B20-0536 - 31872 PASEO ADELANTO11/07/2024
B21 0536
Letter of Transmittal
3707 W Garden Grove Blvd. Suite 100, Orange, CA 92868
phone 714.568.1010 fax 714.568.1028 www.csgengr.com ORA – BPR - 160801
To: City of San Juan Capistrano Date Completed: 12/15/2021 Review #:PC03
32400 Paseo Adelanto Date Received: 10/21/20
San Juan Capistrano, CA 92675 CSG #: 4010693
Attn: Building & Safety Division Agency Plan Check #: B20-0536
Job Address: 31872 Paseo Adelanto
Job Description:
River Street Hay Loft - Shell and T.I. permit for brewery/tasting facility
Status: Hours: (By Rate)
X Plan is approved. 4.0 1st Plan Check
Plan is approved with conditions. See remarks. 5.0 2nd Plan Check
Plan is approved with redlines. See remarks. 3.0 3rd Plan Check
Plan is approved with redlines and conditions. See remarks. 4th Plan Check
Plan requires corrections. See attached list. Total Hours
We have reviewed the following documents ( X Digital only):
X Plans Truss Calculations
X Structural Calculations Energy Calculations
X Soil Report Specifications
Geotechnical Review Letter Special Inspection Form(s)
Other:
Special items to note:
X Plan has been stamped and signed by CSG
Environmental Health Services approval required
Special inspection required for
Hardship Form included
Remarks:
Recommend for approval
From: Jensen Ku S.E. (ginsun@csgengr.com)
CSG Consultants Inc.
BOARD OF DIRECTORS
LAURA FREESE
CHARLES T. GIBSON
SAUNDRA F. JACOBS
BETTY H. OLSON, PH.D
FRANK URY
ROBERT GRANTHAM
GENERAL MANAGER
Santa Margarita Water District 26111 Antonio Parkway, Rancho Santa Margarita, CA 92688
www.SMWD.com (949) 459-6420
November 1, 2024
Building Department
City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, California 92675
Subject: Final Water and Sewer Letter for Capo Leisure House at 31872 Paseo Adelanto Ste
B, San Juan Capistrano in Improvement District No. 9
Dear Building Department:
Subject to the developer’s successful completion of the on-site water and sewer facilities, and subject to the
availability of water from the Metropolitan Water District of Southern California, the District can and will
provide water and sewer service to the subject project. This approval is only for the issuance of building
permits and is only good for two years from the date of this letter. At this time, no further inspection of the
on-site water and sewer facilities is needed by SMWD to enable the City to release the certificate of
occupancy. However, The District still reserves the right to inspect the on-site plumbing and backflow
prevention when necessary. Use of self-regenerative water softeners is discouraged within the District and
application for use at this site has not been approved.
The following conditions must be adhered to:
1. Applicant must notify SMWD at least 48-hours in advance prior to brewery production.
2. Per discussion help on 11/1/124, applicant will do a batch process for neutralization and
discharge of production waste into the sewer. Applicant is required to follow the attached SOP
provided on 11/1/24. Refer to attached SMWD and SOCWA pretreatment ordinances for your
reference.
3. The District and/or SOCWA will inspect the location within 1 year of start of production to
ensure SOP is being adhered to.
4. The grease interceptor submitted under these plans is not approved under this Will Serve letter as
the applicant has not submitted grease interceptor calculations nor does the applicant plan to
utilize the grease interceptor under the current operation. If applicant installs a kitchen and plans
to utilize the grease interceptor system, a new Wastewater Application must be submitted to
receive a new Will Serve letter for acceptance of that system.
• The fixtures below will empty into the Sanitary Sewer:
• 2 Hand Sinks • 3 Dishwashers • 2 Mop Sinks
• 11 Toilet
• 1 3-Compartment Sink
• 3 Floor Drain
• 7 Urinals
• 11 Floor Sinks
• 2 Trench Drains
Should you have any questions or desire additional information, please call the Engineering Counter at
(949) 459-6503.
Sincerely,
SANTA MARGARITA WATER DISTRICT
Pablo Marti
Senior Project Engineer
P:\Finalws\ Capo Leisure House.doc.bp
H. Cox 01/04/20222022-928
brewery equipment01/04/20222022-928per SCAQMD Rule 219(i)(13)
ATTN: Karla Dalla Torre
DATE: EMAIL:
APPLICANT/OWNER NAME:
JOB ADDRESS:
DEVELOPMENT NAME:
PHASE:
TRACT(s):
LOT(s):
UNIT(s):
CONTACT NAME:
CONTACT PHONE:
COMPANY NAME:
TRACT LOT UNIT
TOTAL SQUARE
FOOTAGE
PREPARED BY:LISA LA
PHONE: 949-443-6349
ADDRESS
NEW RESIDENTIAL
ROOM ADDITIONS
CITY OF SAN JUAN CAPISTRANO
SCHOOL FEES WORKSHEET
COMMERCIAL/INDUSTRIAL
CUSD FAX: (949) 493-3728
LLA@SANJUANCAPISTRANO.ORG
TOTAL SQUARE FOOTAGE
PROJECT INFORMATION
SQUARE FOOTAGEAPN
April 8, 2022
Via Email and Personal Delivery:
City of San Juan Capistrano
Building Department
32400 Paseo Adelanto
San Juan Capistrano, California 92675
Attention: Steve Salcedo, Senior City Grading Inspector
Email: ssalcedo@sanjuancapistrano.org
Subject: LINE AND GRADE BUILDING PAD CERTIFICATION BY
PROFESSIONAL LAND SURVEYOR
Project:
River Street Marketplace
Tract: N TR 103 BLK LOT 56 TR 103 LOT 56 WLY 1/3 -INC POR OF
RIVER ST ADJ-
Street Addresses: 31872 Paseo Adelanto, San Juan Capistrano, California
92675 (the, “Hayloft”)
Building Permit: #B20-0536
Dear Mr. Salcedo,
On March 25th, 2022, upon completion of the building pad at the Building Address, a field
survey was performed by
Based on the pad elevations shown in the “Precise Grading Plan” prepared by Blue Peak
Engineering, Inc., dated 12/15/2021 and approved by the Joe Parco, City Engineer for the City
of San Juan Capistrano on 12/20/2021 as City Permit No. B20-0545, we do hereby certify the
building pad is built to within substantial conformance to the designed pad elevation.
The line and grade building certification exhibit is attached hereto as Exhibit A.
PROFESSIONAL LAND SURVEYOR SIGNATURE AND SEAL:
RIDGELINE ENGINEERING
By: ______________________________
Jordan Baldwin, President
Professional Land Surveyor 8513 (Expiration December 31, 2022)
EXHIBIT A
LINE AND GRADE BUILDING CERTIFICATION EXHIBIT
(ATTACHED)
8711 Monroe Cout, Suite A
Rancho Cucamonga, California
909) 980-6455 Office
(909) 980-6435 Fax
SAN JO SE ▪ STOCKTON ▪ FRESNO ▪ BAKERSFIELD ▪ RANCHO CUCAMONGA
DALLAS, TX ▪ DENVER, CO ▪ CHARLESTON, SC
April 27, 2021 Project No. 3-220-0314
Mr. Alex Osinski
River Street SJC, LLC.
23727 Hawthorne Boulevard, Suite 1
Torrance, CA 90505
SUBJECT: GEOTECHNICAL CONSULTANT OF RECORD
PROPOSED COMMERCIAL BUILDINGS
EASTERN CORNER OF PASEO ADELANTO AND RIVER STREET
SAN JUAN CAPISTRANO, CALIFORNIA
Reference: Inland Engineering Technologies, Inc., Preliminary Geotechnical Investigation for the Proposed
Commercial Building Located at The Eastern Corner of the Paseo Adelanto – River Street
Intersection, City of San Juan Capistrano, County of Orange, California, Project No. 16-3371,
Dated July 2016
Dear Mr. Osinski:
In accordance with your request, Salem Engineering Group, Inc. (SALEM) has prepared this letter to confirm that
SALEM is the Geotechnical Consultant of Record (Soils Engineer-of-Record) and will be providing geotechnical
engineering services for the subject project, and has replaced the previous geotechnical engineering consultant,
Kleinfelder. SALEM has reviewed the referenced report, concurs with their findings, conclusions and
recommendations, and will act in accordance with geotechnical engineering recommendations in the referenced report,
as well as the requirements of the California Building Code. SALEM should be present at the site during site
preparation to observe site clearing, preparation of exposed surfaces after clearing, placement, treatment and
compaction of fill material, and footing excavation. SALEM's observations should be supplemented with periodic
compaction tests to establish substantial conformance with these recommendations. Moisture content of the building
pad (footings and slab subgrade) should be tested immediately prior to concrete placement. SALEM should observe
foundation excavations prior to placement of reinforcing steel or concrete to assess whether the actual bearing
conditions are compatible with the conditions anticipated during the preparation of this report. SALEM should also
observe placement of foundation and slab concrete. If you have any questions, or if we may be of further assistance, please
do not hesitate to contact our office at (909) 980-6455.
Respectfully submitted,
SALEM Engineering Group, Inc.
Clarence Jiang, GE
Senior Geotechnical Engineer
RGE 2477
8711 Monroe Court, Suite A
Rancho Cucamonga, CA 91730
Phone (909) 980-6455
Fax (909) 980-6435
Project No. 3-220-0027 - 1 -
July 9, 2021 Project No. 3-220-0314
Mr. Dan Almquist
President
River Street, LLC
31791 Los Rios Street
San Juan Capistrano, CA 92675
SUBJECT: RESPONSE TO THIRD-PARTY REVIEW (SECOND)
PROPOSED RIVER STREET MARKETPLACE
31825 LOS RIOS STREET
SAN JUAN CAPISTRANO, CALIFORNIA
PERMIT NUMBER: B20-0545
References: Attached.
Dear Mr. Almquist:
This report presents our response to the Third-Party Geotechnical Review (Second) Letter dated June 20,
2021 prepared by Hetherington Engineering, Inc. (Project No. 9198.1, Log No. 21249). The review letter
is attached for reference.
We have reviewed the Precise Grading Plans dated May 7, 2021 prepared by Blue Peak Engineering,
Inc. and the Foundation Plans dated July 9, 2021 prepared by STB Structural Engineers, Inc. Based on
our review, from a geotechnical point-of-view, the relevant geotechnical aspects of the precise grading
and foundation plans, related details, and notes are in compliance with the geotechnical engineering
recommendations presented in the referenced reports.
The limitations and recommendations provided in the referenced reports apply to this letter. If you
have any questions, or if we may be of further assistance, please do not hesitate to contact our office at
(909) 980-6455.
Respectfully Submitted,
SALEM ENGINEERING GROUP, INC.
Clarence Jiang, GE
Senior Geotechnical Engineer
RGE 2477
Attachments: References
City Review Comments
SAN JOSE, CA | STOCKTON, CA | FRESNO, CA | BAKERSFIELD, CA | RANCHO CUCAMONGA, CA
DALLAS, TX | DENVER, CO | CHARLESTON, SC
REFERENCES
1. Inland Engineering Technologies, Inc., Preliminary Geotechnical Investigation for the Proposed
Commercial Building Located at The Eastern Corner of the Paseo Adelanto – River Street
Intersection, City of San Juan Capistrano, County of Orange, California, Project No. 16-3371,
Dated July 11, 2016
2. ----, Infiltration Testing for the San Juan Rios District Located at Paseo Adelanto and River
Street, San Juan Capistrano, California, dated July 8, 2016
3. ----, Geotechnical Response to the City of San Juan Capistrano Review Comments, Geotechnical
Investigation for the Proposed Commercial Buildings Located at the Eastern Corner of the Paseo
Adelanto – River Street Intersection, City of San Juan Capistrano, County of Orange, California,
Project No. 16-3371, Dated October 27, 2017
4. ----, Second Geotechnical Response to the City of San Juan Capistrano Review Comments,
Geotechnical Investigation for the Proposed Commercial Buildings Located at the Eastern Corner
of the Paseo Adelanto – River Street Intersection, City of San Juan Capistrano, County of Orange,
California, Project No. 16-3371, Dated May 4, 2018
5. ----, Third Geotechnical Response to the City of San Juan Capistrano Review Comments,
Geotechnical Investigation for the Proposed Commercial Buildings Located at the Eastern Corner
of the Paseo Adelanto – River Street Intersection, City of San Juan Capistrano, County of Orange,
California, Project No. 16-3371, Dated May 21, 2018
6. Hetherington Engineering, Inc., Third Party Geotechnical Review (First), San Juan Rios District
(Los Rios Street Market), Paseo Adelanto and River Street, San Juan Capistrano, California,
AC16-029, dated February 6, 2017
7. ----, Third Party Geotechnical Review (Second), San Juan Rios District (Los Rios Street Market),
Paseo Adelanto and River Street, San Juan Capistrano, California, AC16-029, dated February 20,
2018
8. ----, Third Party Geotechnical Review (Third), San Juan Rios District (Los Rios Street Market),
Paseo Adelanto and River Street, San Juan Capistrano, California, AC16-029, dated May 15,
2018
9. ----, Third Party Geotechnical Review (Fourth), San Juan Rios District (Los Rios Street Market),
Paseo Adelanto and River Street, San Juan Capistrano, California, AC16-029, Project No. 8205-
1, Log No. 19901, Dated June 6, 2018
10. Salem Engineering Group, Inc., Title Page of Geotechnical Investigation Report, Proposed
Commercial Buildings, Eastern Corner of Paseo Adelanto and River Street, San Juan Capistrano,
California, Dated May 4, 2020
11. ----, Percolation Testing and Supplemental Recommendations, Proposed Commercial Buildings,
Eastern Corner of Paseo Adelanto and River Street, San Juan Capistrano, California, Dated May
29, 2020
12. ----, Response to Third-Party Review Comments, Proposed River Street Marketplace, 31825 Los
Rios Street, , San Juan Capistrano, California, Dated June 15, 2021
June 20, 2021
Project No. 9198.1
Log No. 21479
City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, California 92675
Attention: Mr. Jeremy Hohnbaum
Subject: THIRD-PARTY GEOTECHNICAL REVIEW (SECOND)
River Street Marketplace
31825 Los Rios Street
San Juan Capistrano, California
Permit Number: B20-0545
References: Attached
Dear Mr. Hohnbaum:
In accordance with your request, Hetherington Engineering, Inc. has provided third-party
geotechnical review of References 7 and 8. The following comment is provided for
analyses and/or response by the Geotechnical Consultant. Two copies of the Geotechnical
Consultant’s response should be submitted to the City of San Juan Capistrano and one
copy to Hetherington Engineering, Inc.
The Consultant should review the project grading and foundation plans, provide any
additional geotechnical recommendations considered necessary, and confirm that the
plans have been prepared in accordance with the geotechnical recommendations provided
in the referenced reports (second request).
SOIL & FOUNDATION ENGINEERING ENGINEERING GEOLOGY HYDROGEOLOGY
(760) 931-1917 Fax (760) 931-0545
333 Third Stree Laguna Beach, CA 9265 (949) 715-5440 Fax (949) 715-5442
Carlsbad, CA 92008-43695365 Avenida Encinas, Suite A
HETHERINGTON ENGINEERING, INC.
www.hetheringtonengineering.com
THIRD-PARTY GEOTECHNICAL REVIEW (SECOND)
Project No. 9198.1
Log No. 21479
June 20, 2021
Page 2
Please call if there are any questions.
Sincerely,
HETHERINGTON ENGINEERING, INC.
Paul A. Bogseth Mark D. Hetherington
Professional Geologist 3772 Civil Engineer 30488
Certified Engineering Geologist 1153 Geotechnical Engineer 397
Certified Hydrogeologist 591 (expires 3/31/22)
(expires 3/31/22)
Distribution: 1- via e-mail (Jhohnbaum@sanjuancapistrano.org)
1- via e-mail (MLaScalza@sanjuancapistrano.org)
HETHERINGTON ENGINEERING, INC.
REFERENCES
Project No. 9198.1
Log No. 21479
1. “Preliminary Geotechnical Investigation for the Proposed Commercial Building Located
at the Eastern Corner of Paseo Adelanto - River Street Intersection, City of San Juan
Capistrano, County of Orange, California”, by Inland Engineering Technologies, Inc.,
dated July 11, 2016.
2. “Infiltration Testing for the San Juan Rios District Located at Paseo Adelanto and River
Street, San Juan Capistrano, California”, by Inland Engineering Technologies, Inc.,
dated July 8, 2016.
3. “Title Page of Geotechnical Investigation Report, Proposed Commercial Buildings,
Eastern Corner of Paseo Adelanto and River Street, San Juan Capistrano, California”, by
Salem Engineering Group, Inc., dated May 4, 2020.
4. “Percolation Testing and Supplemental Recommendations, Proposed Commercial
Buildings, Eastern Corner of Paseo Adelanto and River Street, San Juan Capistrano,
California”, by Salem Engineering Group, Inc., dated May 29, 2020.
5. “Precise Grading Plan, River Street Marketplace, 31825 Los Rios Street, San Juan
Capistrano, CA”, by Blue Peak Engineering, Inc., dated July 28, 2020 (15-Sheets).
6. “Third-Party Geotechnical Review (First), River Street Marketplace, 31825 Los Rios
Street, San Juan Capistrano, California”, Permit Number B20-0545”, by Hetherington
Engineering, Inc., dated January 5, 2021.
7. “Geotechnical Consultant of Record, Proposed Commercial Buildings, Eastern
Corner of Paseo Adelanto and River Street, San Juan Capistrano, California,” by
Salem Engineering Group, Inc., dated April 27, 2021.
8. “Response to Third-Party Review Comments, Proposed River Street Marketplace,
31825 Los Rios Street, San Juan Capistrano, California Permit Number: B20-0545,”
by Salem Engineering Group, Inc., dated June 15, 2021.
HETHERINGTON ENGINEERING, INC.
Restrooms
AUG 05, 2020NOV 19, 2021
CSG 12/16/21
B20-0536
18-B-31650 Page 1 of 3
September 23, 2021
EMPIRE STEEL BUILDINGS **
5230 CARROLL CANYON RD STE 300
San Diego, CA 92121
18-B-31650
River Street SJC
San Juan Capistrano, CA
MULTIPLE BUILDINGS
To Whom It May Concern:
This is to certify that materials for the subject structure have been designed in
accordance with the order documents, specifically as shown per the attached
Engineering Design Criteria Sheet.
Aspects of code compliance as related to use or occupancy, such as sprinkler
requirements, are not addressed by these documents.
These materials, when properly erected on an adequate foundation in accordance with
the erection drawings as supplied and using the components as furnished, will meet
the attached loading requirements.
This certification does not cover field modifications or the design of materials
not furnished by Metallic Building Systems.
The attached design criteria information is to remain with and form part of this
Letter of Certification.
The calculations and the metal building they represent are the product of Metallic
Building Systems or a division of its affiliate Cornerstone Building Brands. The
engineer whose seal appears hereon is employed by either Metallic Building Systems
or a division of its affiliate Cornerstone Building Brands and is not the engineer
of record for this project.
Cordially,
Metallic Building Systems
Materials for Metal Buildings
A Cornerstone Building Brands Company
This document has been
digitally signed.
Anan Almughrabi, P.E.
Engineer IV
&6*
%
c
&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&&666666666666666666666666666666666666666666666*******************************************
%%%%%%%%
./1./')1')'1''$(!&1'$(!&
11++-&1'*1*&,&1'1 (*$,1+!!&',11 '&+,*-,'1
1 1 (*$,1'*1 '*1&1 ((*'.!1 '1 &01.'",'&'1&01 '1 ,(*'.+'&+1
'1 ,+1 '1 '*1 '1 &01 ',*1 '*&&1 '1 ,1 -*+,'&1 *%,+1
(*+-$&,'1 .1 -,'*,01 ,'1 .'!,'*1 &!1 ,1 (*'.+'&+1 '1 ,+1
'1 '*1 ',*'*&&+1 '1 ,1 -*+,'&++#!&',1 1 .#1
1
.*01 (*$,1 ++-1 +!!'$1 &.!-&!++1 /'* 1 +1
'$$&/,&1 0+
2021-09-29
15:27:42
18-B-31650 Page 2 of 3
Building Code ..................... 2019 California Building Code
Building Risk Category ............ Normal (Risk Category II)
Roof Dead Load
Superimposed ................. 2.62 psf (Bldg A)
2.65 psf (Bldg B)
Collateral ................... 5.00 psf (Bldg A)
(0.00 psf Ceiling 5.00 psf Other)
1.00 psf (Bldg B)
(0.00 psf Ceiling 1.00 psf Other)
Roof Live Load .................... 20.00 psf reduction allowed
Wind
Ultimate Wind Speed (Vult) ... 100.00 mph
Nominal Wind Speed (Vasd) .... 77 mph (IBC section 1609.3.1)
Serviceability Wind Speed .... 67 mph
Ground Elevation Factor ...... 1.00 (94 ft ASL)
Wind Exposure Category ....... C
Exposure Coefficient (MWFRS) . 0.929 (Bldg A)
0.939 (Bldg B)
Exposure Coefficient (C & C) . 0.929
Enclosure Classification ..... Enclosed Building (Bldg A)
Partially Enclosed Building (Bldg B)
Internal Pressure Coef (GCpi) 0.18/-0.18 (Bldg A)
0.55/-0.55 (Bldg B)
Wall Loads for components not provided by building manufacturer
Zone 5 Areas (within 6.00' of corner) 23.76 psf pressure -31.81 psf
suction
Zone 4 Areas (away from corners) 23.76 psf pressure -25.77 psf
suction
These values are the maximum values required based on a 10 sq ft
area.
Components with larger areas may have lower wind loads.
Seismic
Seismic Importance Factor (Ie) 1.00
Seismic Design Category ...... D
Soil Site Class .............. D Stiff Soil
Ss ........................... 1.183 g Sds ..... 0.946 g
S1 ........................... 0.425 g Sd1 ..... 0.531 g
Analysis Procedure ........... Equivalent Lateral Force
Column Line (Bldg A) 1 & 4 2-3 SWA & SWC
Basic Force Resisting System B3 C4 C4 & B3
Response Modification Coefficient (R) 3.25 3.50 3.25
Seismic Response Coefficient (Cs) 0.291 0.270 0.291
Design Base Shear in kips (V) 3.44 7.16 11.62
Column Line (Bldg B) SWA
Basic Force Resisting System B3
Response Modification Coefficient (R) 3.25
Seismic Response Coefficient (Cs) 0.291
Design Base Shear in kips (V) 0.00
Basic Structural System (from ASCE 7-16 Table 12.2-1)
B3 - Ordinary Steel Concentrically Braced Frame
C4 - Ordinary Steel Moment Frame
18-B-31650 Page 3 of 3
The material supplied by the manufacturer has been designed with the
following minimum deflection criteria. The actual deflection may be
less depending on actual load and actual member length.
BUILDING DEFLECTION LIMITS.......: BLDG-A and BLDG-B
Roof Limits Rafters Purlins Panels
------------------------------- -------- ------- ------
Live: L/ 180 150 60
Snow: L/ 180 180 60
Serviceability Wind: L/ 180 180 60
Total Gravity: L/ 120 120 60
Total Uplift: L/ N/A N/A 60
Frame Limits Sidesway Portal Frame Sidesway
------------------------------- -------- ---------------------
Live: H/ 60
Snow: H/ 60
Serviceability Wind: H/ 60
Seismic Drift: H/ 40 40
Service-Level Crane: H/ 100
Portal Serviceability Wind: H/ N/A 60
Total Gravity: H/ 60
Service Seismic: H/ 40 40
Wall Limits Limit
------------------------------- --------
Total Wind Panels: L/ 60
Total Wind Girts: L/ 90
Total Wind EW Columns: L/ 120
The Service Seismic limit as shown here is at service level loads.
DESIGN PACKAGE
BUILDER: EMPIRE STEEL BUILDINGS **
CUSTOMER: NONE
JOB NUMBER: 18-B-31650
TABLE OF CONTENTS
Page
Design Criteria 1-2
Notes on Drawings 3-4
Deflection Criteria 5
Project Layout 6
Building A and Lean-To 7-27
Special Details 28
Note to Detailing: Eds2Xds Drawings (Y)
Original Design Completed thru Change Order # 1
Date: 9/23/2021
Revision History
Rev
#
Update
Reactions?Reason for Revision Pages Revised Date
Revised Eng.
0 No Original Design All 09/23/2021 MMF
Project Engineer: Mohsen M. Farahani (Fairview)
Checking Engineer: Mehrdad Pirataie
Signing Engineer: Anan Almughrabi, P.E.
Job Number ........................ 18-B-31650
Builder ........................... EMPIRE STEEL BUILDINGS **
Jobsite Location .................. RIVER STREET SJC, San Juan
Capistrano, California
Building Code ..................... 2019 California Building Code
Building Risk Category ............ Normal (Risk Category II)
Roof Dead Load
Superimposed ................. 2.62 psf (Bldg A)
2.65 psf (Bldg B)
Collateral ................... 5.00 psf (Bldg A)
(0.00 psf Ceiling 5.00 psf Other)
1.00 psf (Bldg B)
(0.00 psf Ceiling 1.00 psf Other)
Roof Live Load .................... 20.00 psf reduction allowed
Wind
Ultimate Wind Speed (Vult) ... 100.00 mph
Nominal Wind Speed (Vasd) .... 77 mph (IBC section 1609.3.1)
Serviceability Wind Speed .... 67 mph
Ground Elevation Factor ...... 1.00 (94 ft ASL)
Wind Exposure Category ....... C
Exposure Coefficient (MWFRS) . 0.929 (Bldg A)
0.939 (Bldg B)
Exposure Coefficient (C & C) . 0.929
Enclosure Classification ..... Enclosed Building (Bldg A)
Partially Enclosed Building (Bldg B)
Internal Pressure Coef (GCpi) 0.18/-0.18 (Bldg A)
0.55/-0.55 (Bldg B)
Wall Loads for components not provided by building manufacturer
Zone 5 Areas (within 6.00' of corner) 23.76 psf pressure -31.81 psf
suction
Zone 4 Areas (away from corners) 23.76 psf pressure -25.77 psf
suction
These values are the maximum values required based on a 10 sq ft
area.
Components with larger areas may have lower wind loads.
Seismic
Seismic Importance Factor (Ie) 1.00
Seismic Design Category ...... D
Soil Site Class .............. D Stiff Soil
Ss ........................... 1.183 g Sds ..... 0.946 g
S1 ........................... 0.425 g Sd1 ..... 0.531 g
Analysis Procedure ........... Equivalent Lateral Force
Column Line (Bldg A) 1 & 4 2-3 SWA & SWC
Basic Force Resisting System B3 C4 C4 & B3
Response Modification Coefficient (R) 3.25 3.50 3.25
Seismic Response Coefficient (Cs) 0.291 0.270 0.291
Design Base Shear in kips (V) 3.44 7.16 11.62
Column Line (Bldg B) SWA
Basic Force Resisting System B3
Page 1
09/23/2021
Response Modification Coefficient (R) 3.25
Seismic Response Coefficient (Cs) 0.291
Design Base Shear in kips (V) 0.00
Basic Structural System (from ASCE 7-16 Table 12.2-1)
B3 -Ordinary Steel Concentrically Braced Frame
C4 - Ordinary Steel Moment Frame
Page 2
09/23/2021
Material properties of steel bar, plate, and sheet used in the
fabrication of built-up structural framing members conforms to ASTM
A529, ASTM A572, or ASTM A1011 with 55 ksi min. yield, except flanges
Wider than 12" and thicker than 3/8", all flanges thicker than 1",
and all webs thicker than 3/8" are 50 ksi min. yield. Rod X-bracing
conforms to ASTM A529 or ASTM A572 with 50 ksi min. yield. Cable X-
bracing conforms to ASTM A475 7 Strand Extra High-Strength grade.
Hot rolled structural shapes conform to ASTM A992, ASTM A529, or
ASTM A572 with 50 ksi min. yield. Hot rolled angles, other than
flange braces conform to ASTM A36 minimum. Round and rectangular
HSS conforms to ASTM A500 Grade B. Cold-formed steel secondary
framing Members conform to ASTM A1011 or ASTM A653 Grade 55 with
55 ksi min. yield. For Canada, material properties conform to
CAN/CSA G40.20/G40.21 or equivalent.
All bolted joints with A325 Type 1 bolts are specified as fully
tightened joints in accordance with the most recent edition of the
RCSC Specification for Structural Joints Using ASTM A325 or A490 Bolts.
Pre-tensioning methods, including turn-of-nut, calibrated wrench,
twist-off-type tension-control bolts or direct-tension-indicator
are NOT required. Installation inspection requirements for Fully Tight
Bolts (Specification for Structural Joints Section 9.1) is suggested.
Design criteria as noted is as given within order documents and is
applied in general accordance with the applicable provisions of the
model code and/or specification indicated. Neither the metal building
manufacturer nor the certifying engineer declares or attests that the
loads as designated are proper for local provisions that may apply or
for site specific parameters. The design criteria is supplied by the
builder, project owner, or an Architect and/or Engineer of Record for
the overall construction project.
This project is designed using manufacturer's standard serviceability
criteria. Generally, this means that all deflections are within
typical performance limits for normal occupancy and standard metal
building products.
This metal building system (Bldg A)is designed as an Enclosed
Building. Exterior and/or operable components including, but not
Limited to, doors, windows, vents, etc. ("Components") must be
designed to withstand the required component and cladding wind
pressures specified by the building code. In order to maintain
the metal building system's Enclosed Building condition, all
Components shall be closed when wind velocities reach half the
designed wind load for the metal building system as shown on the
drawings and design criteria documentation. Failure to maintain
the metal building system's Enclosed Building condition will
violate and void all warranties and certifications applicable to
the material supplied by the metal building manufacturer.
The design collateral load has been uniformly applied to the
design of the building. Hanging loads are to be attached to the
purlin web. This may not be appropriate for heavily concentrated
Page 3
09/23/2021
loads. Any attached load in excess of 150 pounds shall be
accounted for by special design performed by a licensed engineer
using concentrated loads and may require separate support members
within the roof system.
The Lean-To frame at building B line 1 is designed as a non-
expandable frame. Corresponding frame reactions are calculated
based upon actual tributary area.
The Lean-To frame at building B line 4 is designed to receive a
future addition with a maximum bay spacing of 20 feet as measured
between centerline of the existing endwall frame to the centerline
of the future frame.
Building A has been designed for two 17'-6" x 14'-6" Bi-Fold
doors in the SWA with "moving panel door/ window weight with
cladding" weight of 2791 lbs each. Any changes to the size or
weight of the doors will need to be signed off by licensed engineer.
X-Bracing is to be installed to a taut condition with all slack
removed. Do not tighten beyond this state.
Page 4
09/23/2021
Job Number.....................: 18-B-31650
Builder........................: EMPIRE STEEL BUILDINGS **
Jobsite Location...............: RIVER STREET SJC, San Juan Capistrano,
CA California
The material supplied by the manufacturer has been designed with the
following minimum deflection criteria. The actual deflection may be
less depending on actual load and actual member length.
BUILDING DEFLECTION LIMITS.......: BLDG-A and BLDG-B
Roof Limits Rafters Purlins Panels
------------------------------- -------- ------- ------
Live: L/ 180 150 60
Snow: L/ 180 180 60
Serviceability Wind: L/ 180 180 60
Total Gravity: L/ 120 120 60
Total Uplift: L/ N/A N/A 60
Frame Limits Sidesway Portal Frame Sidesway
------------------------------- -------- ---------------------
Live: H/ 60
Snow: H/ 60
Serviceability Wind: H/ 60
Seismic Drift: H/ 40 40
Service-Level Crane: H/ 100
Portal Serviceability Wind: H/ N/A 60
Total Gravity: H/ 60
Service Seismic: H/ 40 40
Wall Limits Limit
------------------------------- --------
Total Wind Panels: L/ 60
Total Wind Girts: L/ 90
Total Wind EW Columns: L/ 120
The Service Seismic limit as shown here is at service level loads.
