX V NATIONALLY RECOGNIZED STANDARDS OF GOOD PRACTICE is hereby deleted and the following is substituted: APPENDIX V ADOPTED STANDARDS 62 1. ADOPTION BY REFERENCE 393 (a) NFPA Standards. The NFPA Standards as listed in this section by name and edition, and as published by the National Fire Protection Association, save and except such portions as are hereinafter added, deleted, modified or amended, are hereby adopted and incorporated as fully as if set forth at length herein; and the provisions thereby shall be controlling within the limits of the incorporated area of the City. One copy of each adopted Standard is on file at the Orange County Fire Authority, Fire Prevention Division headquarters. 1. NFPA 11A Standard for Medium- and High -Expansion Foam Systems, 49991994 Edition, as amended in subsection (b). 2. NFPA 12 Standard on Carbon Dioxide Extinguishing Systems, 4959.1994 Edition, as amended in subsection (b). 3. NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems, 4999L 1992 Edition, as amended in subsection (b). 4. NFPA 12B Standard on Halon 1211 Fire Extinguishing Systems, 1990 Edition, as amended by subsection (b). 5. NFPA 13 Standard for the Installation of Sprinkler Systems, 4954 1994 Edition, as amended in subsection (b) and Section 2. 6. NFPA 13D Standard for the Installation of Sprinkler Systems in One -and Two -Family Dwellings and Mobile Homes, 4499} 1994 Edition, as amended in subsection (b) and Section 3. 7. NFPA 13R Standard for the Installation of Sprinkler Systems in Residential Occupancies up to Four Stories in Height, 4959.1994 Edition, as amended in subsection (b) and Section 4. 8. NFPA 14 Standard for the Installation of Standpipe and Hose Systems, 4999 1993 Edition, as amended in subsection (b) and Section 5. a 10. NFPA 16 Standard on Deluge Foam -Water Sprinkler and Foam - Water Spray System, 1991 Edition, as amended in subsection (b). 11. NFPA 16A Recommended Practice for the Installation of Closed - Head Foam -Water Sprinkler Systems, 4955. 1994 Edition, as amended in subsection (b) and Section 6. 63 394 12. NFPA 17 Standard for Dry Chemical Extinguishing Systems, 1990 Edition, as amended in subsection (b). 13. NFPA 17A Standard on Wet Chemical Extinguishing Systems, 1990 Edition, as amended in subsection (b). 14. NFPA 20 Standard for the Installation of Centrifugal Fire Pumps, 44941993 Edition, as amended in subsection (b). 15. NFPA 24 Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 49821992 Edition, as amended in subsection (b). 16. NFPA 37 Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, 4994 1994 Edition, as amended in subsection (b) and Section 8. 17. NFPA 50 Standard for Bulk Oxygen Systems at Consumer Sites, 1990 Edition, as amended in subsection (b) and Section 9. 18. NFPA 231 Standard for General Storage, 1990 Edition, as amended in subsection (b) and Section 10. 19. NFPA 231C Standard for Rack Storage of Materials, 1991 Edition, as amended in subsection (b) and Section 11. 20. NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems. 1994 Edition, as amended in subsection (b) General Amendments. The amendments listed below apply to all of the NFPA Standards adopted in subsection (a) above. 1. NFPA Purpose. These NFPA Standards are adopted for the purpose of establishing design, installation, testing and maintenance criteria for the subjects covered therein. This purpose takes priority over the purpose as stated in the NFPA Standards. 2. NFPA Explanatory Material. Explanatory material included in the form of fine print notes, in footnotes or in an appendix of the NFPA Standards are for informational purposes and are not adopted. 3. NFPA Alternative Material and Methods. The provisions of Section 103.1.2 of the Uniform Fire Code, as adopted in this Municipal Code, shall be applied to all requests to use XI 695 alternative material and methods to meet the requirements of this standard. 4. NFPA Definitions. The following definitions shall be applied to the NFPA Standards and take priority over any similar definitions: A. "Authority Having Jurisdiction" is the official responsible for the enforcement of the NFPA Standard. B. "Approved" shall be defined as specified in Section 202-A of the adopted Uniform Fire Code. C. "Labeled" and "Listed" shall be defined as specified in Section 213-L of the adopted Uniform Fire Code. 5. NFPA Referenced Publications. The publications referenced in the text, the referenced publication chapter and reference publication appendix of the NFPA Standards are hereby deleted and whenever a publication is referenced, it shall mean the following as appropriate: A. The NFPA Standards as adopted in Appendix V or Section 9003 of the adopted Uniform Fire Code. B. The applicable article of the adopted Uniform Fire Code. C. The applicable local ordinance such as the adopted Uniform Building rCode, Uniform Mechanical Code, Uniform Plumbing Code, or the Electrical Code. D. Whenever none of the documents listed above apply, nationally recognized standards or nationally recognized engineering practices as approved by the chief shall apply. 