Page 5
09/23/2021
Page 6 09/23/2021
123 1/2o| 1/2o| 1/2o| 1/2o|420'05'05'020'0LeanTo Tie-In2'0 Slimline2'0 G.O.H.2'0 G.O.H.420'020'0420'0P.F.60'07'613'616'620'0420'020'0 3/4o|420'060'07'6
13'6
20'0
LCC
4.0
12
D
20'0
C
10'0
1/2o|
1/2o|
RCC
20'07'613'618'623'6LCCC20'0D10'0 1/2o| 1/2o|RCC20'050'07'613'618'623'614x10
F.O.8'4x8'2-1/217'0x14'8SIDEWALL SWAENDWALL EWBSIDEWALL SWCENDWALL EWDBuilder :EMPIRE STEEL BUILDINGSJob No: 31650A run01Version: ver02-mmfarahaniWed Sep 22 18:22:28 2021 San Juan Capistrano CA 9key Strut: x=double Z, xx=triple Z, o=pipe(FM)17'0x14'817'6x14'8Page 7 09/23/20211010101010101010101010101010'0'0'0'0'0'0'0'0''''0'0'20505050505050505050505050505000'000000000000WDWWWWWWWWWWWWWALALALALALALALALALALALALALALLLLLLLLLLLLLLEEEEEEEEEEEEEEWDWDWDWDWDWDWDWDWDWDWDWDWDDW8x24W8x24W8x24W8x24
432 1/2o|112'02'0 Slimline2'0 G.O.H.2'0 G.O.H.420'020'0420'060'016'0
A
4.0
12
12'0A 12'0 60x16OPENTO REMAIN OPEN 12x20
OPEN 12x20OPENSIDEWALLENDWALL EWDSIDEWALL SWAENDWALL EWBAttached to Building 1 side SWABuilder :EMPIRE STEEL BUILDINGSJob No: 31650A run01Version: ver02-mmfarahaniWed Sep 22 18:22:28 2021 San Juan Capistrano CA 9key Strut: x=double Z, xx=triple Z, o=pipe(FM)TO REMAIN OPEN TO REMAIN OPENPage 8 09/23/20211222122222222222'0'0'0'0'0'0'0'0'0'0'0'0'0'0WWWDWWWWWWWWWWWALALALALALALALALALALALALALALL LLL L LL LLLLLLLEEEEEEEEEEEEEEWBWBWBWBWBWBWBWBWBWBWBWBWBWBAdd 1/2" Diameter Rod Manually
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
BUILDING A DESIGN SUMMARY REPORT
All connections use ASTM F3125 Gr. A325N bolts, unless noted otherwise.
All anchor rods are checked according to ASTM F1554 Gr. 36 strengths.
ROOF PLANE ------- RPA
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\AroofRPA_01.edf
Panel .................... UDEK
Panel width .............. 24 in.
Panel gage ............... 24 ga.
Purlins .................. 55.0 ksi yield strength
Eave struts .............. 55.0 ksi yield strength
Purlin Spacing: 2@3.3097 4@4'4 1'0-9/16
Bay Length Member Size Brace L Lap R Lap
# (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
LE 2.333 8X2.5Z16 None 0.000 0.000 C
1 19.667 8X2.5Z16 2 points C 0.000 1.479 C
2 20.000 8X2.5Z16 2 points C 1.479 1.479 C
3 19.667 8X2.5Z16 2 points C 1.479 0.000 C
RE 2.333 8X2.5Z16 None C 0.000 0.000
Purlin Clip Use 2 A325 Bolts @ Level 2,3,4,5,6,7 @ Supports: 1,2,3,4
Purlin Stiffened Clips @ Level 2,7 @ Supports: 1,2,3,4
Purlin Backup Plate @ Level 2,7 @ Supports: 1,2,3,4
Page 9
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
ROOF PLANE ------- RPA
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\AroofRPC_01.edf
Panel .................... UDEK
Panel width .............. 24 in.
Panel gage ............... 24 ga.
Purlins .................. 55.0 ksi yield strength
Eave struts .............. 55.0 ksi yield strength
Purlin Spacing: 2@3.3097 4@4'4 1'0-9/16
Bay Length Member Size Brace L Lap R Lap
# (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
LE 2.333 8X2.5Z16 None 0.000 0.000 C
1 19.667 8X2.5Z16 2 points C 0.000 1.479 C
2 20.000 8X2.5Z16 2 points C 1.479 1.479 C
3 19.667 8X2.5Z16 2 points C 1.479 0.000 C
RE 2.333 8X2.5Z16 None C 0.000 0.000
Purlin Clip Use 2 A325 Bolts @ Level 2,3,4,5,6,7 @ Supports: 4,3,2,1
Purlin Stiffened Clips @ Level 2,7 @ Supports: 4,3,2,1
Purlin Backup Plate @ Level 2,7 @ Supports: 4,3,2,1
RPA Purlin Strut @ 30.000 (ft) :8X2.5Z16 Bays 1
RPA Purlin Strut @ 30.000 (ft) :8X2.5Z16 Bays 2
RPA Purlin Strut @ 30.000 (ft) :8X2.5Z16 Bays 3
RPC Purlin Strut @ 20.000 (ft) :8X2.5Z16 Bays 1
RPC Purlin Strut @ 25.000 (ft) :8X2.5Z16 Bays 1
RPC Purlin Strut @ 20.000 (ft) :8X2.5Z16 Bays 2
RPC Purlin Strut @ 25.000 (ft) :8X2.5Z16 Bays 2
RPC Purlin Strut @ 20.000 (ft) :8X2.5Z16 Bays 3
RPC Purlin Strut @ 25.000 (ft) :8X2.5Z16 Bays 3
SWA Eave Strut @ 20.000 (ft) :8X3.5E14 Bays 1
SWA Eave Strut @ 20.000 (ft) :8X3.5E14 Bays 2
SWA Eave Strut @ 20.000 (ft) :8X3.5E14 Bays 3
SWC Eave Strut @ 20.000 (ft) :8X3.5E14 Bays 1
SWC Eave Strut @ 20.000 (ft) :8X3.5E14 Bays 2
SWC Eave Strut @ 20.000 (ft) :8X3.5E14 Bays 3
Note: 1) All Purlin strut locations for all roof planes are measured from back
sidewall.
2) All purlin strut rows use the same lap lengths as the main purlin design.
Eave strut interior connection at SWA uses (4)-1/2" A325 bolts w/SC-18 plate.
Eave strut interior connection at SWC uses (4)-1/2" A325 bolts w/SC-18 plate.
Eave strut connection at end-frame uses (4)-1/2" A325 bolts.
BRACING ----
Roof: 1 bays Rod
Plane SWA : Portal Frame (Nested)
Plane SWC : 1 bays Rod: Hillside Washers
Plane EWB : 1 bays Rod
Plane EWD : 1 bays Rod
Page 10
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
Sidewall Plane SWA -- (8.250" Inset columns))
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\AwallSWA_01.edf
Panel .................... PBR
Panel width .............. 36 in.
Panel gage ............... 26 ga.
Girts .................... 55.0 ksi yield strength
Girts Spacing: 7'6 6'0 3'0
Bay Elev. Length Member Size Brace L Lap R Lap
# (ft-in) (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
1 7'6 20.000 8X2.5Z16 None S 0.000 0.000 C
2 7'6 20.000 8X2.5Z16 None C 0.000 0.000 C
3 7'6 20.000 8X2.5Z16 None C 0.000 0.000 S
1 13'6 20.000 8X2.5Z16 None S 0.000 0.000 C
2 13'6 20.000 8X2.5Z16 None C 0.000 0.000 C
3 13'6 20.000 8X2.5Z16 None C 0.000 0.000 S
1 16'6 20.000 8X2.5Z12 None S 0.000 2.479 C
2 16'6 20.000 8X2.5Z12 None C 2.479 2.479 C
3 16'6 20.000 8X2.5Z12 None C 2.479 0.000 S
Note : Maximum distance to extend girt from adjacent bay is 36.00 inches.
Framed Openings:
Width Height Sill Ht Jamb Header/Sill Bay Distance
17'0 14'8 N/A *W8X24 *HSS 5x5x1/4 1 1'6
17'0 14'8 N/A *W8x24 *HSS 5x5x1/4 2 1'6
17'6 14'8 N/A *8X3.5C12 *8X3.5C12 3 1'3
*- Change Manually
Note: ADD 3/8” CAP EXTENDED(TOP&BOT) PLATE TO HSS AND USE 2-1/2” DIAM. A325
AT THE TOP AND BOTTOM FOR CONNECTING HSS TO THE WEB OF W8X24 JAMBS (TYP)
3/8" Plate
HSS 5x5x1/4
Page 11
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
Sidewall Plane SWC -- (8.250" Inset columns)
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\AwallSWC_01.edf
Panel .................... PBR
Panel width .............. 36 in.
Panel gage ............... 26 ga.
Girts .................... 55.0 ksi yield strength
Girts Spacing: 7'6 6'0
Bay Elev. Length Member Size Brace L Lap R Lap
# (ft-in) (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
1 7'6 20.000 8X2.5Z16 None S 0.000 1.479 C
2 7'6 20.000 8X2.5Z16 None C 1.479 1.479 C
3 7'6 20.000 8X2.5Z16 None C 1.479 0.000 S
1 13'6 20.000 8X2.5Z16 None S 0.000 1.479 C
2 13'6 20.000 8X2.5Z16 None C 1.479 1.479 C
3 13'6 20.000 8X2.5Z16 None C 1.479 0.000 S
Note : Maximum distance to extend girt from adjacent bay is 36.00 inches.
Page 12
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
Endwall Plane EWB Design ........BEARING FRAME
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\AwallEWB_01.edf
Panel .................... PBR
Panel width .............. 36 in.
Panel gage ............... 26 ga.
Rafters -----
Mem Description Length Start End
# Member Size Identification (ft) (ft) (ft)
--------------------------------------------------------------
1 W8X10 50.0 ksi 25.101 0.000 25.101
Connections... Left : Type-IV SEP 6.000" X 3/8" (2)-1/2" A325N Bolts
Right: Type-II MEP 6.000" X 3/8" (4)-1/2" A325N Bolts
2 W8X10 50.0 ksi 25.101 25.101 50.201
Connections... Left : Type-II MEP 6.000" X 3/8" (4)-1/2" A325N Bolts
Right: Type-IV SEP 6.000" X 3/8" (2)-1/2" A325N Bolts
Flange Braces at following purlins (horizontal distance from eave):
PLANE SWA: None
PLANE SWC: None
Girts .................... 55.0 ksi yield strength
Girts Spacing: 7'6 6'0 2@5'0
Bay Elev. Length Member Size Brace L Lap R Lap
# (ft-in) (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
1 7'6 19.312 8X2.5Z13 None S 0.000 0.000 S
2 7'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 7'6 19.312 8X2.5Z16 None S 0.000 0.000 S
1 13'6 19.312 8X2.5Z14 None S 0.000 0.000 S
2 13'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 13'6 19.312 8X2.5Z14 None S 0.000 0.000 S
1 18'6 19.312 8X2.5Z16 None S 0.000 0.000 S
2 18'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 18'6 19.312 8X2.5Z16 None S 0.000 0.000 S
Bay Elev. Length Member Size Brace L Lap R Lap
# (ft-in) (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
1 23'6 7.392 8X2.5Z16 None S 0.000 0.000 S
2 23'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 23'6 7.392 8X2.5Z16 None S 0.000 0.000 S
Framed Openings:
Width Height Sill Ht Jamb Header/Sill Bay Distance
14'0 10'0 N/A 8X3.5C14 *8X2.5C14 3 3'0
*- Change Manually
Page 13
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
Columns-----(0.000" Flush columns)
Col Dist. Description Base Elev Base plate design information
# from left Member Size Ident. (ft) Thickness & rods
-----------------------------------------------------------------------------
LCC 0.000' W8X10 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
1-D 20.000' W8X10 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
1-C 30.000' W8X10 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
RCC 50.000' W8X18 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
ENDWALL COLUMN TO BRIDGE CHANNEL CONNECTIONS:
Strut-to-Column Clip
Col. No. Endwall Plane 1
--------- --------------------
Plane SWC:
1-D BETWEEN PURLINS, USING TYPE 3 CONN.,(4)-1/2" A325N
CF Brdg Channel (0.375") w/ (4)-3/4" A325N bolts
W8x10 COLUMN EXTENSION BEVELED w/ 12.000 " LAP LENGTH;
8X2.5C12 BRIDGE CHANNEL
1-C BETWEEN PURLINS, USING TYPE 3 CONN.,(4)-1/2" A325N
CF Brdg Channel (0.375") w/ (4)-3/4" A325N bolts
W8x10 COLUMN EXTENSION BEVELED w/ 12.000 " LAP LENGTH;
8X2.5C12 BRIDGE CHANNEL
PLANE SWA:
Page 14
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
Endwall Plane EWD Design ........BEARING FRAME
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\AwallEWD_01.edf
Panel .................... PBR
Panel width .............. 36 in.
Panel gage ............... 26 ga.
Rafters -----
Mem Description Length Start End
# Member Size Identification (ft) (ft) (ft)
--------------------------------------------------------------
1 W8X10 50.0 ksi 25.101 0.000 25.101
Connections... Left : Type-IV SEP 6.000" X 3/8" (2)-1/2" A325N Bolts
Right: Type-II MEP 6.000" X 3/8" (4)-1/2" A325N Bolts
2 W8X10 50.0 ksi 25.101 25.101 50.201
Connections... Left : Type-II MEP 6.000" X 3/8" (4)-1/2" A325N Bolts
Right: Type-IV SEP 6.000" X 3/8" (2)-1/2" A325N Bolts
Flange Braces at following purlins (horizontal distance from eave) :
PLANE SWA: None
PLANE SWC: None
Girts .................... 55.0 ksi yield strength
Girts Spacing: 7'6 6'0 2@5'0
Bay Elev. Length Member Size Brace L Lap R Lap
# (ft-in) (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
1 7'6 19.312 8X2.5Z13 None S 0.000 0.000 S
2 7'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 7'6 19.312 8X2.5Z16 None S 0.000 0.000 S
1 13'6 19.312 8X2.5Z14 None S 0.000 0.000 S
2 13'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 13'6 19.312 8X2.5Z12 None S 0.000 0.000 S
1 18'6 19.312 8X2.5Z16 None S 0.000 0.000 S
2 18'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 18'6 19.312 8X2.5Z16 None S 0.000 0.000 S
Bay Elev. Length Member Size Brace L Lap R Lap
# (ft-in) (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
1 23'6 7.392 8X2.5Z16 None S 0.000 0.000 S
2 23'6 10.000 8X2.5Z16 None S 0.000 0.000 S
3 23'6 7.392 8X2.5Z16 None S 0.000 0.000 S
Framed Openings:
Width Height Sill Ht Jamb Header/Sill Bay Distance
8'4 8'2-1/2 N/A *8X2.5C14 8X2.5C16 3 8'0
*-change Manually
Page 15
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
Columns-----(0.000" Flush columns)
Col Dist. Description Base Elev Base plate design information
# from left Member Size Ident. (ft) Thickness & rods
-----------------------------------------------------------------------------
LCC 0.000' W10X22 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
4-C 20.000' W8X10 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
4-D 30.000' W8X10 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
RCC 50.000' W8X10 50.0 ksi 0.0000' 0.375" BP thk w/( 4)-0.625" A36
ENDWALL COLUMN TO BRIDGE CHANNEL CONNECTIONS:
Strut-to-Column Clip
Col. No. Endwall Plane 4
--------- --------------------
Plane SWA:
4-C BETWEEN PURLINS, USING TYPE 3 CONN.,(4)-1/2" A325N
CF Brdg Channel (0.375") w/ (4)-3/4" A325N bolts
W8x10 COLUMN EXTENSION BEVELED w/ 12.000 " LAP LENGTH;
8X2.5C12 BRIDGE CHANNEL
4-D BETWEEN PURLINS, USING TYPE 3 CONN.,(4)-1/2" A325N
CF Brdg Channel (0.375") w/ (4)-3/4" A325N bolts
W8x10 COLUMN EXTENSION BEVELED w/ 12.000 " LAP LENGTH;
8X2.5C12 BRIDGE CHANNEL
PLANE SWC:
Page 16
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
LEAN TO BLDG B ON SIDE SWA DESIGN SUMMARY REPORT
All connections use ASTM F3125 Gr. A325N bolts, unless noted otherwise.
All anchor rods are checked according to ASTM F1554 Gr. 36 strengths.
ROOF PLANE ------- RPA
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\BroofRPA_01.edf
Panel .................... UDEK
Panel width .............. 24 in.
Panel gage ............... 24 ga.
Purlins .................. 55.0 ksi yield strength
Eave struts .............. 55.0 ksi yield strength
Purlin Spacing: 2@3'0 4'0 2'0
Bay Length Member Size Brace L Lap R Lap
# (ft) Identification Locations Exten Exten
---------------------------------------------------------------------
LE 2.333 8X2.5Z16 None 0.000 0.000 C
1 19.667 8X2.5Z16 2 points C 0.000 1.479 C
2 20.000 8X2.5Z16 2 points C 1.479 1.479 C
3 19.667 8X2.5Z16 2 points C 1.479 0.000 C
RE 2.333 8X2.5Z16 None C 0.000 0.000
Purlin Clip Use 2 A325 Bolts @ Level 2,3,4 @ Supports: 1,2,3,4
Purlin Stiffened Clips @ Level 2,4 @ Supports: 1,2,3,4
Purlin Backup Plate @ Level 2,4 @ Supports: 1,2,3,4
SWA Eave Strut @ 16.000 (ft) :8X3.5E14 Bays 1
SWA Eave Strut @ 16.000 (ft) :8X3.5E14 Bays 2
SWA Eave Strut @ 16.000 (ft) :8X3.5E14 Bays 3
Note: 1) All Purlin strut locations for all roof planes are measured from back
sidewall.
2) All purlin strut rows use the same lap lengths as the main purlin design.
Eave strut interior connection at SWA uses (2)-1/2" A325 bolts.
Eave strut connection at end-frame uses (4)-1/2" A325 bolts.
BRACING ----
Roof: 1 bays Rod (Add bracing to 2 other bays manually)
Plane SWA :Other constr.
Plane EWD :End Frame
Plane EWB :End Frame
Page 17
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
Sidewall Plane SWA -- (8.250" Inset columns)
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\BwallSWA_01.edf
Panel .................... PBR
Panel width .............. 36 in.
Panel gage ............... 26 ga.
Girts Spacing: N/A
Open Areas:
Size Wall Distance
(*)60'0 x 16'0 SWA 0'0
Endwall Plane EWD Design ........EXPANDABLE FRAME
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\BwallEWD_01.edf
Panel .................... PBR
Panel width .............. 36 in.
Panel gage ............... 26 ga.
Girts Spacing: N/A
Open Areas:
Size Wall Distance
(*)12'0 x 20'0 EWD 0'0
Endwall Plane EWB Design ........NON-EXPANDABLE FRAME
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\BwallEWB_01.edf
Panel .................... PBR
Panel width .............. 36 in.
Panel gage ............... 26 ga.
Girts Spacing: N/A
Open Areas:
Size Wall Distance
(*)12'0 x 20'0 EWB 0'0
(*)-OPEN TO REMAIN OPEN FOR WIND
Page 18
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
A-SWC-CF01 CANOPY DESIGN SUMMARY REPORT
Building Data
Roof Live Load: 20.00 psf
CANOPY 2'0 x 59'4 x 20'0 4.:12 Tributary Check: No
Bays: 19'8 20'0 19'8
Roof Snow Load: 0.00 psf
Wind Exposure Category: C Wind Load: 100.00 mph
Dead Load: 3.79 psf
--------------------------------------------------------------------------------
Panels ----- Roof: UDEK
Panel width .............. 24 in.
Panel gage ............... 24 ga.
PURLINS ---- Spacings(From Free-End): 2'0
Bay Length Member Size Brace L Lap R Lap Bear
# (ft) Identification Locations Exten Exten Stiff
---------------------------------------------------------------------
1 2 points
2 2 points
3 2 points
1- 3 <No purlin design for this plane>
EAVE STRUTS ---- 8X3.5C14 @ Bays 1 - 3
Rafter ---- Hot-Rolled
Length Mem Depths at Member Description
(ft) Start(in) End(in)
---------------------------------------------------------------------
4.083 7.890 7.890 **W8X10
**-USE (4) 1/2” DIAM. A325 BOLTS FOR TYPE IF CONNECTION (MIN. GA. 2.5”)
Page 19
09/23/2021
Metallic
Design Summary Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/22/21
Start Time: 06:21:55
R:\..\18-B-31650\ver02-mmfarahani\BLDG-A\run01\31650A_bldg_A_01.cds
-------------------------------------------------------------------------------
B-SWA-CF01 CANOPY DESIGN SUMMARY REPORT
Building Data
Roof Live Load: 20.00 psf
CANOPY 2'0 x 59'4 x 16'0 4.:12 Tributary Check: No
Bays: 19'8 20'0 19'8
Roof Snow Load: 0.00 psf
Wind Exposure Category: C Wind Load: 100.00 mph
Dead Load: 3.79 psf
--------------------------------------------------------------------------------
Panels ----- Roof: UDEK
Panel width .............. 24 in.
Panel gage ............... 24 ga.
PURLINS ---- Spacings(From Free-End): 2'0
Bay Length Member Size Brace L Lap R Lap Bear
# (ft) Identification Locations Exten Exten Stiff
---------------------------------------------------------------------
1 2 points
2 2 points
3 2 points
1- 3 <No purlin design for this plane>
EAVE STRUTS ---- 8X3.5C14 @ Bays 1 - 3
Rafter ---- Hot-Rolled
Length Mem Depths at Member Description
(ft) Start(in) End(in)
---------------------------------------------------------------------
4.083 7.890 7.890 **W8X10
**-USE (4) 1/2” DIAM. A325 BOLTS FOR TYPE IF CONNECTION (MIN. GA. 2.5”)
Page 20
09/23/2021
Building: BLDG-A
CDS file name: 18-B-31650_BLDG-A_Eds2Xds.cds
Eds2Xds User: mmfarahani Job Number: 18-B-31650
Fairview Date: 09/23/2021 03:24:42 PM
Relative path: \\HOUNA04\TS\jobs\Active\Eng\18-B-31650
----------------------------------------------------------------------------------------------------------------------------
Planes
Name File
SWA \ver02-mmfarahani\BLDG-A\run01\AwallSWA_01.edf
EWD \ver02-mmfarahani\BLDG-A\run01\AwallEWD_01.edf
SWC \ver02-mmfarahani\BLDG-A\run01\AwallSWC_01.edf
EWB \ver02-mmfarahani\BLDG-A\run01\AwallEWB_01.edf
RPA \ver02-mmfarahani\BLDG-A\run01\AroofRPA_01.edf
RPC \ver02-mmfarahani\BLDG-A\run01\AroofRPC_01.edf
Frames
Frame
Line
Left
Frame
Left File Right
Frame
Right File
2 A \ver02-mmfarahani\BLDG-
A\DRFTG\x03L
B \ver02-mmfarahani\BLDG-
A\DRFTG\x03R
3 A \ver02-mmfarahani\BLDG-
A\DRFTG\x03L
B \ver02-mmfarahani\BLDG-
A\DRFTG\x03R
Portal Frames
Plane
Name
Bay Frame File
SWA 3 F \ver02-mmfarahani\BLDG-A\DRFTG\x05L
Page 21
09/23/2021
Note: Nested Portal Frame
Building: BLDG-B
CDS file name: 18-B-31650_BLDG-B_Eds2Xds.cds
Eds2Xds User: mmfarahani Job Number: 18-B-31650
Fairview Date: 09/23/2021 03:24:42 PM
Relative path: \\HOUNA04\TS\jobs\Active\Eng\18-B-31650
----------------------------------------------------------------------------------------------------------------------------
Planes
Name File
SWA \ver02-mmfarahani\BLDG-A\run01\BwallSWA_01.edf
EWD \ver02-mmfarahani\BLDG-A\run01\BwallEWD_01.edf
EWB \ver02-mmfarahani\BLDG-A\run01\BwallEWB_01.edf
RPA \ver02-mmfarahani\BLDG-A\run01\BroofRPA_01.edf
Frames
Frame Line Left Frame Left File
4 C \ver02-mmfarahani\BLDG-A\DRFTG\x01L
3 C \ver02-mmfarahani\BLDG-A\DRFTG\x01L
2 C \ver02-mmfarahani\BLDG-A\DRFTG\x01L
1 B \ver02-mmfarahani\BLDG-A\DRFTG\x02L
Portal Frames
Plane
Name
Bay Frame File
Page 22
09/23/2021
25'12345678I.F.WEB LEN.WEB THK.O.F.I.F.WEB LEN.WEB THK.O.F.0.1560.250.15610.0'7.857'14.205'10.0'5X0.255X0.255X0.255X0.2510'0"7.857'4.205'10'0"10'0"17'10 1/4"26'4"CCCCCCC20' E.H.4.012Metallic Building SystemsMetallic Building SystemsMetallic Building SystemsFRAME ID #FRAME ID #3USER NAME:USER NAME:mmfarahaniDATE:DATE: 9/22/21TIME:TIME:18:26:36PAGE:PAGE: 3 -1cs 50./20./19.833 20./100./0. JOB NAME:JOB NAME:31650AFILE:FILE:frame_2_3.fraLOCATION: GridlinesLOCATION:23DETAIL FILE: tive\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\Drftg\x03LDETAIL FILE:BOLTS:A325 FULLY TIGHT WEIGHT: 2165 lbsPURLINS(horz. from eave) :8"-Z 2@3'3 11/16",4@4'4"GIRTS (vert. from floor): 8"-Z 7'6",6'(8.25")(1) All sectional dimensions are in inches.(2) All Flange lengths are measured along outer flange.CONNECTION DETAILS :CONNECTION DETAILS :CONNECTION DETAILS : GRIDLINES * =23LocationLocationWeb Dep.Web Dep.TypeTypePlate(DN)PlatePlate(UP)PlateBoltsBolts10.0BASE6.0X0.375N/A(4)-3/417.8400SPLICEN/AN/AN/A24.0HORZ STF2.25X0.25N/AN/AN/ACAP (EXT)6.0X0.375N/AN/A26.02E/2E6.0X0.756.0X0.75(8)-3/422.4479SPLICEN/AN/AN/A14.0SPLICEN/AN/AN/A14.02E/2E6.0X0.3756.0X0.375(8)-3/4*-E12345678Page 23 09/23/2021
25'1234
5678 I.F.
WEB LEN.
WEB THK.
O.F. I.F. WEB LEN. WEB THK. O.F.0.25 0.156
0.1567.857'10.0'10.0'14.205'8X0.25
5X0.258X0.25
5X0.257.857'10'0"10'0"10'0"4.205'17'10 1/4"
26'4"AOOC
CCCCC20' E.H.4.012Metallic Building SystemsMetallic Building SystemsMetallic Building SystemsFRAME ID #FRAME ID #3USER NAME:USER NAME:mmfarahaniDATE:DATE: 9/22/21TIME:TIME:18:26:36PAGE:PAGE: 3 -2cs 50./20./19.833 20./100./0. JOB NAME:JOB NAME:31650AFILE:FILE:frame_2_3.fraLOCATION: GridlinesLOCATION:23DETAIL FILE: tive\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\Drftg\x03RDETAIL FILE:BOLTS:A325 FULLY TIGHT WEIGHT: 2165 lbsPURLINS(horz. from eave) :8"-Z 2@3'3 11/16",4@4'4"GIRTS (vert. from floor): 8"-Z 7'6",6',3'(8.25")(1) All sectional dimensions are in inches.(2) All Flange lengths are measured along outer flange.CONNECTION DETAILS :CONNECTION DETAILS :CONNECTION DETAILS : GRIDLINES * =23LocationLocationWeb Dep.Web Dep.TypeTypePlate(DN)PlatePlate(UP)PlateBoltsBolts10.0BASE8.0X0.375N/A(4)-3/417.8400SPLICEN/AN/AN/A24.0HORZ STF3.75X0.25N/AN/AN/ACAP (EXT)8.0X0.375N/AN/A26.02E/2E8.0X0.756.0X0.75(8)-3/422.4479SPLICEN/AN/AN/A14.0SPLICEN/AN/AN/A14.02E/2E6.0X0.3756.0X0.375(8)-3/4*-B12345678ANONELT STIFN/AN/AN/APage 24 09/23/20210.0.0.0.200.000.0.000.0.5
12'123456I.F.W SHAPEO.F.I.F.W SHAPEO.F.W10X22W10X1210'0"4.921'11.297'14'11"18'5 7/8"16' E.H.4.012Metallic Building SystemsMetallic Building SystemsMetallic Building SystemsFRAME ID #FRAME ID #2USER NAME:USER NAME:mmfarahaniDATE:DATE: 9/22/21TIME:TIME:18:27:46PAGE:PAGE: 2 -1lt 12./16./12.167 20./100./0. JOB NAME:JOB NAME:31650AFILE:FILE:ltfrar_1_.fraLOCATION: GridlinesLOCATION:1DETAIL FILE: tive\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\Drftg\x02LDETAIL FILE:BOLTS:A325 FULLY TIGHT WEIGHT: 517 lbsPURLINS(horz. from eave) :8"-Z 2@3',4'GIRTS (vert. from floor): 8"-Z (8.25")- LEFT COLUMN(1) All sectional dimensions are in inches.(2) All Flange lengths are measured along outer flange.CONNECTION DETAILS :CONNECTION DETAILS :CONNECTION DETAILS : GRIDLINES * =1LocationLocationWeb Dep.Web Dep.TypeTypePlate(DN)PlatePlate(UP)PlateBoltsBolts10.2BASE6.0X0.375N/A(4)-5/810.2SPLICEN/AN/AN/A10.2N/AN/AN/AN/AN/ACAP (EXT)6.0X0.25N/AN/A9.872P/05.75X0.365.0X0.25(4)-1/29.872P/05.0X0.255.0X0.25(4)-1/2*-A1234563"3"TYPICAL AT KNEE AND PEAKPage 25 09/23/2021
12'123456I.F.W SHAPEO.F.I.F.W SHAPEO.F.W10X22W10X1210'0"4.921'11.297'14'11"18'5 7/8"CC16' E.H.4.012Metallic Building SystemsMetallic Building SystemsMetallic Building SystemsFRAME ID #FRAME ID #1USER NAME:USER NAME:mmfarahaniDATE:DATE: 9/22/21TIME:TIME:18:28:34PAGE:PAGE: 1 -1lt 12./16./20. 20./100./0. JOB NAME:JOB NAME:31650AFILE:FILE:ltfrar_2-4.fraLOCATION: GridlinesLOCATION:432DETAIL FILE: tive\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\Drftg\x01LDETAIL FILE:BOLTS:A325 FULLY TIGHT WEIGHT: 523 lbsPURLINS(horz. from eave) :8"-Z 2@3',4'GIRTS (vert. from floor): 8"-Z (8.25")- LEFT COLUMN(1) All sectional dimensions are in inches.(2) All Flange lengths are measured along outer flange.CONNECTION DETAILS :CONNECTION DETAILS :CONNECTION DETAILS : GRIDLINES * =432LocationLocationWeb Dep.Web Dep.TypeTypePlate(DN)PlatePlate(UP)PlateBoltsBolts10.2BASE6.0X0.375N/A(4)-3/410.2SPLICEN/AN/AN/A10.2N/AN/AN/AN/AN/ACAP (EXT)6.0X0.25N/AN/A9.872P/05.75X0.365.0X0.25(4)-1/29.872P/05.0X0.255.0X0.25(4)-1/2*-A1234563"3"TYPICAL AT KNEE AND PEAKPage 26 09/23/2021
19'8"12345678910
I.F.WEB LEN.WEB THK.O.F.I.F.WEB LEN.WEB THK.O.F. I.F.