6. Conflicts between NFPA and UFC or Other Adopted Codes or Standards. Whenever an NFPA Standard contains a provision which duplicates or conflicts with a requirement of the Uniform Fire Code, Uniform Fire Code Standards, applicable state regulations, or other codes and standards as adopted by local ordinance, the provisions of the latter will take precedence. 7. NFPA Appendices. All NFPA appendices are for informational purposes and are not adopted. 2. NFPA 13 AMENDED (as adopted in UBC Standard 9-1) RK" 396 In addition to the amendments, additions and deletions of Section 2. (b) and UBC Standard 9-1, NFPA 13 Standard for the Installation_ of Sprinkler Systems, 1994 Edition, is further amended as follows: Subsection 1-6.1.1 Buildings of Undetermined Use is added as follows: 1-6.1.1 Buildings of Undetermined Use. When fire sprinkler systems are required in buildings of undetermined use, they shall be designed and installed to have a sprinkler density of not less than that required for an Ordinary Hazard Group 3 use, with a minimum design area of 3,000 square feet (279 m2). Use is considered undetermined if not specified at the time the permit is issued. Where a subsequent occupancy requires a system with greater capability, it shall be the responsibility of the occupant to upgrade the system to the required density for the new occupancy. Section 2-1 General is hereby amended by deleting Exception No. 2 of Subsection 2-1.1 and substituting with the following: 2-1.1 Exception No. 2: Components which do not affect system operations such as drain valves and signs need not be listed. Subsection 4-6.1.1 Valves Controlling Sprinkler Systems is hereby amended by deleting Subsection 4-6.1.1.4 and substituting with the following: 4-6.1.1.4: Control valves shall be installed and positioned so that they are operable from the floor below. The center line of the valve shall be no more than 7 feet (2134 mm) above finished floor. 3. NFPA 13D AMENDED In addition to the amendments, additions and deletions of Section 2. (b), NFPA 13D Standard for the Installation of Sprinkler Systems in One- and Two -Family Dwellings and Mobile Homes, 1994 Edition, is further amended as follows: (a) Section 3-1.1 Valves and Drains is amended by deleting Exception No. 1 and Exception No. 2 without substitution. (b) Section 3-2 Pressure Gages is deleted and the following substituted: 397 3-2 Pressure Gage. At least one water pressure gage shall be installed on the riser assembly. (c) Section 3-3 Piping is amended as follows: Table 3-3.5. All listings under cast iron, malleable iron, and steel are deleted. (d) Section 3-6 Alarms is amended by adding the following ending paragraph and deleting the exception without substitution: 3-6 Alarms. addressed on. Alarms shall be of sufficient intensity to be clearly (e) Section 4-6 Location of Sprinklers is amended by deleting the exceptions and substituting the following three exceptions and final paragraph: Exception No. 1: Sprinklers are not required in bathrooms not exceeding 55 square feet (5.1 m2). Exception No. 2: Sprinklers are not required in small clothes closets, linen closets and pantries where the least dimension does not exceed 3 feet (914 mm), the area does not exceed 24 square feet (2.2 m2), and the walls and ceilings are surfaced with noncombustible or fire -resistive material as defined in the adopted Uniform Building Code. Exception No. 3: Sprinklers may be omitted from open attached porches, carports and similar open attached structures. Attached garages shall be protected with listed quick -response sprinklers spaced to protect a maximum area of 130 square feet (12.1 m2). These heads are not required to be calculated as part of the system if the lines are supplied by the largest piping in the system. All attics shall be protected with intermediate temperature quick - response heads which shall be located to protect attic penetrations created by access scuttles or mechanical equipment. Crawl spaces that are intended for use as a living or storage area or that exceed a maximum height dimension of 5 feet (1524 mm) shall be protected with intermediate temperature quick -response heads. 