WEB LEN.
WEB THK.
O.F.0.1560.31250.1560.3125 0.156
10.0'7.458'16.521'7.458'10.0'6X0.256X0.3758X0.256X0.375 6X0.25
6X0.31256X0.3758X0.256X0.375 6X0.3125
10'0"7.458'16.521'7.458'10'0"17'5 1/2"
17'5 1/2"20' E.H.20' E.H.0.012Metallic Building SystemsMetallic Building SystemsMetallic Building SystemsFRAME ID #FRAME ID #5USER NAME:USER NAME:mmfarahaniDATE:DATE: 9/22/21TIME:TIME:18:29:22PAGE:PAGE: 5 -1pf 19.667/20. main building at plane SW JOB NAME:JOB NAME:31650AFILE:FILE:p5_.fraLOCATION:LOCATION:bays 3-(Gridline B)DETAIL FILE: tive\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\Drftg\x05LDETAIL FILE:BOLTS:A325 FULLY TIGHT WEIGHT: 1709 lbsRafter Offset : (14")Column Offsets : (0.12")- LEFT COLUMN(0.12")- RIGHT COLUMN(1) All sectional dimensions are in inches.(2) All Flange lengths are measured along outer flange.CONNECTION DETAILS :CONNECTION DETAILS :CONNECTION DETAILS : GRIDLINES * =BLocationLocationWeb Dep.Web Dep.TypeTypePlate(DN)PlatePlate(UP)PlateBoltsBolts18.0BASE6.0X0.375N/A(4)-3/418.0SPLICEN/AN/AN/A18.0HORZ STF2.75X0.25N/AN/AN/ACAP (EXT)6.0X0.375N/AN/A16.03E/3E12.0X0.75 C12.0X0.75 R(12)-116.03E/3E12.0X0.75 C12.0X0.75 R(12)-118.0BASE6.0X0.375N/A(4)-3/418.0SPLICEN/AN/AN/A18.0HORZ STF2.75X0.25N/AN/AN/ACAP (EXT)6.0X0.375N/AN/A*-LEFT123456*-RIGHT78910CJP1/4Typicalat Both ColumnsTypicalat Both ColumnsTYPSee Page # Bolted connection to main FramecolumnsPage 27 09/23/202128 -
Page 28
09/23/2021
At Grade Line 3
(+)
Rev H 6/15/20
REACTIONS
BUILDER: EMPIRE STEEL BUILDINGS **
CUSTOMER: NONE
JOB NUMBER: 18-B-31650
Notes
1) The reactions provided are based on the Order Documents at the time of mailing. Any changes to building loads or
dimensions may change the reactions. The reactions will be superseded and voided by any future mailing.
2) The reactions provided have been created with the following layout (unless noted otherwise).
a) A reaction table is provided with the reactions for each load group.
b) Rigid Frames
(1) See Note 3.
c) Endwalls
(1) See Note 3.
d) X-Bracing
(1) X- Bracing reactions are included in values shown in the reaction tables.
(2) For IBC and UBC based building codes, when x-bracing is present in the sidewall, individual
longitudinal seismic loads (RBUPEQ, RBDWEQ, E+, E- and LEQ) do not include the amplification
factor, :0.
(3) For IBC and UBC based building codes, when x-bracing is present in the endwall, individual transverse
seismic loads (EL & ER) do not include the amplification factor, :0.
e) The metal building manufacturer is responsible only for the portion of the anchor rod design pertaining to the
transfer of forces between the base plate bearing and the anchor rod’s shear and tension. The metal building
manufacturer is not responsible for the anchor rod embedment for transfer of forces to the foundation. The metal
building manufacturer does not design and is not responsible for the design, material, and construction of the
foundation embedments. The end use customer shall assure that adequate provisions are made to the foundation
design for loads imposed by column reactions of the building, other imposed loads, and bearing capacity of the
soil and other conditions of the building site. It is recommended that the anchorage and foundation of the
building be designed by a registered professional engineer competent in the design of such structures.
i) (ref. Appendix A3 of the MBMA Metal Building Systems Manual)
f) Anchor rods are ASTM F1554 Gr. 36 material unless noted otherwise on the anchor rod layout drawing.
3) Reactions are provided as un-factored for each load group applied to the column. The factors applied to load groups
for the steel column design may be different than the factors used in the foundation design. The foundation engineer
shall apply the appropriate load factors and combine the reactions in accordance with the building code and design
specifications for proper foundation design.
a) For projects using ultimate design wind speeds such as 2012 IBC, 2015 IBC, or Florida building code, the wind
load reactions are at a strength value with a load factor of 1.0.
b) For IBC codes, the seismic reactions provided are at a strength level with a load factor of 1.0, and do not contain
the rho factor.
The manufacturer does not provide "maximum" load combination reactions. However, the individual load reactions
provided may be used by the foundation engineer to determine the applicable load combinations for his/her design
procedures and allow for an economical foundation design.
Page 1
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8
Metallic Building Systems User: mmfarahani Page: F3- 1
R-Frame Design Program - Version V8.15 Job : 31650A
Input Data Echo File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
\\hounas04\TS\Jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\
--------------------------------------------------------------------------------
VERSION V8.15
BRAND METALLIC
DESCRIPTION cs 50./20./19.833 20./100./0.
FRAME_ID 3
# FRAME LEFT SIDE IS BLDG. PLANE SWC
# AND FRAME RIGHT SIDE IS BLDG. PLANE SWA
PRINT echo code loads base connection deflection profile seismic detail \
flg_brace summary l_stiffeners pro_grplds
OPTIMIZATION none *PLANT atw *JOB 31650A
ANALYZE all *DATASET members brace combinations wind_array connection base
BUILDING LABEL A
LOCATION frame lines 2 3
LATERAL GRID LABEL 2 3
LONGITUDINAL GRID LABEL E B
NUMBER FRAMES 2 *PRICE summary
TYPE LEFT cs t cs 60. 60.
TYPE RIGHT cs t cs 60. 60.
MAIN GEOMETRY
WIDTH 50. 25.
LENGTH 60.
EAVE 20. *ROOF SLOPE 4.
LEANTO RIGHT GEOMETRY
WIDTH 12. 0.
LENGTH 60.
EAVE 16. *ROOF SLOPE 4.
GIRT DEPTH 8. 8.25 *PURLIN DEPTH 8. 8.25
GIRT THICKNESS 0.059 *PURLIN THICKNESS 0.059
GIRT FLANGE 2.5 *PURLIN FLANGE 2.5
PURLIN STIFFNESS 30.882 12.936 7.865 6.484
CODE LABEL 2019 CALIFORNIA BUILDING CODE
BUILDING CODE IB18 U=Normal
DEAD LOAD 2.623 *COLLATERAL LOAD 5.
LIVE LOAD 20. reduce
SNOW R=0. E=0.9 T=1.2 S=N WEL=27. WER=39. WML=25. WMR=37.
SEISMIC LOAD S1=42.5 SS=118.3 TL=16. %CR=NORM %SR=NORM RHOT=1.5 RHOL=1.3 \
R=3.5 LOF=2. TOF=2.5 RL=3.25 Cd=3. Ct=0.028
SOIL PROFILE D
SECOND ORDER FOA
###Increased Trib. by 5% for accidental eccentricity###
ROOF TRIBUTARY TR=20.833
WALL TRIBUTARY LEFT TR= 20.833 S=0. E=20.
WALL TRIBUTARY RIGHT TR= 0. S=0. E=20.
####
DESIGN ASD16
LATERAL BRACE LENGTH 20.00
STIFFNESS CHECK SNOW ONLY
BOLT TIGHTENING Fully
NOFB 0.
DEFLECTION ROOF L=180. S=180. W=180. G=120.
DEFLECTION WALL L=60. S=60. W=60. E=40. C=100. G=60. TE=40.
MIN_MOMT_BOLT_DIA 0.5
CANOPYL CFT=C FL=Y PR=2. LEN=64. HT=20. CS=4. PD=8. FT=0.205 WH=7.48 MN=5. \
0.375 BAY=19.833 DL=4.508 LL=20. WL1=-27.991 -1.39 WL2=-27.991 -1.39 \
LWL1=-13.8948 -0.69 LWL2=-7.4508 -0.37 LWL3=-6.6454 -0.33 LWL4=-0.2014 -0.01 \
MWL1=-27.991 -1.39 MWL2=-9.4646 -0.47 WL3=-9.4646 -0.47 WL4=-9.4646 -0.47 \
WL1D=-12.608 -1.39 WL2D=-12.608 -1.39 LWL1D=-6.2586 -0.69 LWL2D=-3.3561 -0.37 \
LWL3D=-2.9933 -0.33 LWL4D=-0.0907 -0.01 WL3D=-4.2631 -0.47 WL4D=-4.2631 -0.47
SYMKNEE CONNECTION
SPLICE GUSSETS NA
LT BOSS RIGHT HT=19.2973 LEN=8.25 DEPF=10.23 BF=5. TF=0.25 TW=0.134 EPW=5. \
EPD=10.75 EPT=0.25 BTD=0.5 BTN=2
BRACING SIDES LC=1 RA=1 RC=1
BRACE ATTACHMENT FLANGE
FLANGE BRACE ATTACHMENT LC=0 RA=0 RC=0
GIRT SPACING LEFT 7.5 6.
GIRT SPACING RIGHT 7.5 6. 3.