67 M. 4. NFPA 13R AMENDED (as adopted in UBC Standard 9-3) In addition to the amendments, additions and deletions of Section 2. (b) and UBC Standard 9-3, NFPA 13R Standard for the Installation of Sprinkler Systems in Residential Occupancies up to Four Stories in Height, 1994 Edition, is further amended as follows: Section 2-4.5.6 is amended to read as follows: Section 2-4.5.6 Standard or quick response sprinklers shah may be used in areas outside dwelling units. Section 2-6 Location of Sprinklers Exception No. 4 is deleted and substituted with the following: Exception No. 4: Sprinklers may be omitted from penthouse equipment rooms, crawl spaces, floor/ ceiling spaces, elevator shafts, and other concealed spaces that are not used or intended for livingpurposes or storage. Sprinklers may also be omitted from attics which are not located over dwelling units. When attics are separated by unit, each unit's attic space may be protected per the Orange County Fire Authority Guidelines for Detached One and Two Family Dwellings. All other attics shall be protected per NFPA 13, 1994 Edition. 5. NFPA 14 AMENDED In addition to the amendments, additions and deletions of Section 2. (b), NFPA 14 Standard for the Installation of Standpipe and Hose Systems, 1993 Edition, is further amended as follows: (a) Section 2-9 Fire Department Connections is amended as follows: 2-9.2 Each fire department connection shall have at least two 2- 1/2 - 1/2 inch (63.5 -mm) internal threaded swivel fittings, plus of the system, having NH standard threads .... (b) Section 5-7 Minimum Pressure for System Design and Sizing � of Pipe is amended by deleting subsection (b) and the word either- at the end of the first paragraph and the letter (a} at the beginning of the second paragraph, and by replacing the number 109 psi- at the end of the second sentence in the second paragraph with 150 psi (10.4 bars). M 6. NFPA 16A AMENDED In addition to the amendments, additions and deletions of Section 2. (b), NFPA 16A Recommended Practice for the Installation of Closed -Head Foam -Water Sprinkler Systems, 1988 Edition, is further amended as follows: Section 1-1 Scope is amended by adding a beginning paragraph as follows: Whenever in this standard the word "recommended" is used, it means "required," and whenever in this standard the word "should" is used, it means "shall." 7. NFPA 24 AMENDED In addition to the amendments, additions and deletions of Section 2 (b), NFPA 24 Standard for Private Fire Service Mains and Their Appurtenances, 1992 Edition, is further amended as follows: (a) Section 1-5 Installation Work is hereby deleted and substituted with the following: (b) Section 2-2 Public Water Systems is hereby amended by deleting Section 2-2.6 and substituting with the following: 111111111111111111!11111 1: 111,1111111111111!111 iiiiiiiiiiiijillililll ?"411 IMITIMIUMT-Mg 1 . • • . l . - 1 . ... . - . . . . . I assembly shall be controlled by an approved post indicator ig 399 X11 F�WGTITI 0 .. NORM MOT (c) Section 2-6 Fire Department Connections is hereby amended by adding the following to the end of Section 2-6.2 and Section 2-6.6: Section 2-6.2 ... and shall be protected from mechanical injury. (d) Section 3-3 Post Indicator Valves is hereby amended by adding the following beginning sentence to Section 3-3.1: .• m shall have a separate connection .11 ft . 11, 1 (e) Section 3-4 Valves in Pits is hereby amended by adding the following to Section 3-4.1: Section 3-4.1 Where it is impractical to provide a post indicator valve, valves shall be permitted to be placed in valve rooms accessible from exterior, on exterior risers or on interior risers with indicatingposts arranged for outside operations, or in pits with permission of the authority having jurisdiction. (f) Section 3-5 Sectional Valves is hereby amended by adding the words "post indicator type" in front of the words "Sectional controlling valves" on line 2 of Section 3-5.1. (g) Section 7-2 Coating and Lining of Pipe is hereby amended as follows: Section 7-2 Coating and Lining of Pipe. All ferrous metal pipe shall be lined, and steel pipe shall be coated and wrapped, with joints coated and wrapped after assembly. All ferrous pipe and 70 401 The ends of the tube shall be sealed with 2 inch wide