GIRT BRACE LEFT C C
GIRT BRACE RIGHT O O C
PURLIN SPACING 2@3.3097 4@4.3333
PURLIN BRACE C C N C C C
LEFT COLUMN
BASE W=6. T=0.375 L=10.5 N=2 D=0.75
10. 0. 10. 5. 0.25 0.156 5. 0.25
0. 24. 0. 5. 0.25 0.25 5. 0.25
LEFT RAFTER
CONNECTION O=2E I=2E W=6. T=0.75 D=0.75
26. 0. 0. 5. 0.25 0.156 5. 0.25
0. 14. 10. 5. 0.25 0.156 5. 0.25
14. 14. 10. 5. 0.25 0.156 5. 0.25
CONNECTION O=2E I=2E W=6. T=0.375 D=0.75
RIGHT COLUMN
BASE W=8. T=0.375 L=10.5 N=2 D=0.75
10. 0. 10. 8. 0.25 0.156 8. 0.25
0. 24. 0. 8. 0.25 0.25 8. 0.25
RIGHT RAFTER
CONNECTION O=2E I=2E W=8. 6. T=0.75 D=0.75
26. 0. 0. 5. 0.25 0.156 5. 0.25
0. 14. 10. 5. 0.25 0.156 5. 0.25
14. 14. 10. 5. 0.25 0.156 5. 0.25
WIND LOAD WL1 20.137 0.3400 -0.8700 -0.6500 -0.6000 25.000 Left
WIND LOAD WL2 20.137 0.7000 -0.5100 -0.2900 -0.2400 25.000 Left
WIND LOAD LWL1 20.137 -0.6300 -0.8700 -0.5500 -0.6300 25.000
WIND LOAD LWL2 20.137 -0.6300 -0.5500 -0.8700 -0.6300 31.000
WIND LOAD LWL3 20.137 -0.2700 -0.5100 -0.1900 -0.2700 25.000
WIND LOAD LWL4 20.137 -0.2700 -0.1900 -0.5100 -0.2700 31.000
WIND LOAD MWL1 16.000 0.5000 0.2500 0.2500 -0.5000 0.000
WIND LOAD MWL2 16.000 -0.5000 -0.2500 -0.2500 0.5000 0.000
WIND LOAD WL3 20.137 -0.6000 -0.6500 -0.8700 0.3400 31.000 Right
WIND LOAD WL4 20.137 -0.2400 -0.2900 -0.5100 0.7000 31.000 Right
WIND LOAD WL1D 9.071 0.3400 -0.8700 -0.6500 -0.6000 25.000 Left
WIND LOAD WL2D 9.071 0.7000 -0.5100 -0.2900 -0.2400 25.000 Left
WIND LOAD LWL1D 9.071 -0.6300 -0.8700 -0.5500 -0.6300 25.000
WIND LOAD LWL2D 9.071 -0.6300 -0.5500 -0.8700 -0.6300 31.000
WIND LOAD LWL3D 9.071 -0.2700 -0.5100 -0.1900 -0.2700 25.000
WIND LOAD LWL4D 9.071 -0.2700 -0.1900 -0.5100 -0.2700 31.000
WIND LOAD WL3D 9.071 -0.6000 -0.6500 -0.8700 0.3400 31.000 Right
WIND LOAD WL4D 9.071 -0.2400 -0.2900 -0.5100 0.7000 31.000 Right
LOAD COMBINATIONS
1)1. DL 1. COLL 1. PLLL1 1. PLL1 *DEFL 60. 120. *PDELTA L
2)1. DL 1. COLL 1. PLLL1 1. PLL1 *DEFL 60. 120. *PDELTA R
3)1. DL 1. COLL 1. PLL1 1. PLLR1 *DEFL 60. 120. *PDELTA L
4)1. DL 1. COLL 1. PLL1 1. PLLR1 *DEFL 60. 120. *PDELTA R
5)1. DL 1. COLL 1. PLLL1 1. PLLR1 *DEFL 60. 120. *PDELTA L
6)1. DL 1. COLL 1. PLLL1 1. PLLR1 *DEFL 60. 120. *PDELTA R
7)1. DL 1. COLL 1. PLL1 *DEFL 60. 120. *PDELTA L
8)1. DL 1. COLL 1. PLL1 *DEFL 60. 120. *PDELTA R
9)1. DL 1. LL 1. COLL *DEFL 60. 120. *PDELTA L
10)1. DL 1. LL 1. COLL *DEFL 60. 120. *PDELTA R
11)1.1325 DL 1.1325 COLL 0.91 RBDWEQ *DEFL 60. 120. *PDELTA L
12)1.1325 DL 1.1325 COLL 0.91 RBDWEQ *DEFL 60. 120. *PDELTA R
13)1.1325 DL 1.05 EQ *DEFL 40. 120. *PDELTA L
14)1.1325 DL 1.05 EQ *DEFL 40. 120. *PDELTA R
15)1.1325 DL -1.05 EQ *DEFL 40. 120. *PDELTA L
16)1.1325 DL -1.05 EQ *DEFL 40. 120. *PDELTA R
17)1.1325 DL 1.1325 COLL 1.05 EQ *DEFL 40. 120. *PDELTA L
18)1.1325 DL 1.1325 COLL 1.05 EQ *DEFL 40. 120. *PDELTA R
19)1.1325 DL 1.1325 COLL -1.05 EQ *DEFL 40. 120. *PDELTA L
20)1.1325 DL 1.1325 COLL -1.05 EQ *DEFL 40. 120. *PDELTA R
21)0.4675 DL 0.91 RBUPEQ *DEFL 60. 120. *PDELTA L
22)0.4675 DL 0.91 RBUPEQ *DEFL 60. 120. *PDELTA R
23)0.4675 DL 1.05 EQ *DEFL 40. 120. *PDELTA L
24)0.4675 DL 1.05 EQ *DEFL 40. 120. *PDELTA R
25)0.4675 DL -1.05 EQ *DEFL 40. 120. *PDELTA L
26)0.4675 DL -1.05 EQ *DEFL 40. 120. *PDELTA R
27)0.71072 DL 2. RBUPEQ *TYPE R *APP C *PDELTA L
28)0.71072 DL 2. RBUPEQ *TYPE R *APP C *PDELTA R
29)1.38928 DL 1.38928 COLL 2. RBDWEQ *TYPE R *APP C *PDELTA L
30)1.38928 DL 1.38928 COLL 2. RBDWEQ *TYPE R *APP C *PDELTA R
31)0.71072 DL 2.5 EQ *TYPE R *APP C *PDELTA L
32)0.71072 DL 2.5 EQ *TYPE R *APP C *PDELTA R
33)0.71072 DL -2.5 EQ *TYPE R *APP C *PDELTA L
34)0.71072 DL -2.5 EQ *TYPE R *APP C *PDELTA R
35)1.38928 DL 1.38928 COLL 2.5 EQ *TYPE R *APP C *PDELTA L
36)1.38928 DL 1.38928 COLL 2.5 EQ *TYPE R *APP C *PDELTA R
37)1.38928 DL 1.38928 COLL -2.5 EQ *TYPE R *APP C *PDELTA L
38)1.38928 DL 1.38928 COLL -2.5 EQ *TYPE R *APP C *PDELTA R
39)0.71072 DL 2. RBUPEQ *TYPE R *APP B *PDELTA L
40)0.71072 DL 2. RBUPEQ *TYPE R *APP B *PDELTA R
41)1.38928 DL 1.38928 COLL 2. RBDWEQ *TYPE R *APP B *PDELTA L
42)1.38928 DL 1.38928 COLL 2. RBDWEQ *TYPE R *APP B *PDELTA R
43)0.71072 DL 2.5 EQ *TYPE R *APP B *PDELTA L
44)0.71072 DL 2.5 EQ *TYPE R *APP B *PDELTA R
45)0.71072 DL -2.5 EQ *TYPE R *APP B *PDELTA L
46)0.71072 DL -2.5 EQ *TYPE R *APP B *PDELTA R
47)1.38928 DL 1.38928 COLL 2.5 EQ *TYPE R *APP B *PDELTA L
48)1.38928 DL 1.38928 COLL 2.5 EQ *TYPE R *APP B *PDELTA R
49)1.38928 DL 1.38928 COLL -2.5 EQ *TYPE R *APP B *PDELTA L
50)1.38928 DL 1.38928 COLL -2.5 EQ *TYPE R *APP B *PDELTA R
51)0.71072 DL 3.5 EQ *TYPE R *APP K *PDELTA L
52)0.71072 DL 3.5 EQ *TYPE R *APP K *PDELTA R
53)0.71072 DL -3.5 EQ *TYPE R *APP K *PDELTA L
54)0.71072 DL -3.5 EQ *TYPE R *APP K *PDELTA R
55)1.38928 DL 1.38928 COLL 3.5 EQ *TYPE R *APP K *PDELTA L
56)1.38928 DL 1.38928 COLL 3.5 EQ *TYPE R *APP K *PDELTA R
57)1.38928 DL 1.38928 COLL -3.5 EQ *TYPE R *APP K *PDELTA L
58)1.38928 DL 1.38928 COLL -3.5 EQ *TYPE R *APP K *PDELTA R
59)1. DL 0.6 WL1 *PDELTA L
60)1. DL 0.6 WL1 *PDELTA R
61)1. DL 0.6 WL2 *PDELTA L
62)1. DL 0.6 WL2 *PDELTA R
63)1. DL 0.6 WL3 *PDELTA L
64)1. DL 0.6 WL3 *PDELTA R
65)1. DL 0.6 WL4 *PDELTA L
66)1. DL 0.6 WL4 *PDELTA R
67)0.6 DL 0.6 WL1 *PDELTA L
68)0.6 DL 0.6 WL1 *PDELTA R
69)0.6 DL 0.6 WL2 *PDELTA L
70)0.6 DL 0.6 WL2 *PDELTA R
71)0.6 DL 0.6 LWL1 0.6 RBUPLW *PDELTA L
72)0.6 DL 0.6 LWL1 0.6 RBUPLW *PDELTA R
73)0.6 DL 0.6 LWL2 0.6 RBUPLW *PDELTA L
74)0.6 DL 0.6 LWL2 0.6 RBUPLW *PDELTA R
75)0.6 DL 0.6 LWL3 0.6 RBUPLW *PDELTA L
76)0.6 DL 0.6 LWL3 0.6 RBUPLW *PDELTA R
77)0.6 DL 0.6 LWL4 0.6 RBUPLW *PDELTA L
78)0.6 DL 0.6 LWL4 0.6 RBUPLW *PDELTA R
79)0.6 DL 0.6 WL3 *PDELTA L
80)0.6 DL 0.6 WL3 *PDELTA R
81)0.6 DL 0.6 WL4 *PDELTA L
82)0.6 DL 0.6 WL4 *PDELTA R
83)0.6 MWL1 *TYPE M
84)0.6 MWL2 *TYPE M
85)1. DL 1. COLL 0.6 WL1 *PDELTA L
86)1. DL 1. COLL 0.6 WL1 *PDELTA R
87)1. DL 1. COLL 0.6 WL2 *PDELTA L
88)1. DL 1. COLL 0.6 WL2 *PDELTA R
89)1. DL 1. COLL 0.6 WL3 *PDELTA L
90)1. DL 1. COLL 0.6 WL3 *PDELTA R
91)1. DL 1. COLL 0.6 WL4 *PDELTA L
92)1. DL 1. COLL 0.6 WL4 *PDELTA R
93)1. DL 0.75 LL 1. COLL 0.45 WL1 *PDELTA L
94)1. DL 0.75 LL 1. COLL 0.45 WL1 *PDELTA R
95)1. DL 0.75 LL 1. COLL 0.45 WL2 *PDELTA L
96)1. DL 0.75 LL 1. COLL 0.45 WL2 *PDELTA R
97)1. DL 0.75 LL 1. COLL 0.45 LWL1 0.45 RBUPLW *PDELTA L
98)1. DL 0.75 LL 1. COLL 0.45 LWL1 0.45 RBUPLW *PDELTA R
99)1. DL 0.75 LL 1. COLL 0.45 LWL2 0.45 RBUPLW *PDELTA L
100)1. DL 0.75 LL 1. COLL 0.45 LWL2 0.45 RBUPLW *PDELTA R
101)1. DL 0.75 LL 1. COLL 0.45 LWL3 0.45 RBUPLW *PDELTA L
102)1. DL 0.75 LL 1. COLL 0.45 LWL3 0.45 RBUPLW *PDELTA R
103)1. DL 0.75 LL 1. COLL 0.45 LWL4 0.45 RBUPLW *PDELTA L
104)1. DL 0.75 LL 1. COLL 0.45 LWL4 0.45 RBUPLW *PDELTA R
105)1. DL 0.75 LL 1. COLL 0.45 WL3 *PDELTA L
106)1. DL 0.75 LL 1. COLL 0.45 WL3 *PDELTA R
107)1. DL 0.75 LL 1. COLL 0.45 WL4 *PDELTA L
108)1. DL 0.75 LL 1. COLL 0.45 WL4 *PDELTA R
109)1. DL 1. COLL 0.6 LWL1 0.6 RBDWLW *PDELTA L
110)1. DL 1. COLL 0.6 LWL1 0.6 RBDWLW *PDELTA R
111)1. DL 1. COLL 0.6 LWL2 0.6 RBDWLW *PDELTA L
112)1. DL 1. COLL 0.6 LWL2 0.6 RBDWLW *PDELTA R
113)1. DL 1. COLL 0.6 LWL3 0.6 RBDWLW *PDELTA L
114)1. DL 1. COLL 0.6 LWL3 0.6 RBDWLW *PDELTA R
115)1. DL 1. COLL 0.6 LWL4 0.6 RBDWLW *PDELTA L
116)1. DL 1. COLL 0.6 LWL4 0.6 RBDWLW *PDELTA R
117)1. DL 0.75 LL 1. COLL 0.45 LWL1 0.45 RBDWLW *PDELTA L
118)1. DL 0.75 LL 1. COLL 0.45 LWL1 0.45 RBDWLW *PDELTA R
119)1. DL 0.75 LL 1. COLL 0.45 LWL2 0.45 RBDWLW *PDELTA L
120)1. DL 0.75 LL 1. COLL 0.45 LWL2 0.45 RBDWLW *PDELTA R
121)1. DL 0.75 LL 1. COLL 0.45 LWL3 0.45 RBDWLW *PDELTA L
122)1. DL 0.75 LL 1. COLL 0.45 LWL3 0.45 RBDWLW *PDELTA R
123)1. DL 0.75 LL 1. COLL 0.45 LWL4 0.45 RBDWLW *PDELTA L
124)1. DL 0.75 LL 1. COLL 0.45 LWL4 0.45 RBDWLW *PDELTA R
125)1. LL *DEFL 60. 180. *TYPE D
126)1. WL1D *DEFL 60. 180. *TYPE D
127)1. WL2D *DEFL 60. 180. *TYPE D
128)1. LWL1D *DEFL 60. 180. *TYPE D
129)1. LWL2D *DEFL 60. 180. *TYPE D
130)1. LWL3D *DEFL 60. 180. *TYPE D
131)1. LWL4D *DEFL 60. 180. *TYPE D
132)1. WL3D *DEFL 60. 180. *TYPE D
133)1. WL4D *DEFL 60. 180. *TYPE D
134)1.38928 DL 1. EQ *DEFL 40. 0. *TYPE D *EQCD 3.0
135)1.38928 DL -1. EQ *DEFL 40. 0. *TYPE D *EQCD 3.0
136)0.71072 DL 1. EQ *DEFL 40. 0. *TYPE D *EQCD 3.0
137)0.71072 DL -1. EQ *DEFL 40. 0. *TYPE D *EQCD 3.0
138)1.38928 DL 1.38928 COLL 1. EQ *DEFL 40. 0. *TYPE D *EQCD 3.0
139)1.38928 DL 1.38928 COLL -1. EQ *DEFL 40. 0. *TYPE D *EQCD 3.0
LOADS
### Torsional loading Note:Torsional load is about 0.5k, but kept 1 kips used
### 1 kips used by Anchor Rods teams.
RC LWL1 GLOB X C 20.000000 1.000000 0.000000 \
# TOSIONAL BRACING (WIND)
RC LWL2 GLOB X C 20.000000 1.000000 0.000000 \
# TOSIONAL BRACING (WIND)
RC LWL3 GLOB X C 20.000000 -1.000000 0.000000 \
# TOSIONAL BRACING (WIND)
RC LWL4 GLOB X C 20.000000 -1.000000 0.000000 \
# TOSIONAL BRACING (WIND)
RC EQ GLOB X C 20.000000 0.500000 0.000000 \
# TOSIONAL BRACING (SEISMIC)
####
RC DL MEMB X C 17.000000 -2.000000 0.000000 NA \
# BI-FOLD DOOR SELF WT.
####
RC EQDW GLOB M C 20.000000 0.600000 0.000000 \
# PANEL/GIRT SELF-WEIGHT FOR EQ
LC EQDW GLOB M C 20.000000 0.600000 0.000000 \
# PANEL/GIRT SELF-WEIGHT FOR EQ
LC RBUPLW GLOB Y C 0.010000 4.944000 0.916700 \
# WIND BRACE FORCE
LC RBUPLW GLOB L C 0.010000 4.944000 0.000000 \
# WIND BRACE FORCE
LC RBDWLW GLOB Y C 20.000000 -4.944000 0.916700 \
# WIND BRACE FORCE
LC RBUPEQ GLOB Y C 0.010000 5.176000 0.916700 \
# SEISMIC BRACE FORCE
LC RBUPEQ GLOB L C 0.010000 5.176000 0.000000 \
# SEISMIC BRACE FORCE
LC RBDWEQ GLOB Y C 20.000000 -5.176000 0.916700 \
# SEISMIC BRACE FORCE
RC DL GLOB Y C 18.928699 -0.337100 0.000000 \
# RC LEANTO VERT. DL
RC DL GLOB X C 18.928699 0.015200 0.000000 \
# RC LEANTO HORZ. DL
RC COLL GLOB Y C 18.928699 -0.103900 0.000000 \
# RC LEANTO VERT. COLL
RC COLL GLOB X C 18.928699 -0.002200 0.000000 \
# RC LEANTO HORZ. COLL
RC PLLR1 GLOB Y C 18.928699 -1.991400 0.000000 \
# RC LEANTO VERT. PLLR1
RC PLLR1 GLOB X C 18.928699 -0.052100 0.000000 \
# RC LEANTO HORZ. PLLR1
RC LL GLOB Y C 18.928699 -2.031100 0.000000 \
# RC LEANTO VERT. LL
RC LL GLOB X C 18.928699 0.067000 0.000000 \
# RC LEANTO HORZ. LL
RC EQ GLOB Y C 18.928699 0.104000 0.000000 \
# RC LEANTO VERT. EQ
RC EQ GLOB X C 18.928699 0.312100 0.000000 \
# RC LEANTO HORZ. EQ
RC WL1 GLOB Y C 18.928699 0.722900 0.000000 \
# RC LEANTO VERT. WL1
RC WL1 GLOB X C 18.928699 5.071500 0.000000 \
# RC LEANTO HORZ. WL1
RC WL2 GLOB Y C 18.928699 -0.022900 0.000000 \
# RC LEANTO VERT. WL2
RC WL2 GLOB X C 18.928699 -0.499100 0.000000 \
# RC LEANTO HORZ. WL2
RC LWL1 GLOB Y C 18.928699 0.513500 0.000000 \
# RC LEANTO VERT. LWL1
RC LWL1 GLOB X C 18.928699 4.989900 0.000000 \
# RC LEANTO HORZ. LWL1
RC LWL2 GLOB Y C 18.928699 1.074400 0.000000 \
# RC LEANTO VERT. LWL2
RC LWL2 GLOB X C 18.928699 5.578500 0.000000 \
# RC LEANTO HORZ. LWL2
RC LWL3 GLOB Y C 18.928699 -0.173200 0.000000 \
# RC LEANTO VERT. LWL3
RC LWL3 GLOB X C 18.928699 -0.758000 0.000000 \
# RC LEANTO HORZ. LWL3
RC LWL4 GLOB Y C 18.928699 0.387700 0.000000 \
# RC LEANTO VERT. LWL4
RC LWL4 GLOB X C 18.928699 -0.169400 0.000000 \
# RC LEANTO HORZ. LWL4
RC WL3 GLOB Y C 18.928699 2.131600 0.000000 \
# RC LEANTO VERT. WL3
RC WL3 GLOB X C 18.928699 2.406800 0.000000 \
# RC LEANTO HORZ. WL3
RC WL4 GLOB Y C 18.928699 1.385800 0.000000 \
# RC LEANTO VERT. WL4
RC WL4 GLOB X C 18.928699 -3.163700 0.000000 \
# RC LEANTO HORZ. WL4
RC MWL1 GLOB Y C 18.928699 -0.580600 0.000000 \
# RC LEANTO VERT. MWL1
RC MWL1 GLOB X C 18.928699 2.020700 0.000000 \
# RC LEANTO HORZ. MWL1
RC MWL2 GLOB Y C 18.928699 0.480800 0.000000 \
# RC LEANTO VERT. MWL2
RC MWL2 GLOB X C 18.928699 -1.721300 0.000000 \
# RC LEANTO HORZ. MWL2
RC WL1D GLOB Y C 18.928699 0.325500 0.000000 \
# RC LEANTO VERT. WL1D
RC WL1D GLOB X C 18.928699 2.284600 0.000000 \
# RC LEANTO HORZ. WL1D
RC WL2D GLOB Y C 18.928699 -0.010400 0.000000 \
# RC LEANTO VERT. WL2D
RC WL2D GLOB X C 18.928699 -0.224600 0.000000 \
# RC LEANTO HORZ. WL2D
RC LWL1D GLOB Y C 18.928699 0.231300 0.000000 \
# RC LEANTO VERT. LWL1D
RC LWL1D GLOB X C 18.928699 2.247500 0.000000 \
# RC LEANTO HORZ. LWL1D
RC LWL2D GLOB Y C 18.928699 0.483900 0.000000 \
# RC LEANTO VERT. LWL2D
RC LWL2D GLOB X C 18.928699 2.512900 0.000000 \
# RC LEANTO HORZ. LWL2D
RC LWL3D GLOB Y C 18.928699 -0.078100 0.000000 \
# RC LEANTO VERT. LWL3D
RC LWL3D GLOB X C 18.928699 -0.341200 0.000000 \
# RC LEANTO HORZ. LWL3D
RC LWL4D GLOB Y C 18.928699 0.174800 0.000000 \
# RC LEANTO VERT. LWL4D
RC LWL4D GLOB X C 18.928699 -0.076800 0.000000 \
# RC LEANTO HORZ. LWL4D
RC WL3D GLOB Y C 18.928699 0.960300 0.000000 \
# RC LEANTO VERT. WL3D
RC WL3D GLOB X C 18.928699 1.083700 0.000000 \
# RC LEANTO HORZ. WL3D
RC WL4D GLOB Y C 18.928699 0.624400 0.000000 \
# RC LEANTO VERT. WL4D
RC WL4D GLOB X C 18.928699 -1.425400 0.000000 \
# RC LEANTO HORZ. WL4D
RC DL GLOB Y L 18.928699 -0.925500 0.000000 \
# RC LEANTO (SOA) DL
RC COLL GLOB Y L 18.928699 -0.136100 0.000000 \
# RC LEANTO (SOA) COLL
RC PLLR1 GLOB Y L 18.928699 -2.453400 0.000000 \
# RC LEANTO (SOA) PLLR1
RC LL GLOB Y L 18.928699 -3.369900 0.000000 \
# RC LEANTO (SOA) LL
RC EQ GLOB Y L 18.928699 -0.104000 0.000000 \
# RC LEANTO (SOA) EQ
RC WL1 GLOB Y L 18.928699 4.638600 0.000000 \
# RC LEANTO (SOA) WL1
RC WL2 GLOB Y L 18.928699 0.011100 0.000000 \
# RC LEANTO (SOA) WL2
RC LWL1 GLOB Y L 18.928699 4.279500 0.000000 \
# RC LEANTO (SOA) LWL1
RC LWL2 GLOB Y L 18.928699 5.539700 0.000000 \
# RC LEANTO (SOA) LWL2
RC LWL3 GLOB Y L 18.928699 -1.295000 0.000000 \
# RC LEANTO (SOA) LWL3
RC LWL4 GLOB Y L 18.928699 -0.034800 0.000000 \
# RC LEANTO (SOA) LWL4
RC WL3 GLOB Y L 18.928699 5.047500 0.000000 \
# RC LEANTO (SOA) WL3
RC WL4 GLOB Y L 18.928699 0.420100 0.000000 \
# RC LEANTO (SOA) WL4
RC MWL1 GLOB Y L 18.928699 0.959600 0.000000 \
# RC LEANTO (SOA) MWL1
RC MWL2 GLOB Y L 18.928699 0.641200 0.000000 \
# RC LEANTO (SOA) MWL2
RC WL1D GLOB Y L 18.928699 2.089700 0.000000 \
# RC LEANTO (SOA) WL1D
RC WL2D GLOB Y L 18.928699 0.005400 0.000000 \
# RC LEANTO (SOA) WL2D
RC LWL1D GLOB Y L 18.928699 1.927900 0.000000 \
# RC LEANTO (SOA) LWL1D
RC LWL2D GLOB Y L 18.928699 2.495400 0.000000 \
# RC LEANTO (SOA) LWL2D
RC LWL3D GLOB Y L 18.928699 -0.582900 0.000000 \
# RC LEANTO (SOA) LWL3D
RC LWL4D GLOB Y L 18.928699 -0.015800 0.000000 \
# RC LEANTO (SOA) LWL4D
RC WL3D GLOB Y L 18.928699 2.273000 0.000000 \
# RC LEANTO (SOA) WL3D
RC WL4D GLOB Y L 18.928699 0.188700 0.000000 \
# RC LEANTO (SOA) WL4D
##########Nested P.F. Load#########
RC RBUPLW GLOB Y C 0.833300 3.380000 -1.080000 \
#NESTED PORTAL WIND LOAD
RC RBUPLW GLOB Y C 18.666700 3.380000 -1.080000 \
#NESTED PORTAL WIND LOAD
RC RBUPLW GLOB L C 0.010000 3.500000 0.000000 \
#NESTED PORTAL WIND LOAD
RC RBDWLW GLOB Y C 18.666700 -3.380000 -1.080000 \
#NESTED PORTAL WIND LOAD
RC RBDWLW GLOB Y C 0.833300 -3.380000 -1.080000 \
#NESTED PORTAL WIND LOAD
RC RBDWLW GLOB L C 0.010000 -3.500000 0.000000 \
#NESTED PORTAL WIND LOAD
RC RBUPEQ GLOB Y C 0.833300 3.290000 -1.080000 \
#NESTED PORTAL EQ LOAD
RC RBUPEQ GLOB Y C 18.666700 3.290000 -1.080000 \
#NESTED PORTAL EQ LOAD
RC RBUPEQ GLOB L C 0.010000 3.400000 0.000000 \
#NESTED PORTAL EQ LOAD
RC RBDWEQ GLOB Y C 18.666700 -3.290000 -1.080000 \
#NESTED PORTAL EQ LOAD
RC RBDWEQ GLOB Y C 0.833300 -3.290000 -1.080000 \
#NESTED PORTAL EQ LOAD
RC RBDWEQ GLOB L C 0.010000 -3.400000 0.000000 \
#NESTED PORTAL EQ LOAD
RC DL GLOB Y C 18.666700 -1.000000 -1.080000 \
#NESTED PORTAL DEAD LOAD
END
Metallic Building Systems User: mmfarahani Page: F3- 2
R-Frame Design Program - Version V8.15 Job : 31650A
Building Grid label legend File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Building Grid Label Legend
==========================
Building : A
Frame Number : 3
No. of Frames : 2
Left Column : Column @ * - E
Right Column : Column @ * - B
*Frames located @ 2 3
Metallic Building Systems User: mmfarahani Page: F3- 3
R-Frame Design Program - Version V8.15 Job : 31650A
Code Summary Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Building :A
Frame Number :3 Location: frame lines 2 3
No. of Frames: 2
2019 CALIFORNIA BUILDING CODE
Main Code Requirements Per :
International Building Code
2018 Edition
Supporting Design Manual(s):
2016 AISC Specification for Structural Steel Buildings,Allowable Strength Design
2010 AISC Seismic Provisions for Structural Steel Buildings
Frame Data
----------
Eave height Left & Right (feet)..................................... 20.000
Horizontal width from left to right steel line (feet)............... 50.000
Horizontal distance to ridge from left side (feet).................. 25.000
Roof Slope Left & Right (rise:12)................................... 4.000
Column Slope Left & Right (lat:12).................................. 0.000
Purlin depth left & right side (inches)............................. 8.000
Frame Rafter Inset left & right side (inches)....................... 8.250
Girt depth left & right side (inches)............................... 8.000
Frame Column Inset left & right side (inches)....................... 8.250
Tributary Width left side (feet).................................... 20.833
..................................from Height 0.00 to Height 20.00
Tributary Width right side (feet)................................... 0.000
..................................from Height 0.00 to Height 20.00
Tributary Width roof (feet)......................................... 20.833
Tension Flange Bolt Hole Reduction.................................. Yes
Tension Field Action at Knee........................................ Yes
Second order analysis method........................................ C2.2b
Frame Design Loads
------------------
Dead Load to Frame Rafter (psf)..................................... 2.623
Frame Rafter Dead Weight (psf)...................................... 0.855
Total Roof Dead Weight (psf)........................................ 3.478
Collateral Load to Frame Rafter (psf)............................... 5.000
Roof Live Load Entered (psf) W/ Live Load Reduction Requested....... 20.000
Design Roof Live Load Used (psf).................................... 12.000
Roof Snow Load Entered (psf)........................................ 0.000
Snow Exposure Factor Entered [Ce] .................................. 0.900
Snow Importance Factor [I] -- Standard Use Category................. 1.000
Snow Thermal Factor Entered [Ct] -- User Entered.................... 1.200
Snow Thermal Factor Used [Ct]Unheated Building...................... 1.200
Slippery & Unobstructed Roof Surface................................ No
Roof Snow Load [Pf = 0.7*Ce*Ct*I*Pg] (psf).......................... 0.000
Snow Slope Factor [Cs].............................................. 1.000
Sloped Roof Snow Load Used [Ps = Cs*Pf] (psf)....................... 0.000
PATTERN LIVE LOADING(s)
-----------------------
1) Any two adjacent spans loaded with 100% of the roof load & all the
remaining spans loaded with 0% (min. of 3 spans).
100% 100% 0%
================
^ ^ ^ ^
2) Alternate spans loaded with 100% of the roof load & all the remaining
spans loaded with 0% (min. of 2 spans).
100% 0% 100% 0% 100%
==========================
^ ^ ^ ^ ^ ^
Metallic Building Systems User: mmfarahani Page: F3- 4
R-Frame Design Program - Version V8.15 Job : 31650A
Wind Summary Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
Eave height Left & Right (feet)..................................... 20.000
Wind Elevation on left column (feet)................................ 20.000
Wind Elevation on right column (feet)............................... 16.000
Total frame width (feet)............................................ 50.000
Total building length (feet)........................................ 60.000
Number of primary wind loadings .................................... 18
Metallic Building Systems User: mmfarahani Page: F3- 5
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Wind Summary Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
*** PRIMARY WIND COEFFICIENTS FOR MAIN FRAME ***
--------------------------------------------------------------------------------
Wind Load WL1 Wind from left direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.340 -0.870( 50.0%) -0.650( 50.0%) -0.600
--------------------------------------------------------------------------------
Wind Load WL2 Wind from left direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.700 -0.510( 50.0%) -0.290( 50.0%) -0.240
--------------------------------------------------------------------------------
Wind Load LWL1 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.630 -0.870( 50.0%) -0.550( 50.0%) -0.630
--------------------------------------------------------------------------------
Wind Load LWL2 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.630 -0.550( 62.0%) -0.870( 38.0%) -0.630
--------------------------------------------------------------------------------
Wind Load LWL3 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.270 -0.510( 50.0%) -0.190( 50.0%) -0.270
--------------------------------------------------------------------------------
Wind Load LWL4 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.270 -0.190( 62.0%) -0.510( 38.0%) -0.270
--------------------------------------------------------------------------------
Wind Load MWL1 Min. Wind from left dir.
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.500 0.250 0.250 -0.500
--------------------------------------------------------------------------------
Wind Load MWL2 Min. Wind from right dir.
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.500 -0.250 -0.250 0.500
--------------------------------------------------------------------------------
Wind Load WL3 Wind from right direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.600 -0.650( 62.0%) -0.870( 38.0%) 0.340
--------------------------------------------------------------------------------
Wind Load WL4 Wind from right direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.240 -0.290( 62.0%) -0.510( 38.0%) 0.700
--------------------------------------------------------------------------------
Notes :
1. Wind coefficients applied to the roof may be located as a percentage
of the total frame width (xx.x%). If not shown the coefficients are
applied fully to their respective rafter.
Metallic Building Systems User: mmfarahani Page: F3- 6
R-Frame Design Program - Version V8.15 Job : 31650A
Load Combinations Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Load Combination :
------------------
1) DL +COLL +PLLL1 +PLL1 (SOA-L) N A P
2) DL +COLL +PLLL1 +PLL1 (SOA-R) N A P
3) DL +COLL +PLL1 +PLLR1 (SOA-L) N A P
4) DL +COLL +PLL1 +PLLR1 (SOA-R) N A P
5) DL +COLL +PLLL1 +PLLR1 (SOA-L) N A P
6) DL +COLL +PLLL1 +PLLR1 (SOA-R) N A P
7) DL +COLL +PLL1 (SOA-L) N A P
8) DL +COLL +PLL1 (SOA-R) N A P
9) DL +LL +COLL (SOA-L) N A P
10) DL +LL +COLL (SOA-R) N A P
11) 1.1325DL +1.1325COLL +0.91RBDWEQ (SOA-L) N A P
12) 1.1325DL +1.1325COLL +0.91RBDWEQ (SOA-R) N A P
13) 1.1325DL +1.05EQ (SOA-L) N A P
14) 1.1325DL +1.05EQ (SOA-R) N A P
15) 1.1325DL -1.05EQ (SOA-L) N A P
16) 1.1325DL -1.05EQ (SOA-R) N A P
17) 1.1325DL +1.1325COLL +1.05EQ (SOA-L) N A P
18) 1.1325DL +1.1325COLL +1.05EQ (SOA-R) N A P
19) 1.1325DL +1.1325COLL -1.05EQ (SOA-L) N A P
20) 1.1325DL +1.1325COLL -1.05EQ (SOA-R) N A P
21) 0.4675DL +0.91RBUPEQ (SOA-L) N A P
22) 0.4675DL +0.91RBUPEQ (SOA-R) N A P
23) 0.4675DL +1.05EQ (SOA-L) N A P
24) 0.4675DL +1.05EQ (SOA-R) N A P
25) 0.4675DL -1.05EQ (SOA-L) N A P
26) 0.4675DL -1.05EQ (SOA-R) N A P
27) 0.7107DL +2.RBUPEQ (SOA-L) N C R P
28) 0.7107DL +2.RBUPEQ (SOA-R) N C R P
29) 1.3893DL +1.3893COLL +2.RBDWEQ (SOA-L) N C R P
30) 1.3893DL +1.3893COLL +2.RBDWEQ (SOA-R) N C R P
31) 0.7107DL +2.5EQ (SOA-L) N C R P
32) 0.7107DL +2.5EQ (SOA-R) N C R P
33) 0.7107DL -2.5EQ (SOA-L) N C R P
34) 0.7107DL -2.5EQ (SOA-R) N C R P
35) 1.3893DL +1.3893COLL +2.5EQ (SOA-L) N C R P
36) 1.3893DL +1.3893COLL +2.5EQ (SOA-R) N C R P
37) 1.3893DL +1.3893COLL -2.5EQ (SOA-L) N C R P
38) 1.3893DL +1.3893COLL -2.5EQ (SOA-R) N C R P
39) 0.7107DL +2.RBUPEQ (SOA-L) N B R P
40) 0.7107DL +2.RBUPEQ (SOA-R) N B R P
41) 1.3893DL +1.3893COLL +2.RBDWEQ (SOA-L) N B R P
42) 1.3893DL +1.3893COLL +2.RBDWEQ (SOA-R) N B R P
43) 0.7107DL +2.5EQ (SOA-L) N B R P
44) 0.7107DL +2.5EQ (SOA-R) N B R P
45) 0.7107DL -2.5EQ (SOA-L) N B R P
46) 0.7107DL -2.5EQ (SOA-R) N B R P
47) 1.3893DL +1.3893COLL +2.5EQ (SOA-L) N B R P
48) 1.3893DL +1.3893COLL +2.5EQ (SOA-R) N B R P
49) 1.3893DL +1.3893COLL -2.5EQ (SOA-L) N B R P
50) 1.3893DL +1.3893COLL -2.5EQ (SOA-R) N B R P
Metallic Building Systems User: mmfarahani Page: F3- 7
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Load Combination :
------------------
51) 0.7107DL +3.5EQ (SOA-L) N K R P
52) 0.7107DL +3.5EQ (SOA-R) N K R P
53) 0.7107DL -3.5EQ (SOA-L) N K R P
54) 0.7107DL -3.5EQ (SOA-R) N K R P
55) 1.3893DL +1.3893COLL +3.5EQ (SOA-L) N K R P
56) 1.3893DL +1.3893COLL +3.5EQ (SOA-R) N K R P
57) 1.3893DL +1.3893COLL -3.5EQ (SOA-L) N K R P
58) 1.3893DL +1.3893COLL -3.5EQ (SOA-R) N K R P
59) DL +0.6WL1 (SOA-L) N A P
60) DL +0.6WL1 (SOA-R) N A P
61) DL +0.6WL2 (SOA-L) N A P
62) DL +0.6WL2 (SOA-R) N A P
63) DL +0.6WL3 (SOA-L) N A P
64) DL +0.6WL3 (SOA-R) N A P
65) DL +0.6WL4 (SOA-L) N A P
66) DL +0.6WL4 (SOA-R) N A P
67) 0.6DL +0.6WL1 (SOA-L) N A P
68) 0.6DL +0.6WL1 (SOA-R) N A P
69) 0.6DL +0.6WL2 (SOA-L) N A P
70) 0.6DL +0.6WL2 (SOA-R) N A P
71) 0.6DL +0.6LWL1 +0.6RBUPLW (SOA-L) N A P
72) 0.6DL +0.6LWL1 +0.6RBUPLW (SOA-R) N A P
73) 0.6DL +0.6LWL2 +0.6RBUPLW (SOA-L) N A P
74) 0.6DL +0.6LWL2 +0.6RBUPLW (SOA-R) N A P
75) 0.6DL +0.6LWL3 +0.6RBUPLW (SOA-L) N A P
76) 0.6DL +0.6LWL3 +0.6RBUPLW (SOA-R) N A P
77) 0.6DL +0.6LWL4 +0.6RBUPLW (SOA-L) N A P
78) 0.6DL +0.6LWL4 +0.6RBUPLW (SOA-R) N A P
79) 0.6DL +0.6WL3 (SOA-L) N A P
80) 0.6DL +0.6WL3 (SOA-R) N A P
81) 0.6DL +0.6WL4 (SOA-L) N A P
82) 0.6DL +0.6WL4 (SOA-R) N A P
83) 0.6MWL1 N M
84) 0.6MWL2 N M
85) DL +COLL +0.6WL1 (SOA-L) N A P
86) DL +COLL +0.6WL1 (SOA-R) N A P
87) DL +COLL +0.6WL2 (SOA-L) N A P
88) DL +COLL +0.6WL2 (SOA-R) N A P
89) DL +COLL +0.6WL3 (SOA-L) N A P
90) DL +COLL +0.6WL3 (SOA-R) N A P
91) DL +COLL +0.6WL4 (SOA-L) N A P
92) DL +COLL +0.6WL4 (SOA-R) N A P
93) DL +0.75LL +COLL +0.45WL1 (SOA-L) N A P
94) DL +0.75LL +COLL +0.45WL1 (SOA-R) N A P
95) DL +0.75LL +COLL +0.45WL2 (SOA-L) N A P
96) DL +0.75LL +COLL +0.45WL2 (SOA-R) N A P
97) DL +0.75LL +COLL +0.45LWL1 +0.45RBUPLW (SOA-L) N A P
98) DL +0.75LL +COLL +0.45LWL1 +0.45RBUPLW (SOA-R) N A P
99) DL +0.75LL +COLL +0.45LWL2 +0.45RBUPLW (SOA-L) N A P
100) DL +0.75LL +COLL +0.45LWL2 +0.45RBUPLW (SOA-R) N A P
Metallic Building Systems User: mmfarahani Page: F3- 8
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Load Combination :
------------------
101) DL +0.75LL +COLL +0.45LWL3 +0.45RBUPLW (SOA-L) N A P
102) DL +0.75LL +COLL +0.45LWL3 +0.45RBUPLW (SOA-R) N A P
103) DL +0.75LL +COLL +0.45LWL4 +0.45RBUPLW (SOA-L) N A P
104) DL +0.75LL +COLL +0.45LWL4 +0.45RBUPLW (SOA-R) N A P
105) DL +0.75LL +COLL +0.45WL3 (SOA-L) N A P
106) DL +0.75LL +COLL +0.45WL3 (SOA-R) N A P
107) DL +0.75LL +COLL +0.45WL4 (SOA-L) N A P
108) DL +0.75LL +COLL +0.45WL4 (SOA-R) N A P
109) DL +COLL +0.6LWL1 +0.6RBDWLW (SOA-L) N A P
110) DL +COLL +0.6LWL1 +0.6RBDWLW (SOA-R) N A P
111) DL +COLL +0.6LWL2 +0.6RBDWLW (SOA-L) N A P
112) DL +COLL +0.6LWL2 +0.6RBDWLW (SOA-R) N A P
113) DL +COLL +0.6LWL3 +0.6RBDWLW (SOA-L) N A P
114) DL +COLL +0.6LWL3 +0.6RBDWLW (SOA-R) N A P
115) DL +COLL +0.6LWL4 +0.6RBDWLW (SOA-L) N A P
116) DL +COLL +0.6LWL4 +0.6RBDWLW (SOA-R) N A P
117) DL +0.75LL +COLL +0.45LWL1 +0.45RBDWLW (SOA-L) N A P
118) DL +0.75LL +COLL +0.45LWL1 +0.45RBDWLW (SOA-R) N A P
119) DL +0.75LL +COLL +0.45LWL2 +0.45RBDWLW (SOA-L) N A P
120) DL +0.75LL +COLL +0.45LWL2 +0.45RBDWLW (SOA-R) N A P
121) DL +0.75LL +COLL +0.45LWL3 +0.45RBDWLW (SOA-L) N A P
122) DL +0.75LL +COLL +0.45LWL3 +0.45RBDWLW (SOA-R) N A P
123) DL +0.75LL +COLL +0.45LWL4 +0.45RBDWLW (SOA-L) N A P
124) DL +0.75LL +COLL +0.45LWL4 +0.45RBDWLW (SOA-R) N A P
125) LL D
126) WL1D D
127) WL2D D
128) LWL1D D
129) LWL2D D
130) LWL3D D
131) LWL4D D
132) WL3D D
133) WL4D D
134) 1.3893DL +EQ D E
135) 1.3893DL -EQ D E
136) 0.7107DL +EQ D E
137) 0.7107DL -EQ D E
138) 1.3893DL +1.3893COLL +EQ D E
139) 1.3893DL +1.3893COLL -EQ D E
Metallic Building Systems User: mmfarahani Page: F3- 9
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Where :
-------
DL = Roof Dead Load
COLL = Roof Collateral Load
PLLL1 = Pattern Live Load Left Leanto/Canopy [PLLLxx]
PLL1 = Pattern Live Load [PLLxx]
PLLR1 = Pattern Live Load Right Leanto/Canopy [PLLRxx]
LL = Roof Live Load
RBDWEQ= Downward Acting Rod Brace Load from Long. Seismic
EQ = Lateral Seismic Load [parallel to plane of frame]
RBUPEQ= Upward Acting Rod Brace Load from Long. Seismic
WL1 = Wind from Left to Right with +GCpi
WL2 = Wind from Left to Right with -GCpi
WL3 = Wind from Right to Left with +GCpi
WL4 = Wind from Right to Left with -GCpi
LWL1 = Windward Corner Left with +GCpi
RBUPLW= Upward Acting Rod Brace Load from Long. Wind
LWL2 = Windward Corner Right with +GCpi
LWL3 = Windward Corner Left with -GCpi
LWL4 = Windward Corner Right with -GCpi
MWL1 = Minimum Wind Load
MWL2 = Minimum Wind Load
RBDWLW= Downward Acting Rod Brace Load from Long. Wind
WL1D = Wind from Left to Right with +GCpi at Service Level
WL2D = Wind from Left to Right with -GCpi at Service Level
LWL1D = Windward Corner Left with +GCpi at Service Level
LWL2D = Windward Corner Right with +GCpi at Service Level
LWL3D = Windward Corner Left with -GCpi at Service Level
LWL4D = Windward Corner Right with -GCpi at Service Level
WL3D = Wind from Right to Left with +GCpi at Service Level
WL4D = Wind from Right to Left with -GCpi at Service Level
Combination Descriptions :
--------------------------
N= No 1/3 Increase in Allowable for Combination
B= Base Only Combination
K= Knee Connection Only Combination
A= Allowable Strength Design Combination - ASD16
C= Column Only Combination for Seismic
D= Deflection Only Combination
P= Second Order Analysis Combination - SOA
R= Load and Resistance Factor Design Combination - LRFD
E= Cd is applied and Ie is omitted from frame drift calculations
M= Minimum Wind Load Combination. Checked for Allowable Strength not for Deflection
Metallic Building Systems User: mmfarahani Page: F3- 10
R-Frame Design Program - Version V8.15 Job : 31650A
User Load Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
* USER INPUT LOADS
-------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
1 RC LWL1 GLOB X C 20.000 1.0000 0.0000 0.000
2 RC LWL2 GLOB X C 20.000 1.0000 0.0000 0.000
3 RC LWL3 GLOB X C 20.000 -1.0000 0.0000 0.000
4 RC LWL4 GLOB X C 20.000 -1.0000 0.0000 0.000
5 RC EQ GLOB X C 20.000 0.5000 0.0000 0.000
6 RC DL MEMB X C 17.000 -2.0000 0.0000 0.000
7 RC EQDW GLOB M C 20.000 0.6000 0.0000 0.000
8 LC EQDW GLOB M C 20.000 0.6000 0.0000 0.000
9 LC RBUPLW GLOB Y C 0.010 4.9440 0.0000 0.917
10 LC RBUPLW GLOB L C 0.010 4.9440 0.0000 0.000
11 LC RBDWLW GLOB Y C 20.000 -4.9440 0.0000 0.917
12 LC RBUPEQ GLOB Y C 0.010 5.1760 0.0000 0.917
13 LC RBUPEQ GLOB L C 0.010 5.1760 0.0000 0.000
14 LC RBDWEQ GLOB Y C 20.000 -5.1760 0.0000 0.917
15 RC DL GLOB Y C 18.929 -0.3371 0.0000 0.000
16 RC DL GLOB X C 18.929 0.0152 0.0000 0.000
17 RC COLL GLOB Y C 18.929 -0.1039 0.0000 0.000
18 RC COLL GLOB X C 18.929 -0.0022 0.0000 0.000
19 RC PLLR1 GLOB Y C 18.929 -1.9914 0.0000 0.000
20 RC PLLR1 GLOB X C 18.929 -0.0521 0.0000 0.000
21 RC LL GLOB Y C 18.929 -2.0311 0.0000 0.000
22 RC LL GLOB X C 18.929 0.0670 0.0000 0.000
23 RC EQ GLOB Y C 18.929 0.1040 0.0000 0.000
24 RC EQ GLOB X C 18.929 0.3121 0.0000 0.000
25 RC WL1 GLOB Y C 18.929 0.7229 0.0000 0.000
26 RC WL1 GLOB X C 18.929 5.0715 0.0000 0.000
27 RC WL2 GLOB Y C 18.929 -0.0229 0.0000 0.000
28 RC WL2 GLOB X C 18.929 -0.4991 0.0000 0.000
29 RC LWL1 GLOB Y C 18.929 0.5135 0.0000 0.000
30 RC LWL1 GLOB X C 18.929 4.9899 0.0000 0.000
31 RC LWL2 GLOB Y C 18.929 1.0744 0.0000 0.000
32 RC LWL2 GLOB X C 18.929 5.5785 0.0000 0.000
33 RC LWL3 GLOB Y C 18.929 -0.1732 0.0000 0.000
34 RC LWL3 GLOB X C 18.929 -0.7580 0.0000 0.000
35 RC LWL4 GLOB Y C 18.929 0.3877 0.0000 0.000
36 RC LWL4 GLOB X C 18.929 -0.1694 0.0000 0.000
37 RC WL3 GLOB Y C 18.929 2.1316 0.0000 0.000
38 RC WL3 GLOB X C 18.929 2.4068 0.0000 0.000
39 RC WL4 GLOB Y C 18.929 1.3858 0.0000 0.000
40 RC WL4 GLOB X C 18.929 -3.1637 0.0000 0.000
41 RC MWL1 GLOB Y C 18.929 -0.5806 0.0000 0.000
42 RC MWL1 GLOB X C 18.929 2.0207 0.0000 0.000
43 RC MWL2 GLOB Y C 18.929 0.4808 0.0000 0.000
44 RC MWL2 GLOB X C 18.929 -1.7213 0.0000 0.000
45 RC WL1D GLOB Y C 18.929 0.3255 0.0000 0.000
46 RC WL1D GLOB X C 18.929 2.2846 0.0000 0.000
47 RC WL2D GLOB Y C 18.929 -0.0104 0.0000 0.000
48 RC WL2D GLOB X C 18.929 -0.2246 0.0000 0.000
49 RC LWL1D GLOB Y C 18.929 0.2313 0.0000 0.000
50 RC LWL1D GLOB X C 18.929 2.2475 0.0000 0.000
51 RC LWL2D GLOB Y C 18.929 0.4839 0.0000 0.000
52 RC LWL2D GLOB X C 18.929 2.5129 0.0000 0.000
53 RC LWL3D GLOB Y C 18.929 -0.0781 0.0000 0.000
54 RC LWL3D GLOB X C 18.929 -0.3412 0.0000 0.000
55 RC LWL4D GLOB Y C 18.929 0.1748 0.0000 0.000
56 RC LWL4D GLOB X C 18.929 -0.0768 0.0000 0.000
57 RC WL3D GLOB Y C 18.929 0.9603 0.0000 0.000
58 RC WL3D GLOB X C 18.929 1.0837 0.0000 0.000
59 RC WL4D GLOB Y C 18.929 0.6244 0.0000 0.000
60 RC WL4D GLOB X C 18.929 -1.4254 0.0000 0.000
61 RC DL GLOB Y L 18.929 -0.9255 0.0000 0.000
62 RC COLL GLOB Y L 18.929 -0.1361 0.0000 0.000
63 RC PLLR1 GLOB Y L 18.929 -2.4534 0.0000 0.000
64 RC LL GLOB Y L 18.929 -3.3699 0.0000 0.000
65 RC EQ GLOB Y L 18.929 -0.1040 0.0000 0.000
66 RC WL1 GLOB Y L 18.929 4.6386 0.0000 0.000
67 RC WL2 GLOB Y L 18.929 0.0111 0.0000 0.000
68 RC LWL1 GLOB Y L 18.929 4.2795 0.0000 0.000
69 RC LWL2 GLOB Y L 18.929 5.5397 0.0000 0.000
70 RC LWL3 GLOB Y L 18.929 -1.2950 0.0000 0.000
71 RC LWL4 GLOB Y L 18.929 -0.0348 0.0000 0.000
72 RC WL3 GLOB Y L 18.929 5.0475 0.0000 0.000
73 RC WL4 GLOB Y L 18.929 0.4201 0.0000 0.000
74 RC MWL1 GLOB Y L 18.929 0.9596 0.0000 0.000
75 RC MWL2 GLOB Y L 18.929 0.6412 0.0000 0.000
76 RC WL1D GLOB Y L 18.929 2.0897 0.0000 0.000
77 RC WL2D GLOB Y L 18.929 0.0054 0.0000 0.000
78 RC LWL1D GLOB Y L 18.929 1.9279 0.0000 0.000
79 RC LWL2D GLOB Y L 18.929 2.4954 0.0000 0.000
80 RC LWL3D GLOB Y L 18.929 -0.5829 0.0000 0.000
81 RC LWL4D GLOB Y L 18.929 -0.0158 0.0000 0.000
82 RC WL3D GLOB Y L 18.929 2.2730 0.0000 0.000
83 RC WL4D GLOB Y L 18.929 0.1887 0.0000 0.000
84 RC RBUPLW GLOB Y C 0.833 3.3800 0.0000 -1.080
85 RC RBUPLW GLOB Y C 18.667 3.3800 0.0000 -1.080
86 RC RBUPLW GLOB L C 0.010 3.5000 0.0000 0.000
87 RC RBDWLW GLOB Y C 18.667 -3.3800 0.0000 -1.080
88 RC RBDWLW GLOB Y C 0.833 -3.3800 0.0000 -1.080
89 RC RBDWLW GLOB L C 0.010 -3.5000 0.0000 0.000
90 RC RBUPEQ GLOB Y C 0.833 3.2900 0.0000 -1.080
91 RC RBUPEQ GLOB Y C 18.667 3.2900 0.0000 -1.080
92 RC RBUPEQ GLOB L C 0.010 3.4000 0.0000 0.000
93 RC RBDWEQ GLOB Y C 18.667 -3.2900 0.0000 -1.080
94 RC RBDWEQ GLOB Y C 0.833 -3.2900 0.0000 -1.080
95 RC RBDWEQ GLOB L C 0.010 -3.4000 0.0000 0.000
96 RC DL GLOB Y C 18.667 -1.0000 0.0000 -1.080
Metallic Building Systems User: mmfarahani Page: F3- 11
R-Frame Design Program - Version V8.15 Job : 31650A
Canopy Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Left Side Canopy Data
---------------------
Canopy #1 : At Eave Canopy w/ Flush purlin
Width (horizontal projection from steel line) (feet)...... 2.0000
Length (used for drifting snow only) (feet)............... 64.0000
Canopy bay size (feet).................................... 19.8330
Roof height at the wall(feet)............................. 20.0000
Roof height at the free end (feet)........................ 19.3333
Roof slope (rise:12)...................................... 4.0000
Purlin depth (inches) .................................... 8.0000
Minimum cap plate width (inches) ......................... 5.0000
Minimum cap plate thickness (inches)...................... 0.3750
Canopy beam flange thickness (inches)..................... 0.2050
Canopy beam vertical web height at the steel line (inches) 7.4800
Connection plate thickness (inches)....................... 0.0000
Canopy Design Loads
-------------------
Snow Thermal Factor [Ct] -- Unheated Canopy 1.2000
Slippery & Unobstructed Canopy Roof Surface No
Canopy Snow Slope Factor [Cs] 1.0000
Total Canopy Dead Load (psf).............................. 4.5080
Canopy Collateral Load (psf).............................. 0.0000
Canopy Live Load Entered (psf)............................ 20.0000
Canopy Live Load Used (psf)............................... 20.0000
Design Snow Load Used (psf)............................... 0.0000
Unbalanced Snow Load Used (psf)........................... 0.0000
Canopy wind elevation (feet).............................. 19.6667
Number of wind arrays .................................... 18
Canopy wind coefficients and design loads
-----------------------------------------
Wind Wind Coeff. Design Load
Array (psf)
WL1 -1.390 -27.99
WL2 -1.390 -27.99
LWL1 -0.690 -13.89
LWL2 -0.370 -7.45
LWL3 -0.330 -6.65
LWL4 -0.010 -0.20
MWL1 -1.390 -27.99
MWL2 -0.470 -9.46
WL3 -0.470 -9.46
WL4 -0.470 -9.46
WL1D -1.390 -12.61
WL2D -1.390 -12.61
LWL1D -0.690 -6.26
LWL2D -0.370 -3.36
LWL3D -0.330 -2.99
LWL4D -0.010 -0.09
WL3D -0.470 -4.26
WL4D -0.470 -4.26
* CANOPY LOADS GENERATED
-------------------------
LOAD MEM NAME SYS DIR TYP DIST. INTENSITY ECCEN. DESCRIPTION
NO.