tapc gpRroved for underground use. Galvanizing does not meet the requirements of this section. (h)Section 8-5 Pipe Joint Assembly is hereby amended by adding the words "assembly and prior to poly -tube" before the last word "installation" in the paragraph in Section 8-5.2. (i) Section 8-9 Testing Underground Systems is hereby amended by adding a beginning sentence to Section 8-9.2 as follows: 8. NFPA 37 AMENDED In addition to the amendments, additions and deletions of Section 2. (b), NFPA 37 Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, 1990 Edition, is further amended as follows: (a) Section 2-1.1.2.2 General Locations is amended by deleting the last paragraph without substitution. (b) Section 2-1.1.2.3 General Locations is amended by deleting the last sentence without substitution. (c) New Section 2-1.1.2.4 General Locations is added as follows: 2-1.1.2.4 Doors, windows and louvered openings shall be located on exterior walls only. When such openings are located below openings in another story or less than 10 feet (3048 mm) from doors, windows or louvered openings of the same building, they shall be protected by a fire assembly having a 3/4 hour rating. Such fire assemblies shall be fixed, automatic or self-closing. Combustion engines and gas turbines used for emergency power shall not be located in a room or area used for any other purpose. 9. NFPA 50 AMENDED In addition to the amendments, additions and deletions of Section 2. (b), NFPA 50 Standard for Bulk Oxygen Systems at Consumer Sites, 1990 Edition, is further amended as specified in the Uniform Fire Code Standard 74-1 Part I. 71 402 10. NFPA 231 AMENDED In addition to the amendments, additions and deletions of Section 2. (b), NFPA 231 Standard for General Storage, 1990 Edition, is further amended as specified in the adopted Uniform Fire Code Standard 81-1 Part I. 11. NFPA 231C AMENDED In addition to the amendments, additions and deletions of Section 2. (b), NFPA 231C Standard for Rack Storage of Materials, 1991 Edition, is further amended as specified in the adopted Uniform Fire Code Standard 81-2 Part I. Sec. 4-2.36. Appendix VI -A, Section 1 amended. APPENDIX VI -A HAZARDOUS MATERIALS CLASSIFICATION is hereby amended by adding the following beginning paragraph to SECTION 1—SCOPE: 1 • 1 " ! 1• 1 • . . • . Sec. 4-2.37. Appendix VI -E amended. APPENDIX VI -E REQUIRED SEPARATION DISTANCES FOR EXPLOSIVE MATERIALS is hereby amended as follows: (a) A beginning paragraph is added as follows: Whenever the word "recommended" is used in Appendix VI -E, it means "r uired " (b) The first sentence of the first paragraph as printed in Appendix VI -E (UFC 1994 Edition) is deleted and the following substituted: passage. The following information is adopted for use in applying Article 77. SECTION 3. Effective Date. This Ordinance shall take effect and be in force thirty (30) days after its 72 SECTION 3. Effective Date. This Ordinance shall take effect and be in force thirty (30) days after its passage. SECTION 4. City Clerk's Certification. The City Clerk shall certify to the adoption of this Ordinance and cause the same to be posted at the duly designated posting places within the City and published once within fifteen (15) days after passage and adoption as required by law; or, in the alternative, the City Clerk may cause to be published a summary of this Ordinance and a certified copy of the text of this Ordinance shall be posted in the Office of the City Clerk five (5) days prior to the date of adoption of this Ordinance; and, within fifteen (15) days after adoption, the City Clerk shall cause to be published the aforementioned summary and shall post a certified copy of this Ordinance, together with the vote for and against the same, in the Office of the City Clerk. PASSED, APPROVED AND ADOPTED this 16th day of January , 1996. DAVID M. S, RD IN, MAYOR PRO TEM ATTEST: S • C,MAW- AM - it A -of �M1 71 403 4U4 STATE OF CALIFORNIA ) COUNTY OF ORANGE ) SS CITY OF SAN JUAN CAPISTRANO ) I, CHERYL JOHNSON, City Clerk of the City of San Juan Capistrano, California, DO HEREBY CERTIFY that the foregoing is a true and correct copy of Ordinance No. 772 which was introduced at a meeting of the City Council of the City of San Juan Capistrano, California, held on January 2 1996, and adopted at a meeting held on January 16 , 1996, by the following vote: AYES: Council Members Jones, Nash, Campbell and Mayor pro tem Swerdlin NOES: None ABSTAIN: None ABSENT: Mayor Hart (SEAL) CHERYL JOHNSOW CITY CLERK