97 LC DL GLOB Y C 19.50 -0.179 -1.00 CANOPY LOAD
98 LC LL GLOB Y C 19.50 -0.793 -1.00 CANOPY LOAD
99 LC RS GLOB Y C 19.50 0.000 -1.00 CANOPY LOAD
100 LC LS GLOB Y C 19.50 0.000 -1.00 CANOPY LOAD
101 LC WL1 GLOB Y C 19.50 1.110 -1.00 CANOPY LOAD
102 LC WL1 GLOB X C 19.50 -0.370 0.00 CANOPY LOAD
103 LC WL2 GLOB Y C 19.50 1.110 -1.00 CANOPY LOAD
104 LC WL2 GLOB X C 19.50 -0.370 0.00 CANOPY LOAD
105 LC LWL1 GLOB Y C 19.50 0.551 -1.00 CANOPY LOAD
106 LC LWL1 GLOB X C 19.50 -0.184 0.00 CANOPY LOAD
107 LC LWL2 GLOB Y C 19.50 0.296 -1.00 CANOPY LOAD
108 LC LWL2 GLOB X C 19.50 -0.099 0.00 CANOPY LOAD
109 LC LWL3 GLOB Y C 19.50 0.264 -1.00 CANOPY LOAD
110 LC LWL3 GLOB X C 19.50 -0.088 0.00 CANOPY LOAD
111 LC LWL4 GLOB Y C 19.50 0.008 -1.00 CANOPY LOAD
112 LC LWL4 GLOB X C 19.50 -0.003 0.00 CANOPY LOAD
113 LC MWL1 GLOB Y C 19.50 1.110 -1.00 CANOPY LOAD
114 LC MWL1 GLOB X C 19.50 -0.370 0.00 CANOPY LOAD
115 LC MWL2 GLOB Y C 19.50 0.375 -1.00 CANOPY LOAD
Metallic Building Systems User: mmfarahani Page: F3- 12
R-Frame Design Program - Version V8.15 Job : 31650A
Continued Canopy Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
* CANOPY LOADS GENERATED (continued)
-------------------------
LOAD MEM NAME SYS DIR TYP DIST. INTENSITY ECCEN. DESCRIPTION
NO.
116 LC MWL2 GLOB X C 19.50 -0.125 0.00 CANOPY LOAD
117 LC WL3 GLOB Y C 19.50 0.375 -1.00 CANOPY LOAD
118 LC WL3 GLOB X C 19.50 -0.125 0.00 CANOPY LOAD
119 LC WL4 GLOB Y C 19.50 0.375 -1.00 CANOPY LOAD
120 LC WL4 GLOB X C 19.50 -0.125 0.00 CANOPY LOAD
121 LC WL1D GLOB Y C 19.50 0.500 -1.00 CANOPY LOAD
122 LC WL1D GLOB X C 19.50 -0.167 0.00 CANOPY LOAD
123 LC WL2D GLOB Y C 19.50 0.500 -1.00 CANOPY LOAD
124 LC WL2D GLOB X C 19.50 -0.167 0.00 CANOPY LOAD
125 LC LWL1D GLOB Y C 19.50 0.248 -1.00 CANOPY LOAD
126 LC LWL1D GLOB X C 19.50 -0.083 0.00 CANOPY LOAD
127 LC LWL2D GLOB Y C 19.50 0.133 -1.00 CANOPY LOAD
128 LC LWL2D GLOB X C 19.50 -0.044 0.00 CANOPY LOAD
129 LC LWL3D GLOB Y C 19.50 0.119 -1.00 CANOPY LOAD
130 LC LWL3D GLOB X C 19.50 -0.040 0.00 CANOPY LOAD
131 LC LWL4D GLOB Y C 19.50 0.004 -1.00 CANOPY LOAD
132 LC LWL4D GLOB X C 19.50 -0.001 0.00 CANOPY LOAD
133 LC WL3D GLOB Y C 19.50 0.169 -1.00 CANOPY LOAD
134 LC WL3D GLOB X C 19.50 -0.056 0.00 CANOPY LOAD
135 LC WL4D GLOB Y C 19.50 0.169 -1.00 CANOPY LOAD
136 LC WL4D GLOB X C 19.50 -0.056 0.00 CANOPY LOAD
Metallic Building Systems User: mmfarahani Page: F3- 13
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
* GENERAL LOAD CARDS GENERATED -
--------------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
1 RC LWL1 GLOB X C 20.000 1.0000 N/A 0.000
2 RC LWL2 GLOB X C 20.000 1.0000 N/A 0.000
3 RC LWL3 GLOB X C 20.000 -1.0000 N/A 0.000
4 RC LWL4 GLOB X C 20.000 -1.0000 N/A 0.000
5 RC EQ GLOB X C 20.000 0.5000 N/A 0.000
6 RC DL MEMB X C 17.000 -2.0000 N/A 0.000
7 RC EQDW GLOB M C 20.000 0.6000 N/A 0.000
8 LC EQDW GLOB M C 20.000 0.6000 N/A 0.000
9 LC RBUPLW GLOB Y C 0.010 4.9440 N/A 0.917
10 LC RBUPLW GLOB L C 0.010 4.9440 N/A 0.000
11 LC RBDWLW GLOB Y C 20.000 -4.9440 N/A 0.917
12 LC RBUPEQ GLOB Y C 0.010 5.1760 N/A 0.917
13 LC RBUPEQ GLOB L C 0.010 5.1760 N/A 0.000
14 LC RBDWEQ GLOB Y C 20.000 -5.1760 N/A 0.917
15 RC DL GLOB Y C 18.929 -0.3371 N/A 0.000
16 RC DL GLOB X C 18.929 0.0152 N/A 0.000
17 RC COLL GLOB Y C 18.929 -0.1039 N/A 0.000
18 RC COLL GLOB X C 18.929 -0.0022 N/A 0.000
19 RC PLLR1 GLOB Y C 18.929 -1.9914 N/A 0.000
20 RC PLLR1 GLOB X C 18.929 -0.0521 N/A 0.000
21 RC LL GLOB Y C 18.929 -2.0311 N/A 0.000
22 RC LL GLOB X C 18.929 0.0670 N/A 0.000
23 RC EQ GLOB Y C 18.929 0.1040 N/A 0.000
24 RC EQ GLOB X C 18.929 0.3121 N/A 0.000
25 RC WL1 GLOB Y C 18.929 0.7229 N/A 0.000
26 RC WL1 GLOB X C 18.929 5.0715 N/A 0.000
27 RC WL2 GLOB Y C 18.929 -0.0229 N/A 0.000
28 RC WL2 GLOB X C 18.929 -0.4991 N/A 0.000
29 RC LWL1 GLOB Y C 18.929 0.5135 N/A 0.000
30 RC LWL1 GLOB X C 18.929 4.9899 N/A 0.000
31 RC LWL2 GLOB Y C 18.929 1.0744 N/A 0.000
32 RC LWL2 GLOB X C 18.929 5.5785 N/A 0.000
33 RC LWL3 GLOB Y C 18.929 -0.1732 N/A 0.000
34 RC LWL3 GLOB X C 18.929 -0.7580 N/A 0.000
35 RC LWL4 GLOB Y C 18.929 0.3877 N/A 0.000
36 RC LWL4 GLOB X C 18.929 -0.1694 N/A 0.000
37 RC WL3 GLOB Y C 18.929 2.1316 N/A 0.000
38 RC WL3 GLOB X C 18.929 2.4068 N/A 0.000
39 RC WL4 GLOB Y C 18.929 1.3858 N/A 0.000
40 RC WL4 GLOB X C 18.929 -3.1637 N/A 0.000
41 RC MWL1 GLOB Y C 18.929 -0.5806 N/A 0.000
42 RC MWL1 GLOB X C 18.929 2.0207 N/A 0.000
43 RC MWL2 GLOB Y C 18.929 0.4808 N/A 0.000
44 RC MWL2 GLOB X C 18.929 -1.7213 N/A 0.000
45 RC WL1D GLOB Y C 18.929 0.3255 N/A 0.000
46 RC WL1D GLOB X C 18.929 2.2846 N/A 0.000
47 RC WL2D GLOB Y C 18.929 -0.0104 N/A 0.000
48 RC WL2D GLOB X C 18.929 -0.2246 N/A 0.000
49 RC LWL1D GLOB Y C 18.929 0.2313 N/A 0.000
50 RC LWL1D GLOB X C 18.929 2.2475 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F3- 14
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
51 RC LWL2D GLOB Y C 18.929 0.4839 N/A 0.000
52 RC LWL2D GLOB X C 18.929 2.5129 N/A 0.000
53 RC LWL3D GLOB Y C 18.929 -0.0781 N/A 0.000
54 RC LWL3D GLOB X C 18.929 -0.3412 N/A 0.000
55 RC LWL4D GLOB Y C 18.929 0.1748 N/A 0.000
56 RC LWL4D GLOB X C 18.929 -0.0768 N/A 0.000
57 RC WL3D GLOB Y C 18.929 0.9603 N/A 0.000
58 RC WL3D GLOB X C 18.929 1.0837 N/A 0.000
59 RC WL4D GLOB Y C 18.929 0.6244 N/A 0.000
60 RC WL4D GLOB X C 18.929 -1.4254 N/A 0.000
61 RC DL GLOB Y L 18.929 -0.9255 N/A 0.000
62 RC COLL GLOB Y L 18.929 -0.1361 N/A 0.000
63 RC PLLR1 GLOB Y L 18.929 -2.4534 N/A 0.000
64 RC LL GLOB Y L 18.929 -3.3699 N/A 0.000
65 RC EQ GLOB Y L 18.929 -0.1040 N/A 0.000
66 RC WL1 GLOB Y L 18.929 4.6386 N/A 0.000
67 RC WL2 GLOB Y L 18.929 0.0111 N/A 0.000
68 RC LWL1 GLOB Y L 18.929 4.2795 N/A 0.000
69 RC LWL2 GLOB Y L 18.929 5.5397 N/A 0.000
70 RC LWL3 GLOB Y L 18.929 -1.2950 N/A 0.000
71 RC LWL4 GLOB Y L 18.929 -0.0348 N/A 0.000
72 RC WL3 GLOB Y L 18.929 5.0475 N/A 0.000
73 RC WL4 GLOB Y L 18.929 0.4201 N/A 0.000
74 RC MWL1 GLOB Y L 18.929 0.9596 N/A 0.000
75 RC MWL2 GLOB Y L 18.929 0.6412 N/A 0.000
76 RC WL1D GLOB Y L 18.929 2.0897 N/A 0.000
77 RC WL2D GLOB Y L 18.929 0.0054 N/A 0.000
78 RC LWL1D GLOB Y L 18.929 1.9279 N/A 0.000
79 RC LWL2D GLOB Y L 18.929 2.4954 N/A 0.000
80 RC LWL3D GLOB Y L 18.929 -0.5829 N/A 0.000
81 RC LWL4D GLOB Y L 18.929 -0.0158 N/A 0.000
82 RC WL3D GLOB Y L 18.929 2.2730 N/A 0.000
83 RC WL4D GLOB Y L 18.929 0.1887 N/A 0.000
84 RC RBUPLW GLOB Y C 0.833 3.3800 N/A -1.080
85 RC RBUPLW GLOB Y C 18.667 3.3800 N/A -1.080
86 RC RBUPLW GLOB L C 0.010 3.5000 N/A 0.000
87 RC RBDWLW GLOB Y C 18.667 -3.3800 N/A -1.080
88 RC RBDWLW GLOB Y C 0.833 -3.3800 N/A -1.080
89 RC RBDWLW GLOB L C 0.010 -3.5000 N/A 0.000
90 RC RBUPEQ GLOB Y C 0.833 3.2900 N/A -1.080
91 RC RBUPEQ GLOB Y C 18.667 3.2900 N/A -1.080
92 RC RBUPEQ GLOB L C 0.010 3.4000 N/A 0.000
93 RC RBDWEQ GLOB Y C 18.667 -3.2900 N/A -1.080
94 RC RBDWEQ GLOB Y C 0.833 -3.2900 N/A -1.080
95 RC RBDWEQ GLOB L C 0.010 -3.4000 N/A 0.000
96 RC DL GLOB Y C 18.667 -1.0000 N/A -1.080
97 LC DL GLOB Y C 19.504 -0.1790 N/A -1.000
98 LC LL GLOB Y C 19.504 -0.7930 N/A -1.000
99 LC RS GLOB Y C 19.504 0.0000 N/A -1.000
100 LC LS GLOB Y C 19.504 0.0000 N/A -1.000
Metallic Building Systems User: mmfarahani Page: F3- 15
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
101 LC WL1 GLOB Y C 19.504 1.1100 N/A -1.000
102 LC WL1 GLOB X C 19.504 -0.3700 N/A 0.000
103 LC WL2 GLOB Y C 19.504 1.1100 N/A -1.000
104 LC WL2 GLOB X C 19.504 -0.3700 N/A 0.000
105 LC LWL1 GLOB Y C 19.504 0.5510 N/A -1.000
106 LC LWL1 GLOB X C 19.504 -0.1840 N/A 0.000
107 LC LWL2 GLOB Y C 19.504 0.2960 N/A -1.000
108 LC LWL2 GLOB X C 19.504 -0.0990 N/A 0.000
109 LC LWL3 GLOB Y C 19.504 0.2640 N/A -1.000
110 LC LWL3 GLOB X C 19.504 -0.0880 N/A 0.000
111 LC LWL4 GLOB Y C 19.504 0.0080 N/A -1.000
112 LC LWL4 GLOB X C 19.504 -0.0030 N/A 0.000
113 LC MWL1 GLOB Y C 19.504 1.1100 N/A -1.000
114 LC MWL1 GLOB X C 19.504 -0.3700 N/A 0.000
115 LC MWL2 GLOB Y C 19.504 0.3750 N/A -1.000
116 LC MWL2 GLOB X C 19.504 -0.1250 N/A 0.000
117 LC WL3 GLOB Y C 19.504 0.3750 N/A -1.000
118 LC WL3 GLOB X C 19.504 -0.1250 N/A 0.000
119 LC WL4 GLOB Y C 19.504 0.3750 N/A -1.000
120 LC WL4 GLOB X C 19.504 -0.1250 N/A 0.000
121 LC WL1D GLOB Y C 19.504 0.5000 N/A -1.000
122 LC WL1D GLOB X C 19.504 -0.1670 N/A 0.000
123 LC WL2D GLOB Y C 19.504 0.5000 N/A -1.000
124 LC WL2D GLOB X C 19.504 -0.1670 N/A 0.000
125 LC LWL1D GLOB Y C 19.504 0.2480 N/A -1.000
126 LC LWL1D GLOB X C 19.504 -0.0830 N/A 0.000
127 LC LWL2D GLOB Y C 19.504 0.1330 N/A -1.000
128 LC LWL2D GLOB X C 19.504 -0.0440 N/A 0.000
129 LC LWL3D GLOB Y C 19.504 0.1190 N/A -1.000
130 LC LWL3D GLOB X C 19.504 -0.0400 N/A 0.000
131 LC LWL4D GLOB Y C 19.504 0.0040 N/A -1.000
132 LC LWL4D GLOB X C 19.504 -0.0010 N/A 0.000
133 LC WL3D GLOB Y C 19.504 0.1690 N/A -1.000
134 LC WL3D GLOB X C 19.504 -0.0560 N/A 0.000
135 LC WL4D GLOB Y C 19.504 0.1690 N/A -1.000
136 LC WL4D GLOB X C 19.504 -0.0560 N/A 0.000
137 LR DL XREF Y U 0.000 -0.0546 N/A 0.000
138 RR DL XREF Y U 0.000 -0.0546 N/A 0.000
139 LC SW GLOB Y U 0.000 -0.0208 N/A 0.000
140 LR SW GLOB Y U 0.000 -0.0178 N/A 0.000
141 RC SW GLOB Y U 0.000 -0.0259 N/A 0.000
142 RR SW GLOB Y U 0.000 -0.0178 N/A 0.000
143 LR LL XREF Y U 0.000 -0.2500 N/A 0.000
144 RR LL XREF Y U 0.000 -0.2500 N/A 0.000
145 LC PLLL1 GLOB Y C 19.504 -0.7933 N/A -1.125
146 LC PLLL1 GLOB Z M 19.504 0.7933 N/A 0.000
147 LR PLL1 XREF Y U 0.000 -0.2500 N/A 25.000
148 RR PLL1 XREF Y U 0.000 -0.2500 N/A 25.000
149 LR COLL XREF Y U 0.000 -0.1042 N/A 0.000
150 RR COLL XREF Y U 0.000 -0.1042 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F3- 16
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
151 LC WL1 MEMB Y U 0.000 -0.1426 N/A 0.000
152 RC WL1 MEMB Y U 0.000 0.0000 N/A 0.000
153 LR WL1 MEMB Y U 0.000 0.3650 N/A 0.000
154 RR WL1 MEMB Y U 0.000 0.2727 N/A 0.000
155 LC WL2 MEMB Y U 0.000 -0.2937 N/A 0.000
156 RC WL2 MEMB Y U 0.000 0.0000 N/A 0.000
157 LR WL2 MEMB Y U 0.000 0.2140 N/A 0.000
158 RR WL2 MEMB Y U 0.000 0.1217 N/A 0.000
159 LC LWL1 MEMB Y U 0.000 0.2643 N/A 0.000
160 RC LWL1 MEMB Y U 0.000 0.0000 N/A 0.000
161 LR LWL1 MEMB Y U 0.000 0.3650 N/A 0.000
162 RR LWL1 MEMB Y U 0.000 0.2307 N/A 0.000
163 LC LWL2 MEMB Y U 0.000 0.2643 N/A 0.000
164 RC LWL2 MEMB Y U 0.000 0.0000 N/A 0.000
165 LR LWL2 MEMB Y U 0.000 0.2307 N/A 0.000
166 RR LWL2 MEMB Y U 0.000 0.3650 N/A 0.000
167 RR LWL2 MEMB Y U 18.199 -0.1342 N/A 0.000
168 LC LWL3 MEMB Y U 0.000 0.1133 N/A 0.000
169 RC LWL3 MEMB Y U 0.000 0.0000 N/A 0.000
170 LR LWL3 MEMB Y U 0.000 0.2140 N/A 0.000
171 RR LWL3 MEMB Y U 0.000 0.0797 N/A 0.000
172 LC LWL4 MEMB Y U 0.000 0.1133 N/A 0.000
173 RC LWL4 MEMB Y U 0.000 0.0000 N/A 0.000
174 LR LWL4 MEMB Y U 0.000 0.0797 N/A 0.000
175 RR LWL4 MEMB Y U 0.000 0.2140 N/A 0.000
176 RR LWL4 MEMB Y U 18.199 -0.1342 N/A 0.000
177 LC MWL1 MEMB Y U 0.000 -0.1667 N/A 0.000
178 RC MWL1 MEMB Y U 0.000 0.0000 N/A 0.000
179 LR MWL1 GLOB X U 0.000 0.0264 N/A 26.352
180 RR MWL1 GLOB X U 0.000 0.0264 N/A 26.352
181 LC MWL2 MEMB Y U 0.000 0.1667 N/A 0.000
182 RC MWL2 MEMB Y U 0.000 0.0000 N/A 0.000
183 LR MWL2 GLOB X U 0.000 -0.0264 N/A 26.352
184 RR MWL2 GLOB X U 0.000 -0.0264 N/A 26.352
185 LC WL3 MEMB Y U 0.000 0.2517 N/A 0.000
186 RC WL3 MEMB Y U 0.000 0.0000 N/A 0.000
187 LR WL3 MEMB Y U 0.000 0.2727 N/A 0.000
188 RR WL3 MEMB Y U 0.000 0.3650 N/A 0.000
189 RR WL3 MEMB Y U 18.199 -0.0923 N/A 0.000
190 LC WL4 MEMB Y U 0.000 0.1007 N/A 0.000
191 RC WL4 MEMB Y U 0.000 0.0000 N/A 0.000
192 LR WL4 MEMB Y U 0.000 0.1217 N/A 0.000
193 RR WL4 MEMB Y U 0.000 0.2140 N/A 0.000
194 RR WL4 MEMB Y U 18.199 -0.0923 N/A 0.000
195 LC WL1D MEMB Y U 0.000 -0.0643 N/A 0.000
196 RC WL1D MEMB Y U 0.000 0.0000 N/A 0.000
197 LR WL1D MEMB Y U 0.000 0.1644 N/A 0.000
198 RR WL1D MEMB Y U 0.000 0.1228 N/A 0.000
199 LC WL2D MEMB Y U 0.000 -0.1323 N/A 0.000
200 RC WL2D MEMB Y U 0.000 0.0000 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F3- 17
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
201 LR WL2D MEMB Y U 0.000 0.0964 N/A 0.000
202 RR WL2D MEMB Y U 0.000 0.0548 N/A 0.000
203 LC LWL1D MEMB Y U 0.000 0.1191 N/A 0.000
204 RC LWL1D MEMB Y U 0.000 0.0000 N/A 0.000
205 LR LWL1D MEMB Y U 0.000 0.1644 N/A 0.000
206 RR LWL1D MEMB Y U 0.000 0.1039 N/A 0.000
207 LC LWL2D MEMB Y U 0.000 0.1191 N/A 0.000
208 RC LWL2D MEMB Y U 0.000 0.0000 N/A 0.000
209 LR LWL2D MEMB Y U 0.000 0.1039 N/A 0.000
210 RR LWL2D MEMB Y U 0.000 0.1644 N/A 0.000
211 RR LWL2D MEMB Y U 18.199 -0.0605 N/A 0.000
212 LC LWL3D MEMB Y U 0.000 0.0510 N/A 0.000
213 RC LWL3D MEMB Y U 0.000 0.0000 N/A 0.000
214 LR LWL3D MEMB Y U 0.000 0.0964 N/A 0.000
215 RR LWL3D MEMB Y U 0.000 0.0359 N/A 0.000
216 LC LWL4D MEMB Y U 0.000 0.0510 N/A 0.000
217 RC LWL4D MEMB Y U 0.000 0.0000 N/A 0.000
218 LR LWL4D MEMB Y U 0.000 0.0359 N/A 0.000
219 RR LWL4D MEMB Y U 0.000 0.0964 N/A 0.000
220 RR LWL4D MEMB Y U 18.199 -0.0605 N/A 0.000
221 LC WL3D MEMB Y U 0.000 0.1134 N/A 0.000
222 RC WL3D MEMB Y U 0.000 0.0000 N/A 0.000
223 LR WL3D MEMB Y U 0.000 0.1228 N/A 0.000
224 RR WL3D MEMB Y U 0.000 0.1644 N/A 0.000
225 RR WL3D MEMB Y U 18.199 -0.0416 N/A 0.000
226 LC WL4D MEMB Y U 0.000 0.0454 N/A 0.000
227 RC WL4D MEMB Y U 0.000 0.0000 N/A 0.000
228 LR WL4D MEMB Y U 0.000 0.0548 N/A 0.000
229 RR WL4D MEMB Y U 0.000 0.0964 N/A 0.000
230 RR WL4D MEMB Y U 18.199 -0.0416 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F3- 18
R-Frame Design Program - Version V8.15 Job : 31650A
Web Panel Lengths File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Member Panel Lengths (Feet)
------ -----------------------------------------------------------------------
LC 17.86
LR 24.20
RC 17.86
RR 24.20
Metallic Building Systems User: mmfarahani Page: F3- 19
R-Frame Design Program - Version V8.15 Job : 31650A
Seismic Summary Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Seismic Force Resisting System Per :
ASCE 7 Standard
2016 Edition
Standard Risk Category Building for Seismic Loadings
Seismic Loads Required for Building ................................ Yes
Response Acceleration Coeff., for Short Periods [Ss] (%g) .......... 118.3000
Response Acceleration Coeff., for 1 sec. Periods [S1] (%g) ......... 42.5000
Long-period Transition Period Time [TL] (seconds) .................. 16.0000
Seismic Design Category ............................................ D
Soil Profile Type .................................................. D
Seismic Site Coefficient [Fa] ...................................... 1.2000
Seismic Site Coefficient [Fv] ...................................... 1.8750
Maximum Spectral Response Accel., for Short Periods [Sms] (g) ...... 1.4196
Maximum Spectral Response Accel., for 1 sec. Periods [Sm1] (g) ..... 0.7969
Design Spectral Response Accel., for Short Periods [Sds] (g) ....... 0.9464
Design Spectral Response Accel., for 1 sec. Periods [Sd1] (g) ...... 0.5312
Sds and Sd1 values .......................................... Code-calculated
Seismic Response Modification Factor [R] ........................... 3.5000
Seismic Importance Factor [I] ...................................... 1.0000
Storage/Equipment Areas and/or Service Rooms Exist ................. No
Seismic Story Height [hn] (feet) ................................... 24.1667
Seismic Fundamental Period [T] Used (seconds) ...................... 0.3579
Longitudinal Seismic Overstrength Factor [OMEGA] ................... 2.0000
Seismic Overstrength Factor [OMEGAo] ............................... 2.5000
Longitudinal Seismic Redundancy/Reliability Factor [L-rho] ......... 1.3000
Seismic Redundancy/Reliability Factor [rho] ........................ 1.5000
Snow in Seismic Force Calculations [Used] (%) ...................... 0.00
Snow in Seismic Force Calculations [Min. Required] (%) ............. 0.00
Snow in Seismic Load Combinations [Used] (%) ....................... 0.00
Snow in Seismic Load Combinations [Min. Required] (%) .............. 0.00
Mezz. Live load in Seismic Force Calculations [Used] (%) ........... 0.00
Mezz. Live load in Seismic Force Calculations [Min. Required] (%) .. 0.00
Mezz. Live load in Seismic Load Combinations [Used] (%) ............ 100.00
Mezz. Live load in Seismic Load Combinations [Min. Required] (%) ... 100.00
Building Height Limit (feet) ....................................... 65.0000
Seismic Story Drift Limit Factor ................................... 0.0250
Seismic Story Drift Limit (in) ..................................... 6.0000
Seismic Deflection Amplification Factor [Cd] ....................... 3.0000
Seismic Response Coefficient [Cs] Used ............................. 0.2704
Seismic Story Drift [Cd*Drift/Importance Factor] (in) .............. 5.178
Theta [Px*Ie*Delta/Vx/hx/Cd]........................................ 0.008
Theta Max [.5/BETA/Cd] where BETA=1.0............................... 0.167
Roof Dead Load = 8.801
Wall Weight = 0.000
Collateral Load = 5.312
Snow Load = 0.000
Rafter Crane Weight = 0.000
-------------------------------------
Total Roof Weight = 14.113 kips
User Mass Load (1) = 1.200
-------------------------------------
Total User Mass = 1.200 kips
Total Roof Weight = 14.113
Total User Mass = 1.200
Mezzanine Weight = 0.000
Col. Crane Weight = 0.000
-------------------------------------
TOTAL Bldg Weight = 15.313 kips
X X
Seismic Coeff. = 0.2704
-------------------------------------
BASE SHEAR = 4.1407 kips
Seismic Load for Roof at col # 1 = 1.4218 kips
Seismic Load for Roof at col # 2 = 2.4317 kips
---------------------------------------------------
SEISMIC LOAD for Roof in TOTAL = 3.8536 kips
Seismic Ld for Mass # 1 @ col # 1 = 0.1436 kips
Seismic Ld for Mass # 1 @ col # 2 = 0.1436 kips
---------------------------------------------------
SEISMIC LOAD for Mass in TOTAL = 0.2872 kips
Metallic Building Systems User: mmfarahani Page: F3- 20
R-Frame Design Program - Version V8.15 Job : 31650A
Continued Seismic Load Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
* SEISMIC GENERAL LOAD CARDS GENERATED
--------------------------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
231 LC EQ YREF X C 18.664 1.4218 N/A 0.000
232 LC EQ YREF X C 20.000 0.1436 N/A 0.000
233 RC EQ YREF X C 18.664 2.4317 N/A 0.000
234 RC EQ YREF X C 20.000 0.1436 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F3- 21
R-Frame Design Program - Version V8.15 Job : 31650A
Forces and Allowable Stresses Summary File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Left Column Analysis Length = 18.67 ft Kx = 1.00 Weight = 389. lbs
Effective Ix = 415.0 in4
Part Length Web Height at Outer Flange Web Inner Flange Taper Fy
No. (ft) Start(in) End(in) (in) Thick (in) Angle (ksi)
1 10.00 10.000 17.840 5.00x 0.2500 0.1560 5.00x 0.2500 3.74 55.0
2 7.86 17.840 24.000 5.00x 0.2500 0.2500 5.00x 0.2500 3.74 55.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
110 -7.6 -41.2 -4.4 15.2 38.0 29.5 10.1 0.11 0.48 0.60 0.60 19
208 -7.4 -73.7 -4.4 11.7 40.8 32.4 12.0 0.04 0.44 0.55 0.55 19
--------------------------------------------------------------------------------
Left Rafter Analysis Length = 24.71 ft Kx = 1.00 Weight = 443. lbs
Effective Ix = 297.5 in4
Part Length Web Height at Outer Flange Web Inner Flange Taper Fy
No. (ft) Start(in) End(in) (in) Thick (in) Angle (ksi)
3 4.20 26.000 22.448 5.00x 0.2500 0.1560 5.00x 0.2500 -4.03 55.0
4 10.00 22.448 14.000 5.00x 0.2500 0.1560 5.00x 0.2500 -4.03 55.0
5 10.00 14.000 14.000 5.00x 0.2500 0.1560 5.00x 0.2500 0.00 55.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
301 -4.5 -72.1 5.5 15.5 39.1 29.5 7.0 0.14 0.48 0.62 0.62 19
403 -4.1 -41.6 4.4 8.4 38.4 25.6 8.9 0.11 0.41 0.59 0.59 19
501 -0.8 24.9 -0.6 20.3 34.9 37.4 12.9 0.02 0.39 0.36 0.39 18
--------------------------------------------------------------------------------
Right Column Analysis Length = 18.67 ft Kx = 1.00 Weight = 484. lbs
Effective Ix = 574.5 in4
Part Length Web Height at Outer Flange Web Inner Flange Taper Fy
No. (ft) Start(in) End(in) (in) Thick (in) Angle (ksi)
6 10.00 10.000 17.840 8.00x 0.2500 0.1560 8.00x 0.2500 3.74 55.0
7 7.86 17.840 24.000 8.00x 0.2500 0.2500 8.00x 0.2500 3.74 55.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
612 -11.2 -45.4 -4.9 9.6 36.6 22.8 10.1 0.11 0.43 0.64 0.64 18
707 -11.0 -73.8 -4.9 7.4 38.7 20.3 12.7 0.04 0.42 0.73 0.73 18
--------------------------------------------------------------------------------
Metallic Building Systems User: mmfarahani Page: F3- 22
R-Frame Design Program - Version V8.15 Job : 31650A
Forces and Allowable Stresses Summary File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Right Rafter Analysis Length = 24.71 ft Kx = 1.00 Weight = 443. lbs
Effective Ix = 297.5 in4
Part Length Web Height at Outer Flange Web Inner Flange Taper Fy
No. (ft) Start(in) End(in) (in) Thick (in) Angle (ksi)
8 4.20 26.000 22.448 5.00x 0.2500 0.1560 5.00x 0.2500 -4.03 55.0
9 10.00 22.448 14.000 5.00x 0.2500 0.1560 5.00x 0.2500 -4.03 55.0
10 10.00 14.000 14.000 5.00x 0.2500 0.1560 5.00x 0.2500 0.00 55.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
801 -3.0 -80.9 6.0 15.5 39.1 29.5 7.0 0.15 0.52 0.69 0.69 18
903 -2.7 -46.9 4.9 8.4 38.4 25.7 8.9 0.12 0.44 0.64 0.64 18
1001 -2.3 25.9 -1.1 20.3 34.9 37.4 12.9 0.04 0.41 0.38 0.41 19
--------------------------------------------------------------------------------
TOTAL MEMBER WEIGHT = 1760. lbs
Metallic Building Systems User: mmfarahani Page: F3- 23
R-Frame Design Program - Version V8.15 Job : 31650A
Anchor Rod and Base Plate Design File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
LEFT EXTERIOR COLUMN ANCHOR RODS AND BASE PLATE DESIGN
======================================================
Anchor Rod & Base Plate Design Sizes >>
---------------------------------------
Use ( 4)- 0.750 in. Dia. F1554, Gr. 36 Anchor Rods
Rod Gage : 4.000 in. Rod Spacing (in.): 3.0000, 1 @ 4.0000, 3.5000
Plate Size : 6.0000 x 10.5000 x 0.3750 in. (Width x Depth x Thickness)
Controlling Reactions for Anchor Rod Design >>
----------------------------------------------
Shear Tension Allowable Load Check
Loading Type (kips) (kips) (kips) No. Ratio
-----------------------------------------------------------------
Rod Tension 0.000 7.336 38.436 72 0.19
Rod Shear 10.365 0.000 34.592 39 0.30
Standard Base Plate Welding >> (Using E70 Electrodes)
------------------------------
Fillet Weld Weld Weld Design Weld
Weld Size Length Capacity Force Load Check
Location (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------
Inner Flg 0.25000 5.000 18.562 3.738 1 0.20
Outer Flg 0.25000 5.000 27.842 8.214 40 0.30
Web Plate 0.18750 10.000 41.763 8.466 49 0.20
RIGHT EXTERIOR COLUMN ANCHOR RODS AND BASE PLATE DESIGN
=======================================================
Anchor Rod & Base Plate Design Sizes >>
---------------------------------------
Use ( 4)- 0.750 in. Dia. F1554, Gr. 36 Anchor Rods
Rod Gage : 4.000 in. Rod Spacing (in.): 3.0000, 1 @ 4.0000, 3.5000
Plate Size : 8.0000 x 10.5000 x 0.3750 in. (Width x Depth x Thickness)
Controlling Reactions for Anchor Rod Design >>
----------------------------------------------
Shear Tension Allowable Load Check
Loading Type (kips) (kips) (kips) No. Ratio
-----------------------------------------------------------------
Rod Tension 0.000 9.130 57.653 39 0.16
Rod Shear 9.651 0.000 34.592 48 0.28
Standard Base Plate Welding >> (Using E70 Electrodes)
------------------------------
Fillet Weld Weld Weld Design Weld
Weld Size Length Capacity Force Load Check
Location (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------
Inner Flg 0.25000 8.000 44.548 9.083 42 0.20
Outer Flg 0.25000 8.000 44.548 6.066 39 0.14
Web Plate 0.18750 10.000 41.763 9.651 48 0.23
Metallic Building Systems User: mmfarahani Page: F3- 24
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Vertical Knee Connection @ Left Rafter Depth 1
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 2 rows Extended - 3/4 in. Dia. - Standard (2 bolts per row)
(I.S.) 2 rows Extended - 3/4 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 6.00 x 0.7500 in. Plate: 6.00 x 0.7500 in.
Fy(Min) 50.0 ksi Fy(Min) 50.0 ksi
Fu 65.0 ksi Fu 65.0 ksi
Flanges: Flanges:
O.S. - 6.00 x 0.3750 in. O.S. - 5.00 x 0.2500 in.
I.S. - 4.75 x 0.2500 in. I.S. - 5.00 x 0.2500 in.
Web Depth - 27.043 in. Web Depth - 27.043 in.
Web Thickness 0.250 in. Web Thickness 0.156 in.
Gage - 3.000 in. Gage - 3.000 in.
Center of Bolt to Flange: Center of Bolt to Flange:
Pf top (out) - 2.562 in. Pf top (out) - 2.194 in.
BFCD top (out) - 1.750 in. BFCD top (out) - 1.750 in.
Rise top (out) - 0.552 in. Rise top (out) - 0.552 in.
XTO top (out) - 2.312 in. XTO top (out) - 2.312 in.
Pf top (ins) - 2.542 in. Pf top (ins) - 3.042 in.
BFCD top (ins) - 1.750 in. BFCD top (ins) - 1.750 in.
Rise top (ins) - 0.552 in. Rise top (ins) - 0.552 in.
XTI top (ins) - 2.792 in. XTI top (ins) - 2.792 in.
Pf bot (out) - 1.770 in. Pf bot (out) - 2.059 in.
BFCD bot (out) - 1.750 in. BFCD bot (out) - 1.750 in.
Rise bot (out) - 0.000 in. Rise bot (out) - 0.683 in.
XBO bot (out) - 1.750 in. XBO bot (out) - 1.750 in.
Pf bot (ins) - 2.480 in. Pf bot (ins) - 2.170 in.
BFCD bot (ins) - 1.750 in. BFCD bot (ins) - 1.750 in.
Rise bot (ins) - 0.000 in. Rise bot (ins) - 0.683 in.
XBI bot (ins) - 2.480 in. XBI bot (ins) - 2.480 in.
Bolt Spacing - 3.000 in. Bolt Spacing - 3.000 in.
Controlling Mode : Thick Plate Controlling Mode : Thick Plate
Angle top - 71.6 degrees Angle top -108.4 degrees
Angle bot - 90.0 degrees Angle bot - 67.6 degrees
Left Side Conn Right Side Conn
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
57) 1.3893DL +1.3893COLL -3.5 -186.42 -4.27 12.89 -186.42 -4.27 12.89
52) 0.7107DL +3.5EQ (SOA-R) 137.23 2.35 -6.01 137.23 2.35 -6.01
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.6789 Plate Unity Check (O.S.) = 0.4953
Bolt Unity Check (I.S.) = 0.5222 Plate Unity Check (I.S.) = 0.3607
Metallic Building Systems User: mmfarahani Page: F3- 25
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Peak Connection @ Left Rafter Depth 4
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 2 rows Extended - 3/4 in. Dia. - Standard (2 bolts per row)
(I.S.) 2 rows Extended - 3/4 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 6.00 x 0.3750 in. Plate: 6.00 x 0.3750 in.
Fy(Min) 55.0 ksi Fy(Min) 55.0 ksi
Fu 70.0 ksi Fu 70.0 ksi
Flanges: Flanges:
O.S. - 5.00 x 0.2500 in. O.S. - 5.00 x 0.2500 in.
I.S. - 5.00 x 0.2500 in. I.S. - 5.00 x 0.2500 in.
Web Depth - 14.757 in. Web Depth - 14.757 in.
Web Thickness 0.156 in. Web Thickness 0.156 in.
Gage - 3.000 in. Gage - 3.000 in.
Center of Bolt to Flange: Center of Bolt to Flange:
Pf top (out) - 1.875 in. Pf top (out) - 1.875 in.
BFCD top (out) - 1.750 in. BFCD top (out) - 1.750 in.
Rise top (out) - 0.427 in. Rise top (out) - 0.427 in.
XTO top (out) - 1.750 in. XTO top (out) - 1.750 in.
Pf top (ins) - 2.361 in. Pf top (ins) - 2.361 in.
BFCD top (ins) - 1.750 in. BFCD top (ins) - 1.750 in.
Rise top (ins) - 0.427 in. Rise top (ins) - 0.427 in.
XTI top (ins) - 2.486 in. XTI top (ins) - 2.486 in.
Pf bot (out) - 2.062 in. Pf bot (out) - 2.062 in.
BFCD bot (out) - 1.750 in. BFCD bot (out) - 1.750 in.
Rise bot (out) - 0.427 in. Rise bot (out) - 0.427 in.
XBO bot (out) - 2.188 in. XBO bot (out) - 2.188 in.
Pf bot (ins) - 2.174 in. Pf bot (ins) - 2.174 in.
BFCD bot (ins) - 1.750 in. BFCD bot (ins) - 1.750 in.
Rise bot (ins) - 0.427 in. Rise bot (ins) - 0.427 in.
XBI bot (ins) - 2.049 in. XBI bot (ins) - 2.049 in.
Bolt Spacing - 3.000 in. Bolt Spacing - 3.000 in.
Angle top - 71.6 degrees Angle top - 71.6 degrees
Angle bot -108.4 degrees Angle bot -108.4 degrees
Left Side Conn Right Side Conn
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
69) 0.6DL +0.6WL2 (SOA-L) -3.91 0.47 -0.01 -3.91 0.47 0.01
100) DL +0.75LL +COLL +0.45LWL 18.54 0.55 -1.10 18.54 0.55 1.10
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.1115 Plate Unity Check (O.S.) = 0.1115
Bolt Unity Check (I.S.) = 0.5062 Plate Unity Check (I.S.) = 0.5062
Required Connection Plate Welding >> (Using E70 Electrodes)
------------------------------------
Welded Weld Weld Weld Design Weld
Joint Size Length Capacity Force Load Check
Weld Location Type (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------------------
Left Side of Conn
Inner Flg Fillet-BS 0.1875 10.0000 41.7635 14.9647 100 0.3583
Outer Flg Fillet-BS 0.1875 10.0000 41.7635 3.2516 69 0.0779
Web Plate Fillet-BS 0.1875 29.5146 82.1755 2.5850 74 0.0315
Right Side of Conn
Inner Flg Fillet-BS 0.1875 10.0000 41.7635 14.9647 100 0.3583
Outer Flg Fillet-BS 0.1875 10.0000 41.7635 3.2516 69 0.0779
Web Plate Fillet-BS 0.1875 29.5146 82.1755 2.5850 74 0.0315
------------------------------------------------------------------------------
NS - Near side weld, FS - Far side weld, BS - Both sides weld.
Metallic Building Systems User: mmfarahani Page: F3- 26
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Vertical Knee Connection @ Right Rafter Depth 1
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 2 rows Extended - 3/4 in. Dia. - Standard (2 bolts per row)
(I.S.) 2 rows Extended - 3/4 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 8.00 x 0.7500 in. Plate: 6.00 x 0.7500 in.
Fy(Min) 50.0 ksi Fy(Min) 50.0 ksi
Fu 65.0 ksi Fu 65.0 ksi
Flanges: Flanges:
O.S. - 8.00 x 0.3750 in. O.S. - 5.00 x 0.2500 in.
I.S. - 7.75 x 0.2500 in. I.S. - 5.00 x 0.2500 in.
Web Depth - 27.043 in. Web Depth - 27.043 in.
Web Thickness 0.250 in. Web Thickness 0.156 in.
Gage - 3.000 in. Gage - 3.000 in.
Center of Bolt to Flange: Center of Bolt to Flange:
Pf top (out) - 2.562 in. Pf top (out) - 2.194 in.
BFCD top (out) - 1.750 in. BFCD top (out) - 1.750 in.
Rise top (out) - 0.552 in. Rise top (out) - 0.552 in.
XTO top (out) - 2.312 in. XTO top (out) - 2.312 in.
Pf top (ins) - 2.542 in. Pf top (ins) - 3.042 in.
BFCD top (ins) - 1.750 in. BFCD top (ins) - 1.750 in.
Rise top (ins) - 0.552 in. Rise top (ins) - 0.552 in.
XTI top (ins) - 2.792 in. XTI top (ins) - 2.792 in.
Pf bot (out) - 1.770 in. Pf bot (out) - 2.059 in.
BFCD bot (out) - 1.750 in. BFCD bot (out) - 1.750 in.
Rise bot (out) - 0.000 in. Rise bot (out) - 0.683 in.
XBO bot (out) - 1.750 in. XBO bot (out) - 1.750 in.
Pf bot (ins) - 2.480 in. Pf bot (ins) - 2.170 in.
BFCD bot (ins) - 1.750 in. BFCD bot (ins) - 1.750 in.
Rise bot (ins) - 0.000 in. Rise bot (ins) - 0.683 in.
XBI bot (ins) - 2.480 in. XBI bot (ins) - 2.480 in.
Bolt Spacing - 3.000 in. Bolt Spacing - 3.000 in.
Controlling Mode : Thick Plate Controlling Mode : Thick Plate
Angle top - 71.6 degrees Angle top -108.4 degrees
Angle bot - 90.0 degrees Angle bot - 67.6 degrees
Left Side Conn Right Side Conn
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
56) 1.3893DL +1.3893COLL +3.5 -215.69 0.85 12.93 -215.69 0.85 12.93
53) 0.7107DL -3.5EQ (SOA-L) 163.80 -2.64 -5.96 163.80 -2.64 -5.96
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.8104 Plate Unity Check (O.S.) = 0.5819
Bolt Unity Check (I.S.) = 0.6022 Plate Unity Check (I.S.) = 0.4144
Metallic Building Systems User: mmfarahani Page: F3- 27
R-Frame Design Program - Version V8.15 Job : 31650A
Knee and Stiffener Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Left Knee Design
================
Knee Web Thickness : Use 0.2500 in. Thick Web
Bearing Stiffener Type : Horizontal
Bearing Stiffener at Knee : 2.2500 X 0.2500 in.
Column Cap Plate : 6.0000 X 0.3750 in.
Stiffener Data for the Left Knee Web Panel
==========================================
Horizon. Knee Stiffener Design Data (A Stiffener on Both Sides of Knee Web and
=================================== Located Opposite Rafter Inner Flange.)
Stiff. Stiff. Design Design Design Web Web Strip Gross
Angle Length Width Thick. K Thick. Width Area
(deg.) (in.) (in.) (in.) Factor (in.) (in.) (sq.in.)
0.00000 24.00000 2.25000 0.25000 0.75000 0.25000 6.25000 2.68750
Moment of Radius of KL Effective Design Design Yield
Inertia Gyration -- Ratio Compr. Area Qs Qa Stress
(in.4) (in.) r (sq.in.) Factor Factor (ksi)
2.24056 0.91307 19.71371 2.68750 1.00000 1.00000 55.0000
Compr. Allow. Max. Tension Allow. Max.
Load Compr. Compr. Compr. Load Tension Tension Tension
Comb. Force Force Check Comb. Force Force Check
No. (kips) (kips) Ratio No. (kips) (kips) Ratio
57 -83.0240 133.0312 0.6241 52 60.7170 106.4250 0.4564
Knee Web Plate Design Data, Web Yield Stress, Fy= 55.000 ksi
==========================
KNEE WEB PLATE SHEAR CHECK ALONG THE COLUMN CAP PLATE:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Rafter Load ------------------ --- --- Shear Shear Web
Moment Comb. a h h t Stress Stress Shear
(k-ft) No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
-186.42 57 24.00000 27.40641 0.88 109.63 25.4408 13.1249 0.5159
KNEE WEB PLATE SHEAR CHECK ALONG THE HORIZONTAL KNEE STIFFENERS:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Load ------------------ --- --- Shear Shear Web
Comb. a h h t Stress Stress Shear
No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
57 24.00000 27.40641 0.88 109.63 25.4408 13.1249 0.5159
KNEE WEB PLATE SHEAR CHECK ALONG THE COLUMN OUTER FLANGE:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Column Load ------------------ --- --- Shear Shear Web
Moment Comb. a h h t Stress Stress Shear
(k-ft) No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
-188.25 57 27.40641 24.00000 1.14 96.00 24.9665 17.7795 0.7121
KNEE WEB PLATE SHEAR CHECK ALONG THE COLUMN KNEE CONNECTION PLATE:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Load ------------------ --- --- Shear Shear Web
Comb. a h h t Stress Stress Shear
No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
57 27.40641 24.00000 1.14 96.00 24.9665 8.7584 0.3508
Knee Panel Weld Sizes
=====================
Required (Due to Weld Shear) Min. Fillet Welds, around the Knee Web Panel are:
Column Cap Plate: 0.2500 in. x 25.298 in. GMAW on NEAR Side (STD. WELD)
Column Cap Plate: 0.2500 in. x 3.000 in. GMAW on FAR Side (STD. WELD)
Horizontal Stiffener: 0.2500 in. x 24.000 in. GMAW on NEAR Side (STD. WELD)
Horizontal Stiffener: 0.2500 in. x 3.000 in. GMAW on FAR Side (STD. WELD)
Column Outer Flange: 0.1875 in. x 19.406 in. SAW on NEAR Side (STD. WELD)
Column Outer Flange: 0.1875 in. x 19.406 in. GMAW on FAR Side (STD. WELD)
Column Connection Pl.: 0.1875 in. x 27.406 in. GMAW on BOTH Sides (STD. WELD)
Knee Stiffener to Connection Plate Weld
=======================================
0.1875 in. x 2.250 in. GMAW Fillet Weld on BOTH Sides of Stiff. (STD. WELD)
(STD. WELD)- Company Standard Weld was Designed and Checked as OK.
Right Knee Design
=================
Knee Web Thickness : Use 0.2500 in. Thick Web
Bearing Stiffener Type : Horizontal
Bearing Stiffener at Knee : 3.7500 X 0.2500 in.
Column Cap Plate : 8.0000 X 0.3750 in.
Stiffener Data for the Right Knee Web Panel
===========================================
Horizon. Knee Stiffener Design Data (A Stiffener on Both Sides of Knee Web and
=================================== Located Opposite Rafter Inner Flange.)
Stiff. Stiff. Design Design Design Web Web Strip Gross
Angle Length Width Thick. K Thick. Width Area
(deg.) (in.) (in.) (in.) Factor (in.) (in.) (sq.in.)
0.00000 24.00000 3.75000 0.25000 0.75000 0.25000 6.25000 3.43750
Moment of Radius of KL Effective Design Design Yield
Inertia Gyration -- Ratio Compr. Area Qs Qa Stress
(in.4) (in.) r (sq.in.) Factor Factor (ksi)
9.70540 1.68029 10.71241 3.43750 1.00000 1.00000 55.0000
Compr. Allow. Max. Tension Allow. Max.
Load Compr. Compr. Compr. Load Tension Tension Tension
Comb. Force Force Check Comb. Force Force Check
No. (kips) (kips) Ratio No. (kips) (kips) Ratio
56 -93.1616 170.1562 0.5475 53 69.7516 136.1250 0.4099
Knee Web Plate Design Data, Web Yield Stress, Fy= 55.000 ksi
==========================
KNEE WEB PLATE SHEAR CHECK ALONG THE COLUMN CAP PLATE:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Rafter Load ------------------ --- --- Shear Shear Web
Moment Comb. a h h t Stress Stress Shear
(k-ft) No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
-215.69 56 24.00000 27.40641 0.88 109.63 25.4408 15.6690 0.6159
KNEE WEB PLATE SHEAR CHECK ALONG THE HORIZONTAL KNEE STIFFENERS:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Load ------------------ --- --- Shear Shear Web
Comb. a h h t Stress Stress Shear
No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
56 24.00000 27.40641 0.88 109.63 25.4408 15.6690 0.6159
KNEE WEB PLATE SHEAR CHECK ALONG THE COLUMN OUTER FLANGE:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Column Load ------------------ --- --- Shear Shear Web
Moment Comb. a h h t Stress Stress Shear
(k-ft) No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
-214.96 56 27.40641 24.00000 1.14 96.00 24.9665 20.3563 0.8153
KNEE WEB PLATE SHEAR CHECK ALONG THE COLUMN KNEE CONNECTION PLATE:
Knee Web Pl. Dimensions a h Allow. Web Pl. Max.
Load ------------------ --- --- Shear Shear Web
Comb. a h h t Stress Stress Shear
No. (in.) (in.) Ratio Ratio (ksi) (ksi) Ratio
56 27.40641 24.00000 1.14 96.00 24.9665 9.8405 0.3941
Knee Panel Weld Sizes
=====================
Required (Due to Weld Shear) Min. Fillet Welds, around the Knee Web Panel are:
Column Cap Plate: 0.2500 in. x 25.298 in. GMAW on NEAR Side (STD. WELD)
Column Cap Plate: 0.2500 in. x 3.000 in. GMAW on FAR Side (STD. WELD)
Horizontal Stiffener: 0.2500 in. x 24.000 in. GMAW on NEAR Side (STD. WELD)
Horizontal Stiffener: 0.2500 in. x 3.000 in. GMAW on FAR Side (STD. WELD)
Column Outer Flange: 0.1875 in. x 19.406 in. SAW on NEAR Side (STD. WELD)
Column Outer Flange: 0.1875 in. x 19.406 in. GMAW on FAR Side (STD. WELD)
Column Connection Pl.: 0.1875 in. x 27.406 in. GMAW on BOTH Sides (STD. WELD)
Knee Stiffener to Connection Plate Weld
=======================================
0.1875 in. x 3.750 in. GMAW Fillet Weld on BOTH Sides of Stiff. (STD. WELD)
(STD. WELD)- Company Standard Weld was Designed and Checked as OK.
Metallic Building Systems User: mmfarahani Page: F3- 28
R-Frame Design Program - Version V8.15 Job : 31650A
Flange Brace Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Girt Spaces - Vertical Measurements
Left Column Right Column
1 @ 7'6 @ FLOOR 1 @ 7'6 @ FLOOR
1 @ 6'0 1 @ 6'0
1 @ 6'6 @ EAVE 1 @ 3'0
1 @ 3'6 @ EAVE
Purlin Spaces - Horizontal Measurements
Left Rafter Right Rafter
2 @ 3'3-11/16" @ EAVE 2 @ 3'3-11/16" @ EAVE
4 @ 4'4 4 @ 4'4
1 @ 1'0-9/16" @ PEAK 1 @ 1'0-9/16" @ PEAK
--------------------------------------------------------------------------------
Member Distance to Brace Points (feet)
- Left Rafter : Measured along T.F. from left steel line
- Right Rafter : Measured along T.F. from right steel line
- Ext. Columns : Measured along T.F. from base
--------------------------------------------------------------------------------
LFT COLUMN 7.50 13.50
(C) (C)
LFT RAFTER 3.49 6.98 11.55 16.11 20.68 25.25
(C) (C) (N) (C) (C) (C)
RGT COLUMN 7.50 13.50 16.50
(O) (O) (C)
RGT RAFTER 3.49 6.98 11.55 16.11 20.68 25.25
(C) (C) (N) (C) (C) (C)
--------------------------------------------------------------------------------
"N" Indicates that No flange braces are located at the brace point
"C" Indicates that One 2"x2"x14 ga flange brace is located at the brace point
"O" Indicates that Brace point is optional and is not considered in design
--------------------------------------------------------------------------------
Metallic Building Systems User: mmfarahani Page: F3- 29
R-Frame Design Program - Version V8.15 Job : 31650A
Primary Deflection Report File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
COLUMN TOP DEFLECTIONS for LOAD COMBS. (Positive = X: Right Y:Upward) (Inches)
==============================================================================
Ext. Left Col Ext Right Col
X-Def Y-Def X-Def Y-Def
------------------------------------------------------------------------------
Pos. Max 4.958 0.054 5.482 0.052
Load Comb 136 19 138 23
Defl. H/ 45 H/ 40
------------------------------------------------------------------------------
Neg. Max -5.798 -0.053 -5.087 -0.060
Load Comb 139 13 137 19
Defl. H/ 38 H/ 44
==============================================================================
MAX RAFTER DEFLECTIONS for SPAN #1. (Positive = Y:Upw ard)
==============================================================================
Max. Downward Deflection Max. Upward Deflection
Y-Def. X-Dist. from Left S.L. Y-Def. X-Dist. from Left S.L.
------------------------------------------------------------------------------
Max. Def -1.102 in. 25.00 ft. 0.400 in. 33.40 ft.
Load Comb 7 126
Defl. L/537 L/999
==============================================================================
PEAK DEFLECTIONS (Positive = Y:Upward)
====================
Y-Def
--------------------
Pos. Max 0.295 in.
Load Comb 126
Defl. L/999
--------------------
Neg. Max -1.102 in.
Load Comb 8
Defl. L/537
====================
Note: The reported horizontal deflections for the load combinations shown below
have been amplified by the value of Cd (deflection amplification factor).
LC# Cd Used
----- -------
134 3.0
135 3.0
136 3.0
137 3.0
138 3.0
139 3.0
Metallic Building Systems User: mmfarahani Page: F3- 30
R-Frame Design Program - Version V8.15 Job : 31650A
Stiffener Design for Leanto File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Leanto Stiffener on Right Column
================================
Web Thickness : Use 0.2500 inches Thick Web
Bearing Stiffener Type : No stiffeners are required
Bottom Bearing Stiffener
Bearing Stiffener Size : Not Required
Control Case : 121
Allowable At Ctrl Case : 22.344 kips
Check Ratio : 0.1851
Panel Stiffener Size : Not Required
Control Case : 0
Allowable Shear Cap. : 0.000 kips
Check Ratio : 0.0000
Metallic Building Systems User: mmfarahani Page: F3- 31
R-Frame Design Program - Version V8.15 Job : 31650A
Stiffener Design for Leanto File: frame_2_3.fra Date: 9/22/21
cs 50./20./19.833 20./100./0. Start Time: 18:26:36
--------------------------------------------------------------------------------
Vertical Clearance at the Left Knee is 17.8804 feet
Vertical Clearance at the Right Knee is 17.8804 feet
Metallic Building Systems User: mmfarahani Page: F2- 1
R-Frame Design Program - Version V8.15 Job : 31650A
Input Data Echo File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
--------------------------------------------------------------------------------
VERSION V8.15
BRAND METALLIC
BUILDING LABEL B
FRAME_ID 2
# FRAME LEFT SIDE IS BLDG. PLANE SWA
# AND FRAME RIGHT SIDE IS BLDG. PLANE
DESCRIPTION lt 12./16./12.167 20./100./0.
PRINT echo code loads summary detail profile deflect base conn flg_brace \
stiff pro_grplds seismic boss
DATASET base combinations connection members wind_array brace
OPTIMIZATION depth *PLANT ATW *JOB 31650A
LOCATION frame lines 1
LATERAL GRID LABEL 1
LONGITUDINAL GRID LABEL A B
NUMBER FRAMES 1 *PRICE summary
MAIN GEOMETRY
WIDTH 50. 25.
EAVE LEFT 20.
ROOF SLOPE LEFT 4.
EAVE RIGHT 20.
ROOF SLOPE RIGHT 4.
LENGTH 60.
SPANS 20. 10. 20.
LEANTO RIGHT GEOMETRY
WIDTH 12. 12.
EAVE 16.
ROOF SLOPE 4.
LENGTH 60.
TYPE lt p cs 60. 60. right
BRACING SIDE LC=3 RA=3 RC=3
FLANGE BRACE ATTACHMENT LC=0 RA=0
GIRT DEPTH 8. 8.25
PURLIN DEPTH 8. 8.25
GIRT SPACING
NOFB 0.
PURLIN SPACING 2@3. 4.
PURLIN THICKNESS 0.059
PURLIN FLANGE 2.5
STIFFNESS CHECK SNOW
PURLIN STIFFNESS 7.857 12.59 2.788 6.848
LATERAL BRACE LENGTH 19.667
BUILDING CODE IB18 U=Normal P=N
DEAD LOAD 2.653
COLLATERAL LOAD 1.
LIVE LOAD 20. REDUCE
SNOW R=0. E=0.9 T=1.2 S=N WEL=27. WER=39. WML=25. WMR=37.
WIND V=100.mph VDEF=67.mph E=C Z=end GE= 94.0 O=P HS=2DE X=0.000 \
H=0.000 LH=9999.000
SEISMIC LOAD S1=42.5 Ss=118.3 TL=16. %CR=NORM %SR=NORM RHOT=1.5 \
RHOL=1.3 R=3.5 RL=3.25 LOF=2. TOF=2.5 Ct=0.028 Cd=3.
SOIL PROFILE D
CODE LABEL 2019 California Building Code
ROOF TRIBUTARY TR=12.167
WALL TRIBUTARY TR=10.167
TFA KNEE YES
DEFLECTION ROOF L=180 S=180 W=180 G=120
DEFLECTION WALL L=60 S=60 W=60 E=50 C=100 G=60 TE=50
CANOPYL CFT = C FL=Y PR= 2. LEN= 64. HT= 16. CS= 4. PD= 8. FT= 0.205 WH= \
7.48 MN= 5. 0.178 BAY= 11.833 DL= 4.994
MIN_MOMT_BOLT_DIA 0.50
BOSS 8.25
END
Metallic Building Systems User: mmfarahani Page: F2- 2
R-Frame Design Program - Version V8.15 Job : 31650A
Building Grid label legend File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Building Grid Label Legend
==========================
Building : B
Frame Number : 2
No. of Frames : 1
Left Column : Column @ * - A
Right Support : Support @ * - B
*Frames located @ 1
Metallic Building Systems User: mmfarahani Page: F2- 3
R-Frame Design Program - Version V8.15 Job : 31650A
Code Summary Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Building :B
Frame Number :2 Location: frame lines 1
No. of Frames: 1
2019 CALIFORNIA BUILDING CODE
Main Code Requirements Per :
International Building Code
2018 Edition
Supporting Design Manual(s):
2016 AISC Specification for Structural Steel Buildings,Allowable Strength Design
2010 AISC Seismic Provisions for Structural Steel Buildings
Frame Data
----------
Eave height Left (feet)............................................. 16.000
Horizontal width from left to right steel line (feet)............... 12.000
Horizontal distance to ridge from left side (feet).................. 12.000
Roof Slope Left (rise:12)........................................... 4.000
Column Slope Left & Right (lat:12).................................. 0.000
Purlin depth left & right side (inches)............................. 8.000
Frame Rafter Inset left & right side (inches)....................... 8.250
Girt depth left & right side (inches)............................... 8.000
Frame Column Inset left & right side (inches)....................... 8.250
Tributary Width left side (feet).................................... 10.167
..................................from Height 0.00 to Height 16.00
Tributary Width roof (feet)......................................... 12.167
Tension Flange Bolt Hole Reduction.................................. Yes
Tension Field Action at Knee........................................ Yes
Second order analysis method........................................ C2.2b
Frame Design Loads
------------------
Dead Load to Frame Rafter (psf)..................................... 2.653
Frame Rafter Dead Weight (psf)...................................... 0.812
Total Roof Dead Weight (psf)........................................ 3.465
Collateral Load to Frame Rafter (psf)............................... 1.000
Roof Live Load Entered (psf) W/ Live Load Reduction Requested....... 20.000
Design Roof Live Load Used (psf).................................... 20.000
Roof Snow Load Entered (psf)........................................ 0.000
Snow Exposure Factor Entered [Ce] .................................. 0.900
Snow Importance Factor [I] -- Standard Use Category................. 1.000
Snow Thermal Factor Entered [Ct] -- User Entered.................... 1.200
Snow Thermal Factor Used [Ct]Unheated Building...................... 1.200
Slippery & Unobstructed Roof Surface................................ No
Roof Snow Load [Pf = 0.7*Ce*Ct*I*Pg] (psf).......................... 0.000
Snow Slope Factor [Cs].............................................. 1.000
Sloped Roof Snow Load Used [Ps = Cs*Pf] (psf)....................... 0.000
Metallic Building Systems User: mmfarahani Page: F2- 4
R-Frame Design Program - Version V8.15 Job : 31650A
Wind Summary Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
Eave height Left (feet)............................................. 16.000
Wind Elevation on left column (feet)................................ 20.000
Wind Elevation on right column (feet)............................... 20.000
Mean Roof Wind Elevation (feet)..................................... 24.167
Total frame width (feet)............................................ 12.000
Total building length (feet)........................................ 60.000
Number of primary wind loadings .................................... 18
Number of wind zones ............................................... 1
Design wind velocity for frames (mph)............................... 100.000
Serviceability wind velocity for frames (mph)....................... 67.000
Elevation Above Sea Level (ft)...................................... 94.000
Wind Exposure Category -- open terrain areas........................ Exp C
Building Enclosure Classification ......................... Partially Enclosed
Velocity Pressure [qh] for strength (psf) at Height h= 24.167 feet 20.353
Velocity Pressure [qh] for serviceability (psf)at Height h= 24.167 feet 9.168
Velocity Pressure Exposure Coefficient [Kh]......................... 0.939
Wind Directionality Factor [Kd]..................................... 0.850
Ground Elevation Factor [Ke]........................................ 0.997
Wind Topographic Factor [Kzt]....................................... 1.000
***** Building Wind Zones *****
-----------------------------------
***** Wind Zone ***** Velocity
Wind Lower Upper Pressure *** Wind Case #1 Below ****
Zone Elevation Elevation qz Windward Wall Leeward Wall
No. (feet) (feet) (psf) (psf) (psf)
--------------------------------------------------------------------
1 0.0000 28.3333 20.3533 -23.8134 4.6813
Windward wall design pressure, P:
P = qh[ (GCpf) - (GCpi) ]
Note that the above reported pressure(s) is used for strength calculations only.
Metallic Building Systems User: mmfarahani Page: F2- 5
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Wind Summary Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
*** PRIMARY WIND COEFFICIENTS FOR LEAN-TO FRAME ***
--------------------------------------------------------------------------------
Wind Load WL1 Wind from left direction [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -1.170 -1.220(100.0%) -1.620( 0.0%) 0.230
--------------------------------------------------------------------------------
Wind Load WL2 Wind from left direction [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.070 -0.120(100.0%) -0.520( 0.0%) 1.330
--------------------------------------------------------------------------------
Wind Load LWL1 Longitudinal wind [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -1.030 -1.080(100.0%) -1.620( 0.0%) -1.030
--------------------------------------------------------------------------------
Wind Load LWL2 Longitudinal wind [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -1.030 -1.620(100.0%) -1.080( 0.0%) -1.030
--------------------------------------------------------------------------------
Wind Load LWL3 Longitudinal wind [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.070 0.020(100.0%) -0.520( 0.0%) 0.070
--------------------------------------------------------------------------------
Wind Load LWL4 Longitudinal wind [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.070 -0.520(100.0%) 0.020( 0.0%) 0.070
--------------------------------------------------------------------------------
Wind Load MWL1 Min. Wind from left dir. [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.500 0.500 0.500 0.500
--------------------------------------------------------------------------------
Wind Load MWL2 Min. Wind from right dir. [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.500 -0.500 -0.500 -0.500
--------------------------------------------------------------------------------
Wind Load WL3 Wind from right direction [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.230 -1.620(100.0%) -1.220( 0.0%) -1.170
--------------------------------------------------------------------------------
Wind Load WL4 Wind from right direction [end zone]
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 1.330 -0.520(100.0%) -0.120( 0.0%) -0.070
--------------------------------------------------------------------------------
Notes :
1. Wind coefficients applied to the roof may be located as a percentage
of the total frame width (xx.x%). If not shown the coefficients are
applied fully to their respective rafter.
Deflection Design Limits >>
---------------------------
Rafter deflection limit for Live load only [L/{x}] ................. 180.000
Rafter deflection limit for Snow load only [L/{x}] ................. 180.000
Rafter deflection limit for Serviceability Wind load only [L/{x}] .. 180.000
Rafter deflection limit for Gravity load conditions [L/{x}] ........ 120.000
Column sway deflection limit for Live load only [L/{x}] ............ 60.000
Column sway deflection limit for Snow load only [L/{x}] ............ 60.000
Column sway deflection limit for Serviceability Wind load only [L/{x}] 60.000
Column sway deflection limit for Seismic load only [L/{x}] ......... 50.000
Column sway deflection limit for Crane load conditions [L/{x}] ..... 100.000
Column sway deflection limit for Gravity load conditions [L/{x}] ... 60.000
Column sway deflection limit for Seismic load conditions [L/{x}] ... 50.000
Metallic Building Systems User: mmfarahani Page: F2- 6
R-Frame Design Program - Version V8.15 Job : 31650A
Load Combinations Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Load Combination :
------------------
1) DL +LL +COLL N A
2) 1.1325DL +1.05EQ N A
3) 1.1325DL -1.05EQ N A
4) 1.1325DL +1.1325COLL +1.05EQ N A
5) 1.1325DL +1.1325COLL -1.05EQ N A
6) 0.4675DL +1.05EQ N A
7) 0.4675DL -1.05EQ N A
8) 0.7107DL +2.5EQ N C R
9) 0.7107DL -2.5EQ N C R
10) 1.3893DL +1.3893COLL +2.5EQ N C R
11) 1.3893DL +1.3893COLL -2.5EQ N C R
12) 0.7107DL +2.5EQ N B R
13) 0.7107DL -2.5EQ N B R
14) 1.3893DL +1.3893COLL +2.5EQ N B R
15) 1.3893DL +1.3893COLL -2.5EQ N B R
16) DL +0.6WL1 N A
17) DL +0.6WL2 N A
18) DL +0.6LWL1 N A
19) DL +0.6LWL2 N A
20) DL +0.6LWL3 N A
21) DL +0.6LWL4 N A
22) DL +0.6WL3 N A
23) DL +0.6WL4 N A
24) 0.6DL +0.6WL1 N A
25) 0.6DL +0.6WL2 N A
26) 0.6DL +0.6LWL1 N A
27) 0.6DL +0.6LWL2 N A
28) 0.6DL +0.6LWL3 N A
29) 0.6DL +0.6LWL4 N A
30) 0.6DL +0.6WL3 N A
31) 0.6DL +0.6WL4 N A
32) 0.6MWL1 N M
33) 0.6MWL2 N M
34) DL +COLL +0.6WL1 N A
35) DL +COLL +0.6WL2 N A
36) DL +COLL +0.6LWL1 N A
37) DL +COLL +0.6LWL2 N A
38) DL +COLL +0.6LWL3 N A
39) DL +COLL +0.6LWL4 N A
40) DL +COLL +0.6WL3 N A
41) DL +COLL +0.6WL4 N A
42) DL +0.75LL +COLL +0.45WL1 N A
43) DL +0.75LL +COLL +0.45WL2 N A
44) DL +0.75LL +COLL +0.45LWL1 N A
45) DL +0.75LL +COLL +0.45LWL2 N A
46) DL +0.75LL +COLL +0.45LWL3 N A
47) DL +0.75LL +COLL +0.45LWL4 N A
48) DL +0.75LL +COLL +0.45WL3 N A
49) DL +0.75LL +COLL +0.45WL4 N A
50) DL +COLL +RS N A
Metallic Building Systems User: mmfarahani Page: F2- 7
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Load Combination :
------------------
51) DL +COLL +LS N A
52) LL (deflection only) D
53) WL1D (deflection only) D
54) WL2D (deflection only) D
55) LWL1D (deflection only) D
56) LWL2D (deflection only) D
57) LWL3D (deflection only) D
58) LWL4D (deflection only) D
59) WL3D (deflection only) D
60) WL4D (deflection only) D
61) 1.3893DL+EQ (deflection only) D E
62) 1.3893DL-EQ (deflection only) D E
63) 0.7107DL+EQ (deflection only) D E
64) 0.7107DL-EQ (deflection only) D E
65) 1.3893DL+1.3893COLL+EQ (deflection only) D E
66) 1.3893DL+1.3893COLL-EQ (deflection only) D E
Metallic Building Systems User: mmfarahani Page: F2- 8
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Where :
-------
DL = Roof Dead Load
LL = Roof Live Load
COLL = Roof Collateral Load
EQ = Lateral Seismic Load [parallel to plane of frame]
WL1 = Wind from Left to Right with +GCpi
WL2 = Wind from Left to Right with -GCpi
LWL1 = Windward Corner Left with +GCpi
LWL2 = Windward Corner Right with +GCpi
LWL3 = Windward Corner Left with -GCpi
LWL4 = Windward Corner Right with -GCpi
WL3 = Wind from Right to Left with +GCpi
WL4 = Wind from Right to Left with -GCpi
MWL1 = Minimum Wind Load
MWL2 = Minimum Wind Load
RS = Unbalanced Right Roof Snow Load
LS = Unbalanced Left Roof Snow Load
WL1D = Wind from Left to Right with +GCpi at Service Level
WL2D = Wind from Left to Right with -GCpi at Service Level
LWL1D = Windward Corner Left with +GCpi at Service Level
LWL2D = Windward Corner Right with +GCpi at Service Level
LWL3D = Windward Corner Left with -GCpi at Service Level
LWL4D = Windward Corner Right with -GCpi at Service Level
WL3D = Wind from Right to Left with +GCpi at Service Level
WL4D = Wind from Right to Left with -GCpi at Service Level
Combination Descriptions :
--------------------------
N= No 1/3 Increase in Allowable for Combination
B= Base Only Combination
A= Allowable Strength Design Combination - ASD16
C= Column Only Combination for Seismic
D= Deflection Only Combination
R= Load and Resistance Factor Design Combination - LRFD
E= Cd is applied and Ie is omitted from frame drift calculations
M= Minimum Wind Load Combination. Checked for Allowable Strength not for Deflection
Metallic Building Systems User: mmfarahani Page: F2- 9
R-Frame Design Program - Version V8.15 Job : 31650A
Canopy Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Left Side Canopy Data
---------------------
Canopy #1 : At Eave Canopy w/ Flush purlin
Width (horizontal projection from steel line) (feet)...... 2.0000
Length (used for drifting snow only) (feet)............... 64.0000
Canopy bay size (feet).................................... 11.8330
Roof height at the wall(feet)............................. 16.0000
Roof height at the free end (feet)........................ 15.3333
Roof slope (rise:12)...................................... 4.0000
Purlin depth (inches) .................................... 8.0000
Minimum cap plate width (inches) ......................... 5.0000
Minimum cap plate thickness (inches)...................... 0.1780
Canopy beam flange thickness (inches)..................... 0.2050
Canopy beam vertical web height at the steel line (inches) 7.4800
Connection plate thickness (inches)....................... 0.0000
Canopy Design Loads
-------------------
Snow Thermal Factor [Ct] -- Unheated Canopy 1.2000
Slippery & Unobstructed Canopy Roof Surface No
Canopy Snow Slope Factor [Cs] 1.0000
Total Canopy Dead Load (psf).............................. 4.9940
Canopy Collateral Load (psf).............................. 0.0000
Canopy Live Load Entered (psf)............................ 20.0000
Canopy Live Load Used (psf)............................... 20.0000
Design Snow Load Used (psf)............................... 0.0000
Unbalanced Snow Load Used (psf)........................... 0.0000
Canopy wind elevation (feet).............................. 19.6667
Canopy basic wind pressure (psf).......................... 20.3533
Number of wind arrays .................................... 18
Canopy wind coefficients and design loads
-----------------------------------------
Wind Wind Coeff. Design Load
Array (psf)
WL1 -0.670 -13.64
WL2 -0.670 -13.64
LWL1 -0.530 -10.79
LWL2 -1.070 -21.78
LWL3 0.570 11.60
LWL4 0.030 0.61
MWL1 -0.670 -13.64
MWL2 -1.770 -36.03
WL3 -1.770 -36.03
WL4 -1.770 -36.03
WL1D -0.670 -6.14
WL2D -0.670 -6.14
LWL1D -0.530 -4.86
LWL2D -1.070 -9.81
LWL3D 0.570 5.23
LWL4D 0.030 0.28
WL3D -1.770 -16.23
WL4D -1.770 -16.23
* CANOPY LOADS GENERATED
-------------------------
LOAD MEM NAME SYS DIR TYP DIST. INTENSITY ECCEN. DESCRIPTION
NO.
1 LC DL GLOB Y C 15.50 -0.118 -1.00 CANOPY LOAD
2 LC LL GLOB Y C 15.50 -0.473 -1.00 CANOPY LOAD
3 LC LS GLOB Y C 15.50 0.000 -1.00 CANOPY LOAD
4 LC RS GLOB Y C 15.50 0.000 -1.00 CANOPY LOAD
5 LC WL1 GLOB Y C 15.50 0.323 -1.00 CANOPY LOAD
6 LC WL1 GLOB X C 15.50 -0.108 0.00 CANOPY LOAD
7 LC WL2 GLOB Y C 15.50 0.323 -1.00 CANOPY LOAD
8 LC WL2 GLOB X C 15.50 -0.108 0.00 CANOPY LOAD
9 LC LWL1 GLOB Y C 15.50 0.255 -1.00 CANOPY LOAD
10 LC LWL1 GLOB X C 15.50 -0.085 0.00 CANOPY LOAD
11 LC LWL2 GLOB Y C 15.50 0.515 -1.00 CANOPY LOAD
12 LC LWL2 GLOB X C 15.50 -0.172 0.00 CANOPY LOAD
13 LC LWL3 GLOB Y C 15.50 -0.275 -1.00 CANOPY LOAD
14 LC LWL3 GLOB X C 15.50 0.092 0.00 CANOPY LOAD
15 LC LWL4 GLOB Y C 15.50 -0.014 -1.00 CANOPY LOAD
16 LC LWL4 GLOB X C 15.50 0.005 0.00 CANOPY LOAD
17 LC MWL1 GLOB Y C 15.50 0.323 -1.00 CANOPY LOAD
18 LC MWL1 GLOB X C 15.50 -0.108 0.00 CANOPY LOAD
19 LC MWL2 GLOB Y C 15.50 0.853 -1.00 CANOPY LOAD
Metallic Building Systems User: mmfarahani Page: F2- 10
R-Frame Design Program - Version V8.15 Job : 31650A
Continued Canopy Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
* CANOPY LOADS GENERATED (continued)
-------------------------
LOAD MEM NAME SYS DIR TYP DIST. INTENSITY ECCEN. DESCRIPTION
NO.
20 LC MWL2 GLOB X C 15.50 -0.284 0.00 CANOPY LOAD
21 LC WL3 GLOB Y C 15.50 0.853 -1.00 CANOPY LOAD
22 LC WL3 GLOB X C 15.50 -0.284 0.00 CANOPY LOAD
23 LC WL4 GLOB Y C 15.50 0.853 -1.00 CANOPY LOAD
24 LC WL4 GLOB X C 15.50 -0.284 0.00 CANOPY LOAD
25 LC WL1D GLOB Y C 15.50 0.145 -1.00 CANOPY LOAD
26 LC WL1D GLOB X C 15.50 -0.048 0.00 CANOPY LOAD
27 LC WL2D GLOB Y C 15.50 0.145 -1.00 CANOPY LOAD
28 LC WL2D GLOB X C 15.50 -0.048 0.00 CANOPY LOAD
29 LC LWL1D GLOB Y C 15.50 0.115 -1.00 CANOPY LOAD
30 LC LWL1D GLOB X C 15.50 -0.038 0.00 CANOPY LOAD
31 LC LWL2D GLOB Y C 15.50 0.232 -1.00 CANOPY LOAD
32 LC LWL2D GLOB X C 15.50 -0.077 0.00 CANOPY LOAD
33 LC LWL3D GLOB Y C 15.50 -0.124 -1.00 CANOPY LOAD
34 LC LWL3D GLOB X C 15.50 0.041 0.00 CANOPY LOAD
35 LC LWL4D GLOB Y C 15.50 -0.007 -1.00 CANOPY LOAD
36 LC LWL4D GLOB X C 15.50 0.002 0.00 CANOPY LOAD
37 LC WL3D GLOB Y C 15.50 0.384 -1.00 CANOPY LOAD
38 LC WL3D GLOB X C 15.50 -0.128 0.00 CANOPY LOAD
39 LC WL4D GLOB Y C 15.50 0.384 -1.00 CANOPY LOAD
40 LC WL4D GLOB X C 15.50 -0.128 0.00 CANOPY LOAD
Metallic Building Systems User: mmfarahani Page: F2- 11
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
* GENERAL LOAD CARDS GENERATED -
--------------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
1 LC DL GLOB Y C 15.504 -0.1180 N/A -1.000
2 LC LL GLOB Y C 15.504 -0.4730 N/A -1.000
3 LC LS GLOB Y C 15.504 0.0000 N/A -1.000
4 LC RS GLOB Y C 15.504 0.0000 N/A -1.000
5 LC WL1 GLOB Y C 15.504 0.3230 N/A -1.000
6 LC WL1 GLOB X C 15.504 -0.1080 N/A 0.000
7 LC WL2 GLOB Y C 15.504 0.3230 N/A -1.000
8 LC WL2 GLOB X C 15.504 -0.1080 N/A 0.000
9 LC LWL1 GLOB Y C 15.504 0.2550 N/A -1.000
10 LC LWL1 GLOB X C 15.504 -0.0850 N/A 0.000
11 LC LWL2 GLOB Y C 15.504 0.5150 N/A -1.000
12 LC LWL2 GLOB X C 15.504 -0.1720 N/A 0.000
13 LC LWL3 GLOB Y C 15.504 -0.2750 N/A -1.000
14 LC LWL3 GLOB X C 15.504 0.0920 N/A 0.000
15 LC LWL4 GLOB Y C 15.504 -0.0140 N/A -1.000
16 LC LWL4 GLOB X C 15.504 0.0050 N/A 0.000
17 LC MWL1 GLOB Y C 15.504 0.3230 N/A -1.000
18 LC MWL1 GLOB X C 15.504 -0.1080 N/A 0.000
19 LC MWL2 GLOB Y C 15.504 0.8530 N/A -1.000
20 LC MWL2 GLOB X C 15.504 -0.2840 N/A 0.000
21 LC WL3 GLOB Y C 15.504 0.8530 N/A -1.000
22 LC WL3 GLOB X C 15.504 -0.2840 N/A 0.000
23 LC WL4 GLOB Y C 15.504 0.8530 N/A -1.000
24 LC WL4 GLOB X C 15.504 -0.2840 N/A 0.000
25 LC WL1D GLOB Y C 15.504 0.1450 N/A -1.000
26 LC WL1D GLOB X C 15.504 -0.0480 N/A 0.000
27 LC WL2D GLOB Y C 15.504 0.1450 N/A -1.000
28 LC WL2D GLOB X C 15.504 -0.0480 N/A 0.000
29 LC LWL1D GLOB Y C 15.504 0.1150 N/A -1.000
30 LC LWL1D GLOB X C 15.504 -0.0380 N/A 0.000
31 LC LWL2D GLOB Y C 15.504 0.2320 N/A -1.000
32 LC LWL2D GLOB X C 15.504 -0.0770 N/A 0.000
33 LC LWL3D GLOB Y C 15.504 -0.1240 N/A -1.000
34 LC LWL3D GLOB X C 15.504 0.0410 N/A 0.000
35 LC LWL4D GLOB Y C 15.504 -0.0070 N/A -1.000
36 LC LWL4D GLOB X C 15.504 0.0020 N/A 0.000
37 LC WL3D GLOB Y C 15.504 0.3840 N/A -1.000
38 LC WL3D GLOB X C 15.504 -0.1280 N/A 0.000
39 LC WL4D GLOB Y C 15.504 0.3840 N/A -1.000
40 LC WL4D GLOB X C 15.504 -0.1280 N/A 0.000
41 LR DL XREF Y U 0.000 -0.0323 N/A 0.000
42 LC SW GLOB Y U 0.000 -0.0221 N/A 0.000
43 LR SW GLOB Y U 0.000 -0.0099 N/A 0.000
44 LR LL XREF Y U 0.000 -0.2433 N/A 0.000
45 LR COLL XREF Y U 0.000 -0.0122 N/A 0.000
46 LC WL1 MEMB Y U 0.000 0.2421 N/A 0.000
47 LR WL1 MEMB Y U 0.000 0.3021 N/A 0.000
48 LC WL2 MEMB Y U 0.000 0.0145 N/A 0.000
49 LR WL2 MEMB Y U 0.000 0.0297 N/A 0.000
50 LC LWL1 MEMB Y U 0.000 0.2131 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F2- 12
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
51 LR LWL1 MEMB Y U 0.000 0.2674 N/A 0.000
52 LC LWL2 MEMB Y U 0.000 0.2131 N/A 0.000
53 LR LWL2 MEMB Y U 0.000 0.4012 N/A 0.000
54 LC LWL3 MEMB Y U 0.000 -0.0145 N/A 0.000
55 LR LWL3 MEMB Y U 0.000 -0.0050 N/A 0.000
56 LC LWL4 MEMB Y U 0.000 -0.0145 N/A 0.000
57 LR LWL4 MEMB Y U 0.000 0.1288 N/A 0.000
58 LC MWL1 MEMB Y U 0.000 0.0813 N/A 0.000
59 LR MWL1 GLOB X U 0.000 -0.0308 N/A 12.649
60 LC MWL2 MEMB Y U 0.000 -0.0813 N/A 0.000
61 LR MWL2 GLOB X U 0.000 0.0308 N/A 12.649
62 LC WL3 MEMB Y U 0.000 -0.0476 N/A 0.000
63 LR WL3 MEMB Y U 0.000 0.4012 N/A 0.000
64 LC WL4 MEMB Y U 0.000 -0.2752 N/A 0.000
65 LR WL4 MEMB Y U 0.000 0.1288 N/A 0.000
66 LC WL1D MEMB Y U 0.000 0.1091 N/A 0.000
67 LR WL1D MEMB Y U 0.000 0.1361 N/A 0.000
68 LC WL2D MEMB Y U 0.000 0.0065 N/A 0.000
69 LR WL2D MEMB Y U 0.000 0.0134 N/A 0.000
70 LC LWL1D MEMB Y U 0.000 0.0960 N/A 0.000
71 LR LWL1D MEMB Y U 0.000 0.1205 N/A 0.000
72 LC LWL2D MEMB Y U 0.000 0.0960 N/A 0.000
73 LR LWL2D MEMB Y U 0.000 0.1807 N/A 0.000
74 LC LWL3D MEMB Y U 0.000 -0.0065 N/A 0.000
75 LR LWL3D MEMB Y U 0.000 -0.0022 N/A 0.000
76 LC LWL4D MEMB Y U 0.000 -0.0065 N/A 0.000
77 LR LWL4D MEMB Y U 0.000 0.0580 N/A 0.000
78 LC WL3D MEMB Y U 0.000 -0.0214 N/A 0.000
79 LR WL3D MEMB Y U 0.000 0.1807 N/A 0.000
80 LC WL4D MEMB Y U 0.000 -0.1240 N/A 0.000
81 LR WL4D MEMB Y U 0.000 0.0580 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F2- 13
R-Frame Design Program - Version V8.15 Job : 31650A
Seismic Summary Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Seismic Force Resisting System Per :
ASCE 7 Standard
2016 Edition
Standard Risk Category Building for Seismic Loadings
Seismic Loads Required for Building ................................ Yes
Response Acceleration Coeff., for Short Periods [Ss] (%g) .......... 118.3000
Response Acceleration Coeff., for 1 sec. Periods [S1] (%g) ......... 42.5000
Long-period Transition Period Time [TL] (seconds) .................. 16.0000
Seismic Design Category ............................................ D
Soil Profile Type .................................................. D
Seismic Site Coefficient [Fa] ...................................... 1.2000
Seismic Site Coefficient [Fv] ...................................... 1.8750
Maximum Spectral Response Accel., for Short Periods [Sms] (g) ...... 1.4196
Maximum Spectral Response Accel., for 1 sec. Periods [Sm1] (g) ..... 0.7969
Design Spectral Response Accel., for Short Periods [Sds] (g) ....... 0.9464
Design Spectral Response Accel., for 1 sec. Periods [Sd1] (g) ...... 0.5312
Sds and Sd1 values .......................................... Code-calculated
Seismic Response Modification Factor [R] ........................... 3.5000
Seismic Importance Factor [I] ...................................... 1.0000
Storage/Equipment Areas and/or Service Rooms Exist ................. No
Seismic Story Height [hn] (feet) ................................... 18.0000
Seismic Fundamental Period [T] Used (seconds) ...................... 0.2827
Seismic Overstrength Factor [OMEGAo] ............................... 2.5000
Longitudinal Seismic Redundancy/Reliability Factor [L-rho] ......... 1.3000
Seismic Redundancy/Reliability Factor [rho] ........................ 1.5000
Snow in Seismic Force Calculations [Used] (%) ...................... 0.00
Snow in Seismic Force Calculations [Min. Required] (%) ............. 0.00
Snow in Seismic Load Combinations [Used] (%) ....................... 0.00
Snow in Seismic Load Combinations [Min. Required] (%) .............. 0.00
Mezz. Live load in Seismic Force Calculations [Used] (%) ........... 0.00
Mezz. Live load in Seismic Force Calculations [Min. Required] (%) .. 0.00
Mezz. Live load in Seismic Load Combinations [Used] (%) ............ 100.00
Mezz. Live load in Seismic Load Combinations [Min. Required] (%) ... 100.00
Building Height Limit (feet) ....................................... 65.0000
Seismic Story Drift Limit Factor ................................... 0.0250
Seismic Story Drift Limit (in) ..................................... 6.0000
Seismic Deflection Amplification Factor [Cd] ....................... 3.0000
Seismic Response Coefficient [Cs] Used ............................. 0.2704
Seismic Story Drift [Cd*Drift/Importance Factor] (in) .............. 0.001
Theta [Px*Ie*Delta/Vx/hx/Cd]........................................ 0.000
Theta Max [.5/BETA/Cd] where BETA=1.0............................... 0.167
Roof Dead Load = 0.798
Wall Weight = 0.000
Collateral Load = 0.083
Snow Load = 0.000
Rafter Crane Weight = 0.000
-------------------------------------
Total Roof Weight = 0.881 kips
Total Roof Weight = 0.881
Mezzanine Weight = 0.000
Col. Crane Weight = 0.000
-------------------------------------
TOTAL Bldg Weight = 0.881 kips
X X
Seismic Coeff. = 0.2704
-------------------------------------
BASE SHEAR = 0.2383 kips
Seismic Load for Roof at col # 1 = 0.2383 kips
Seismic Load for Roof at col # 2 = 0.0000 kips
---------------------------------------------------
SEISMIC LOAD for Roof in TOTAL = 0.2383 kips
* SEISMIC GENERAL LOAD CARDS GENERATED
--------------------------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
82 LC EQ YREF X C 15.300 0.2383 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F2- 14
R-Frame Design Program - Version V8.15 Job : 31650A
Forces and Allowable Stresses Summary File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Left Column Analysis Length = 15.30 ft Kx = 1.00 Weight = 338. lbs
Part Length Mem Depths at Member Description Web Fy
No. (ft) Start(in) End(in) Thickness (ksi)
1 10.00 10.200 10.200 W10X22 0.2400 in 50.0
2 5.09 10.200 10.200 W10X22 0.2400 in 50.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
105 0.1 4.5 0.1 29.9 20.0 33.6 20.0 0.00 0.12 0.07 0.12 23
201 -1.7 3.2 -0.3 7.6 19.7 33.6 20.0 0.01 0.10 0.07 0.10 49
--------------------------------------------------------------------------------
Left Rafter Analysis Length = 11.03 ft Kx = 1.00 Weight = 111. lbs
Part Length Mem Depths at Member Description Web Fy
No. (ft) Start(in) End(in) Thickness (ksi)
3 11.24 7.890 7.890 W8X10 0.1700 in 50.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
308 0.0 4.1 0.1 32.5 33.5 26.6 20.0 0.00 0.19 0.23 0.23 1
--------------------------------------------------------------------------------
TOTAL MEMBER WEIGHT = 449. lbs
Metallic Building Systems User: mmfarahani Page: F2- 15
R-Frame Design Program - Version V8.15 Job : 31650A
Anchor Rod and Base Plate Design File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
LEFT EXTERIOR COLUMN ANCHOR RODS AND BASE PLATE DESIGN
======================================================
Anchor Rod & Base Plate Design Sizes >>
---------------------------------------
Use ( 4)- 0.750 in. Dia. F1554, Gr. 36 Anchor Rods
Rod Gage : 4.000 in. Rod Spacing (in.): 3.0000, 1 @ 4.0000, 3.2000
Plate Size : 6.0000 x 10.2000 x 0.3750 in. (Width x Depth x Thickness)
Controlling Reactions for Anchor Rod Design >>
----------------------------------------------
Shear Tension Allowable Load Check
Loading Type (kips) (kips) (kips) No. Ratio
-----------------------------------------------------------------
Rod Tension 0.000 2.069 38.436 27 0.05
Rod Shear 1.219 0.000 23.061 23 0.05
Standard Base Plate Welding >> (Using E70 Electrodes)
------------------------------
Fillet Weld Weld Weld Design Weld
Weld Size Length Capacity Force Load Check
Location (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------
Inner Flg 0.31250 5.750 26.682 0.668 27 0.03
Outer Flg 0.31250 5.750 26.682 0.668 27 0.03
Web Plate 0.18750 9.480 26.395 1.242 24 0.05
Metallic Building Systems User: mmfarahani Page: F2- 16
R-Frame Design Program - Version V8.15 Job : 31650A
Leanto Boss Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
BOSS DESIGN
SEGMENT STARTING ENDING WEB OUTER FLANGE INNER FLANGE
SEG LENGTH WEB DEPTH WEB DEPTH THICKNESS WIDTH THICKNESS WIDTH THICKNESS
NUM (FEET) (INCHES) (INCHES) (INCHES) (IN.) (IN.) (IN.) (IN.)
--- ------ --------- --------- --------- --------------- ---------------
1 0.725 10.2300 7.4800 0.1340 5.00 x 0.2500 5.00 x 0.2500
FY= 55.00 KSI FU= 70.00 KSI LENGTH= 8.70 INCHES WEIGHT= 9.1 LBS.
Metallic Building Systems User: mmfarahani Page: F2- 17
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Vertical Knee Connection @ Left Rafter Depth 1
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 1 row P. Depth - 1/2 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 5.75 x 0.3600 in. Plate: 5.00 x 0.2500 in.
Fy(Min) 55.0 ksi Fy(Min) 55.0 ksi
Fu 70.0 ksi Fu 70.0 ksi
Flanges:
O.S. - 3.94 x 0.2050 in.
I.S. - 3.94 x 0.2050 in.
Web Depth - 7.885 in.
Web Thickness 0.170 in.
Gage - 2.500 in.
Center of Bolt to Flange:
Pf top (ins) - 2.055 in.
BFCD top (ins) - 1.500 in.
Rise top (ins) - 0.302 in.
XTI top (ins) - 1.971 in.
Bolt Spacing - 2.500 in.
Angle top -108.4 degrees
Angle bot - 71.6 degrees
Plate Length - 3.953 in.
Left Side Conn Right Side Conn
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
16) DL +0.6WL1 0.00 1.37 -1.29 0.00 1.37 -1.29
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.1597 Plate Unity Check (O.S.) = 0.3620
Weld Unity Check = 0.1752
Metallic Building Systems User: mmfarahani Page: F2- 18
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Peak Connection @ Left Rafter Depth 2
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 1 row P. Depth - 1/2 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 5.00 x 0.2500 in. Plate: 5.00 x 0.2500 in.
Fy(Min) 55.0 ksi Fy(Min) 55.0 ksi
Fu 70.0 ksi Fu 70.0 ksi
Flanges: Flanges:
O.S. - 3.94 x 0.2050 in. O.S. - 5.00 x 0.2500 in.
I.S. - 3.94 x 0.2050 in. I.S. - 5.00 x 0.2500 in.
Web Depth - 7.885 in. Web Depth - 7.885 in.
Web Thickness 0.170 in. Web Thickness 0.170 in.
Gage - 2.500 in. Gage - 2.500 in.
Center of Bolt to Flange: Center of Bolt to Flange:
Pf top (ins) - 1.841 in. Pf top (ins) - 2.007 in.
BFCD top (ins) - 1.500 in. BFCD top (ins) - 1.500 in.
Rise top (ins) - 0.302 in. Rise top (ins) - 0.302 in.
XTI top (ins) - 1.924 in. XTI top (ins) - 1.924 in.
Bolt Spacing - 2.500 in. Bolt Spacing - 2.500 in.
Angle top - 71.6 degrees Angle top -108.4 degrees
Angle bot -108.4 degrees Angle bot - 90.0 degrees
Plate Length - 3.953 in. Plate Length - 3.953 in.
Left Side Conn Right Side Conn
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
19) DL +0.6LWL2 -0.00 2.13 0.47
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.1486 Plate Unity Check (O.S.) = 0.5614
Weld Unity Check = 0.1772
Required Connection Plate Welding >> (Using E70 Electrodes)
------------------------------------
Welded Weld Weld Weld Design Weld
Joint Size Length Capacity Force Load Check
Weld Location Type (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------------------
Left Side of Conn
Inner Flg Fillet-BS 0.1875 7.8800 32.9096 0.5812 19 0.0177
Outer Flg Fillet-BS 0.1875 7.8800 32.9096 0.5812 19 0.0177
Web Plate Fillet-BS 0.1875 15.7692 43.9052 1.5755 1 0.0359
------------------------------------------------------------------------------
NS - Near side weld, FS - Far side weld, BS - Both sides weld.
Metallic Building Systems User: mmfarahani Page: F2- 19
R-Frame Design Program - Version V8.15 Job : 31650A
Knee and Stiffener Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Left Knee Design
================
Knee Web Thickness : Use 0.2400 in. Thick Web
Column Cap Plate : 6.0000 X 0.2500 in.
Metallic Building Systems User: mmfarahani Page: F2- 20
R-Frame Design Program - Version V8.15 Job : 31650A
Flange Brace Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
Girt Spaces - Vertical Measurements
Left Column Right Column
1 @ 16'0 @ FLOOR
Purlin Spaces - Horizontal Measurements
Left Rafter Right Rafter
2 @ 3'0 @ EAVE
1 @ 4'0
1 @ 2'0 @ PEAK
--------------------------------------------------------------------------------
Member Distance to Brace Points (feet)
- Left Rafter : Measured along T.F. from left steel line
- Right Rafter : Measured along T.F. from right steel line
- Ext. Columns : Measured along T.F. from base
--------------------------------------------------------------------------------
LFT RAFTER 3.16 6.32 10.54
($) (N) ($)
--------------------------------------------------------------------------------
"N" Indicates that No flange braces are located at the brace point
"$" Indicates that point is braced by a girt
--------------------------------------------------------------------------------
Metallic Building Systems User: mmfarahani Page: F2- 21
R-Frame Design Program - Version V8.15 Job : 31650A
Primary Deflection Report File: ltfrar_1(s).fra Date: 9/22/21
lt 12./16./12.167 20./100./0. Start Time: 18:21:06
--------------------------------------------------------------------------------
COLUMN TOP DEFLECTIONS for LOAD COMBS. (Positive = X: Right Y:Upward) (Inches)
==============================================================================
Ext. Left Col Ext Right Col
X-Def Y-Def X-Def Y-Def
------------------------------------------------------------------------------
Neg. Max -0.003 -0.003
Load Comb 56 1
Defl. H/999
==============================================================================
MAX RAFTER DEFLECTIONS for SPAN #1. (Positive = Y:Upw ard)
==============================================================================
Max. Downward Deflection Max. Upward Deflection
Y-Def. X-Dist. from Left S.L. Y-Def. X-Dist. from Left S.L.
------------------------------------------------------------------------------
Max. Def -0.095 in. 6.35 ft. 0.064 in. 6.35 ft.
Load Comb 1 59
Defl. L/999 L/999
==============================================================================
Vertical Clearance at the Left Knee is 15.1017 feet
Vertical Clearance at the Right Knee is 18.0628 feet
Metallic Building Systems User: mmfarahani Page: F1- 1
R-Frame Design Program - Version V8.15 Job : 31650A
Input Data Echo File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
\\hounas04\TS\Jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\
--------------------------------------------------------------------------------
VERSION V8.15
BRAND METALLIC
DESCRIPTION lt 12./16./20. 20./100./0.
FRAME_ID 1
# FRAME LEFT SIDE IS BLDG. PLANE SWA
# AND FRAME RIGHT SIDE IS BLDG. PLANE
PRINT echo code loads base connection deflection boss profile seismic detail \
flg_brace summary stiffeners pro_grplds
OPTIMIZATION none *PLANT atw *JOB 31650A
ANALYZE all *DATASET members brace combinations wind_array connection base
BUILDING LABEL B
LOCATION frame lines 2-4
LATERAL GRID LABEL 4 3 2
LONGITUDINAL GRID LABEL A B
NUMBER FRAMES 3 *PRICE summary
TYPE lt p cs 60. 60. right
MAIN GEOMETRY
WIDTH 50. 25.
LENGTH 60.
EAVE 20. *ROOF SLOPE 4.
LEANTO RIGHT GEOMETRY
WIDTH 12. 0.
LENGTH 60.
EAVE 16. *ROOF SLOPE 4.
BOSS 8.25
GIRT DEPTH 8. 8.25 *PURLIN DEPTH 8. 8.25
GIRT THICKNESS 0.059 *PURLIN THICKNESS 0.059
GIRT FLANGE 2.5 *PURLIN FLANGE 2.5
PURLIN STIFFNESS 7.857 12.59 2.788 6.484
CODE LABEL 2019 CALIFORNIA BUILDING CODE
BUILDING CODE IB18 U=Normal
DEAD LOAD 2.653 *COLLATERAL LOAD 1.
LIVE LOAD 20. reduce
SNOW R=0. E=0.9 T=1.2 S=N WEL=27. WER=39. WML=25. WMR=37.
SEISMIC LOAD S1=42.5 SS=118.3 TL=16. %CR=NORM %SR=NORM RHOT=1.5 RHOL=1.3 \
R=3.5 LOF=2. TOF=2.5 RL=3.25 Cd=3. Ct=0.028
SOIL PROFILE D
SECOND ORDER FOA
##ROOF TRIBUTARY TR=20.
##WALL TRIBUTARY LEFT TR= 20. S=0. E=16.
##WALL TRIBUTARY RIGHT TR= 22. S=0. E=20.
###Adding 5% More Trib.
ROOF TRIBUTARY TR=21.
WALL TRIBUTARY LEFT TR= 21. S=0. E=16.
WALL TRIBUTARY RIGHT TR= 23.1 S=0. E=20.
####
DESIGN ASD16
LATERAL BRACE LENGTH 20.00
STIFFNESS CHECK SNOW ONLY
BOLT TIGHTENING Fully
NOFB 0.
DEFLECTION ROOF L=180. S=180. W=180. G=120.
DEFLECTION WALL L=60. S=60. W=60. E=50. C=100. G=60. TE=50.
MIN_MOMT_BOLT_DIA 0.5
CANOPYL CFT=C FL=Y PR=2. LEN=64. HT=16. CS=4. PD=8. FT=0.205 WH=7.48 MN=5. \
0.178 BAY=19.833 DL=4.508 LL=20. WL1=-9.5661 -0.47 WL2=-9.5661 -0.47 \
LWL1=-7.5307 -0.37 LWL2=-14.0438 -0.69 LWL3=14.8579 0.73 LWL4=8.3449 0.41 \
MWL1=-9.5661 -0.47 MWL2=-28.2911 -1.39 WL3=-28.2911 -1.39 WL4=-28.2911 -1.39 \
WL1D=-4.3088 -0.47 WL2D=-4.3088 -0.47 LWL1D=-3.3921 -0.37 LWL2D=-6.3257 -0.69 \
LWL3D=6.6925 0.73 LWL4D=3.7588 0.41 WL3D=-12.7432 -1.39 WL4D=-12.7432 -1.39
SPLICE GUSSETS NA
BRACING SIDES LC=3 RA=1 RC=1
BRACE ATTACHMENT FLANGE
FLANGE BRACE ATTACHMENT LC=0 RA=0
GIRT SPACING
GIRT BRACE
PURLIN SPACING 2@3. 4.
PURLIN BRACE C N C
LEFT COLUMN
BASE W=6. T=0.375 L=10.2 N=2 D=0.75
W10X22 10.
W10X22 0.
LEFT RAFTER
CONNECTION O=2P W=5.75 5. T=0.36 0.25 D=0.5
W10X12 0.
CONNECTION O=2P W=5. T=0.25 D=0.5
WIND LOAD WL1 20.353 -0.9700 -1.0200 -1.2400 -0.0300 12.000 Left
WIND LOAD WL2 20.353 0.1300 0.0800 -0.1400 1.0700 12.000 Left
WIND LOAD LWL1 20.353 -1.0000 -0.9200 -1.2400 -1.0000 12.000
WIND LOAD LWL2 20.353 -1.0000 -1.2400 -0.9200 -1.0000 12.000
WIND LOAD LWL3 20.353 0.1000 0.1800 -0.1400 0.1000 12.000
WIND LOAD LWL4 20.353 0.1000 -0.1400 0.1800 0.1000 12.000
WIND LOAD MWL1 16.000 -0.5000 0.5000 0.5000 0.5000 0.000
WIND LOAD MWL2 16.000 0.5000 -0.5000 -0.5000 -0.5000 0.000
WIND LOAD WL3 20.353 -0.0300 -1.2400 -1.0200 -0.9700 12.000 Right
WIND LOAD WL4 20.353 1.0700 -0.1400 0.0800 0.1300 12.000 Right
WIND LOAD WL1D 9.168 -0.9700 -1.0200 -1.2400 -0.0300 12.000 Left
WIND LOAD WL2D 9.168 0.1300 0.0800 -0.1400 1.0700 12.000 Left
WIND LOAD LWL1D 9.168 -1.0000 -0.9200 -1.2400 -1.0000 12.000
WIND LOAD LWL2D 9.168 -1.0000 -1.2400 -0.9200 -1.0000 12.000
WIND LOAD LWL3D 9.168 0.1000 0.1800 -0.1400 0.1000 12.000
WIND LOAD LWL4D 9.168 0.1000 -0.1400 0.1800 0.1000 12.000
WIND LOAD WL3D 9.168 -0.0300 -1.2400 -1.0200 -0.9700 12.000 Right
WIND LOAD WL4D 9.168 1.0700 -0.1400 0.0800 0.1300 12.000 Right
LOAD COMBINATIONS
1)1. DL 1. COLL *DEFL 60. 120.
2)1. DL 1. COLL 1. PLLR1 *DEFL 60. 120.
3)1. DL 1. LL 1. COLL *DEFL 60. 120.
4)1.1325 DL 1.05 EQ *DEFL 50. 120.
5)1.1325 DL -1.05 EQ *DEFL 50. 120.
6)1.1325 DL 1.1325 COLL 1.05 EQ *DEFL 50. 120.
7)1.1325 DL 1.1325 COLL -1.05 EQ *DEFL 50. 120.
8)0.4675 DL 1.05 EQ *DEFL 50. 120.
9)0.4675 DL -1.05 EQ *DEFL 50. 120.
10)0.71072 DL 2.5 EQ *TYPE R *APP C
11)0.71072 DL -2.5 EQ *TYPE R *APP C
12)1.38928 DL 1.38928 COLL 2.5 EQ *TYPE R *APP C
13)1.38928 DL 1.38928 COLL -2.5 EQ *TYPE R *APP C
14)0.71072 DL 2.5 EQ *TYPE R *APP B
15)0.71072 DL -2.5 EQ *TYPE R *APP B
16)1.38928 DL 1.38928 COLL 2.5 EQ *TYPE R *APP B
17)1.38928 DL 1.38928 COLL -2.5 EQ *TYPE R *APP B
18)1. DL 0.6 WL1
19)1. DL 0.6 WL2
20)1. DL 0.6 LWL1
21)1. DL 0.6 LWL2
22)1. DL 0.6 LWL3
23)1. DL 0.6 LWL4
24)1. DL 0.6 WL3
25)1. DL 0.6 WL4
26)0.6 DL 0.6 WL1
27)0.6 DL 0.6 WL2
28)0.6 DL 0.6 LWL1
29)0.6 DL 0.6 LWL2
30)0.6 DL 0.6 LWL3
31)0.6 DL 0.6 LWL4
32)0.6 DL 0.6 WL3
33)0.6 DL 0.6 WL4
34)0.6 MWL1 *TYPE M
35)0.6 MWL2 *TYPE M
36)1. DL 1. COLL 0.6 WL1
37)1. DL 1. COLL 0.6 WL2
38)1. DL 1. COLL 0.6 LWL1
39)1. DL 1. COLL 0.6 LWL2
40)1. DL 1. COLL 0.6 LWL3
41)1. DL 1. COLL 0.6 LWL4
42)1. DL 1. COLL 0.6 WL3
43)1. DL 1. COLL 0.6 WL4
44)1. DL 0.75 LL 1. COLL 0.45 WL1
45)1. DL 0.75 LL 1. COLL 0.45 WL2
46)1. DL 0.75 LL 1. COLL 0.45 LWL1
47)1. DL 0.75 LL 1. COLL 0.45 LWL2
48)1. DL 0.75 LL 1. COLL 0.45 LWL3
49)1. DL 0.75 LL 1. COLL 0.45 LWL4
50)1. DL 0.75 LL 1. COLL 0.45 WL3
51)1. DL 0.75 LL 1. COLL 0.45 WL4
52)1. DL 1. COLL 1. RS
53)1. DL 1. COLL 1. LS
54)1. LL *DEFL 60. 180. *TYPE D
55)1. WL1D *DEFL 60. 180. *TYPE D
56)1. WL2D *DEFL 60. 180. *TYPE D
57)1. LWL1D *DEFL 60. 180. *TYPE D
58)1. LWL2D *DEFL 60. 180. *TYPE D
59)1. LWL3D *DEFL 60. 180. *TYPE D
60)1. LWL4D *DEFL 60. 180. *TYPE D
61)1. WL3D *DEFL 60. 180. *TYPE D
62)1. WL4D *DEFL 60. 180. *TYPE D
63)1.38928 DL 1. EQ *DEFL 50. 0. *TYPE D *EQCD 3.0
64)1.38928 DL -1. EQ *DEFL 50. 0. *TYPE D *EQCD 3.0
65)0.71072 DL 1. EQ *DEFL 50. 0. *TYPE D *EQCD 3.0
66)0.71072 DL -1. EQ *DEFL 50. 0. *TYPE D *EQCD 3.0
67)1.38928 DL 1.38928 COLL 1. EQ *DEFL 50. 0. *TYPE D *EQCD 3.0
68)1.38928 DL 1.38928 COLL -1. EQ *DEFL 50. 0. *TYPE D *EQCD 3.0
END
Metallic Building Systems User: mmfarahani Page: F1- 2
R-Frame Design Program - Version V8.15 Job : 31650A
Building Grid label legend File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Building Grid Label Legend
==========================
Building : B
Frame Number : 1
No. of Frames : 3
Left Column : Column @ * - A
Right Support : Support @ * - B
*Frames located @ 4 3 2
Metallic Building Systems User: mmfarahani Page: F1- 3
R-Frame Design Program - Version V8.15 Job : 31650A
Code Summary Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Building :B
Frame Number :1 Location: frame lines 2-4
No. of Frames: 3
2019 CALIFORNIA BUILDING CODE
Main Code Requirements Per :
International Building Code
2018 Edition
Supporting Design Manual(s):
2016 AISC Specification for Structural Steel Buildings,Allowable Strength Design
2010 AISC Seismic Provisions for Structural Steel Buildings
Frame Data
----------
Eave height Left (feet)............................................. 16.000
Horizontal width from left to right steel line (feet)............... 12.000
Horizontal distance to ridge from left side (feet).................. 12.000
Roof Slope Left (rise:12)........................................... 4.000
Column Slope Left & Right (lat:12).................................. 0.000
Purlin depth left & right side (inches)............................. 8.000
Frame Rafter Inset left & right side (inches)....................... 8.250
Girt depth left & right side (inches)............................... 8.000
Frame Column Inset left & right side (inches)....................... 8.250
Tributary Width left side (feet).................................... 21.000
..................................from Height 0.00 to Height 16.00
Tributary Width roof (feet)......................................... 21.000
Tension Flange Bolt Hole Reduction.................................. Yes
Tension Field Action at Knee........................................ Yes
Second order analysis method........................................ C2.2b
Frame Design Loads
------------------
Dead Load to Frame Rafter (psf)..................................... 2.653
Frame Rafter Dead Weight (psf)...................................... 0.560
Total Roof Dead Weight (psf)........................................ 3.213
Collateral Load to Frame Rafter (psf)............................... 1.000
Roof Live Load Entered (psf) W/ Live Load Reduction Requested....... 20.000
Design Roof Live Load Used (psf).................................... 19.000
Roof Snow Load Entered (psf)........................................ 0.000
Snow Exposure Factor Entered [Ce] .................................. 0.900
Snow Importance Factor [I] -- Standard Use Category................. 1.000
Snow Thermal Factor Entered [Ct] -- User Entered.................... 1.200
Snow Thermal Factor Used [Ct]Unheated Building...................... 1.200
Slippery & Unobstructed Roof Surface................................ No
Roof Snow Load [Pf = 0.7*Ce*Ct*I*Pg] (psf).......................... 0.000
Snow Slope Factor [Cs].............................................. 1.000
Sloped Roof Snow Load Used [Ps = Cs*Pf] (psf)....................... 0.000
PATTERN LIVE LOADING(s)
-----------------------
1) Any two adjacent spans loaded with 100% of the roof load & all the
remaining spans loaded with 0% (min. of 3 spans).
100% 100% 0%
================
^ ^ ^ ^
2) Alternate spans loaded with 100% of the roof load & all the remaining
spans loaded with 0% (min. of 2 spans).
100% 0% 100% 0% 100%
==========================
^ ^ ^ ^ ^ ^
Metallic Building Systems User: mmfarahani Page: F1- 4
R-Frame Design Program - Version V8.15 Job : 31650A
Wind Summary Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
Eave height Left (feet)............................................. 16.000
Wind Elevation on left column (feet)................................ 20.000
Wind Elevation on right column (feet)............................... 20.000
Total frame width (feet)............................................ 12.000
Total building length (feet)........................................ 60.000
Number of primary wind loadings .................................... 18
Metallic Building Systems User: mmfarahani Page: F1- 5
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Wind Summary Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
*** PRIMARY WIND COEFFICIENTS FOR LEAN-TO FRAME ***
--------------------------------------------------------------------------------
Wind Load WL1 Wind from left direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.970 -1.020(100.0%) -1.240( 0.0%) -0.030
--------------------------------------------------------------------------------
Wind Load WL2 Wind from left direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.130 0.080(100.0%) -0.140( 0.0%) 1.070
--------------------------------------------------------------------------------
Wind Load LWL1 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -1.000 -0.920(100.0%) -1.240( 0.0%) -1.000
--------------------------------------------------------------------------------
Wind Load LWL2 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -1.000 -1.240(100.0%) -0.920( 0.0%) -1.000
--------------------------------------------------------------------------------
Wind Load LWL3 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.100 0.180(100.0%) -0.140( 0.0%) 0.100
--------------------------------------------------------------------------------
Wind Load LWL4 Longitudinal wind
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.100 -0.140(100.0%) 0.180( 0.0%) 0.100
--------------------------------------------------------------------------------
Wind Load MWL1 Min. Wind from left dir.
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.500 0.500 0.500 0.500
--------------------------------------------------------------------------------
Wind Load MWL2 Min. Wind from right dir.
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.500 -0.500 -0.500 -0.500
--------------------------------------------------------------------------------
Wind Load WL3 Wind from right direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) -0.030 -1.240(100.0%) -1.020( 0.0%) -0.970
--------------------------------------------------------------------------------
Wind Load WL4 Wind from right direction
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 1.070 -0.140(100.0%) 0.080( 0.0%) 0.130
--------------------------------------------------------------------------------
Notes :
1. Wind coefficients applied to the roof may be located as a percentage
of the total frame width (xx.x%). If not shown the coefficients are
applied fully to their respective rafter.
Metallic Building Systems User: mmfarahani Page: F1- 6
R-Frame Design Program - Version V8.15 Job : 31650A
Load Combinations Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Load Combination :
------------------
1) DL +COLL N A
2) DL +COLL +PLLR1 N A
3) DL +LL +COLL N A
4) 1.1325DL +1.05EQ N A
5) 1.1325DL -1.05EQ N A
6) 1.1325DL +1.1325COLL +1.05EQ N A
7) 1.1325DL +1.1325COLL -1.05EQ N A
8) 0.4675DL +1.05EQ N A
9) 0.4675DL -1.05EQ N A
10) 0.7107DL +2.5EQ N C R
11) 0.7107DL -2.5EQ N C R
12) 1.3893DL +1.3893COLL +2.5EQ N C R
13) 1.3893DL +1.3893COLL -2.5EQ N C R
14) 0.7107DL +2.5EQ N B R
15) 0.7107DL -2.5EQ N B R
16) 1.3893DL +1.3893COLL +2.5EQ N B R
17) 1.3893DL +1.3893COLL -2.5EQ N B R
18) DL +0.6WL1 N A
19) DL +0.6WL2 N A
20) DL +0.6LWL1 N A
21) DL +0.6LWL2 N A
22) DL +0.6LWL3 N A
23) DL +0.6LWL4 N A
24) DL +0.6WL3 N A
25) DL +0.6WL4 N A
26) 0.6DL +0.6WL1 N A
27) 0.6DL +0.6WL2 N A
28) 0.6DL +0.6LWL1 N A
29) 0.6DL +0.6LWL2 N A
30) 0.6DL +0.6LWL3 N A
31) 0.6DL +0.6LWL4 N A
32) 0.6DL +0.6WL3 N A
33) 0.6DL +0.6WL4 N A
34) 0.6MWL1 N M
35) 0.6MWL2 N M
36) DL +COLL +0.6WL1 N A
37) DL +COLL +0.6WL2 N A
38) DL +COLL +0.6LWL1 N A
39) DL +COLL +0.6LWL2 N A
40) DL +COLL +0.6LWL3 N A
41) DL +COLL +0.6LWL4 N A
42) DL +COLL +0.6WL3 N A
43) DL +COLL +0.6WL4 N A
44) DL +0.75LL +COLL +0.45WL1 N A
45) DL +0.75LL +COLL +0.45WL2 N A
46) DL +0.75LL +COLL +0.45LWL1 N A
47) DL +0.75LL +COLL +0.45LWL2 N A
48) DL +0.75LL +COLL +0.45LWL3 N A
49) DL +0.75LL +COLL +0.45LWL4 N A
50) DL +0.75LL +COLL +0.45WL3 N A
Metallic Building Systems User: mmfarahani Page: F1- 7
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Load Combination :
------------------
51) DL +0.75LL +COLL +0.45WL4 N A
52) DL +COLL +RS N A
53) DL +COLL +LS N A
54) LL D
55) WL1D D
56) WL2D D
57) LWL1D D
58) LWL2D D
59) LWL3D D
60) LWL4D D
61) WL3D D
62) WL4D D
63) 1.3893DL +EQ D E
64) 1.3893DL -EQ D E
65) 0.7107DL +EQ D E
66) 0.7107DL -EQ D E
67) 1.3893DL +1.3893COLL +EQ D E
68) 1.3893DL +1.3893COLL -EQ D E
Metallic Building Systems User: mmfarahani Page: F1- 8
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Where :
-------
DL = Roof Dead Load
COLL = Roof Collateral Load
PLLR1 = Pattern Live Load Right Leanto/Canopy [PLLRxx]
LL = Roof Live Load
EQ = Lateral Seismic Load [parallel to plane of frame]
WL1 = Wind from Left to Right with +GCpi
WL2 = Wind from Left to Right with -GCpi
LWL1 = Windward Corner Left with +GCpi
LWL2 = Windward Corner Right with +GCpi
LWL3 = Windward Corner Left with -GCpi
LWL4 = Windward Corner Right with -GCpi
WL3 = Wind from Right to Left with +GCpi
WL4 = Wind from Right to Left with -GCpi
MWL1 = Minimum Wind Load
MWL2 = Minimum Wind Load
RS = Unbalanced Right Roof Snow Load
LS = Unbalanced Left Roof Snow Load
WL1D = Wind from Left to Right with +GCpi at Service Level
WL2D = Wind from Left to Right with -GCpi at Service Level
LWL1D = Windward Corner Left with +GCpi at Service Level
LWL2D = Windward Corner Right with +GCpi at Service Level
LWL3D = Windward Corner Left with -GCpi at Service Level
LWL4D = Windward Corner Right with -GCpi at Service Level
WL3D = Wind from Right to Left with +GCpi at Service Level
WL4D = Wind from Right to Left with -GCpi at Service Level
Combination Descriptions :
--------------------------
N= No 1/3 Increase in Allowable for Combination
B= Base Only Combination
A= Allowable Strength Design Combination - ASD16
C= Column Only Combination for Seismic
D= Deflection Only Combination
R= Load and Resistance Factor Design Combination - LRFD
E= Cd is applied and Ie is omitted from frame drift calculations
M= Minimum Wind Load Combination. Checked for Allowable Strength not for Deflection
Metallic Building Systems User: mmfarahani Page: F1- 9
R-Frame Design Program - Version V8.15 Job : 31650A
Canopy Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Left Side Canopy Data
---------------------
Canopy #1 : At Eave Canopy w/ Flush purlin
Width (horizontal projection from steel line) (feet)...... 2.0000
Length (used for drifting snow only) (feet)............... 64.0000
Canopy bay size (feet).................................... 19.8330
Roof height at the wall(feet)............................. 16.0000
Roof height at the free end (feet)........................ 15.3333
Roof slope (rise:12)...................................... 4.0000
Purlin depth (inches) .................................... 8.0000
Minimum cap plate width (inches) ......................... 5.0000
Minimum cap plate thickness (inches)...................... 0.1780
Canopy beam flange thickness (inches)..................... 0.2050
Canopy beam vertical web height at the steel line (inches) 7.4800
Connection plate thickness (inches)....................... 0.0000
Canopy Design Loads
-------------------
Snow Thermal Factor [Ct] -- Unheated Canopy 1.2000
Slippery & Unobstructed Canopy Roof Surface No
Canopy Snow Slope Factor [Cs] 1.0000
Total Canopy Dead Load (psf).............................. 4.5080
Canopy Collateral Load (psf).............................. 0.0000
Canopy Live Load Entered (psf)............................ 20.0000
Canopy Live Load Used (psf)............................... 20.0000
Design Snow Load Used (psf)............................... 0.0000
Unbalanced Snow Load Used (psf)........................... 0.0000
Canopy wind elevation (feet).............................. 19.6667
Number of wind arrays .................................... 18
Canopy wind coefficients and design loads
-----------------------------------------
Wind Wind Coeff. Design Load
Array (psf)
WL1 -0.470 -9.57
WL2 -0.470 -9.57
LWL1 -0.370 -7.53
LWL2 -0.690 -14.04
LWL3 0.730 14.86
LWL4 0.410 8.34
MWL1 -0.470 -9.57
MWL2 -1.390 -28.29
WL3 -1.390 -28.29
WL4 -1.390 -28.29
WL1D -0.470 -4.31
WL2D -0.470 -4.31
LWL1D -0.370 -3.39
LWL2D -0.690 -6.33
LWL3D 0.730 6.69
LWL4D 0.410 3.76
WL3D -1.390 -12.74
WL4D -1.390 -12.74
* CANOPY LOADS GENERATED
-------------------------
LOAD MEM NAME SYS DIR TYP DIST. INTENSITY ECCEN. DESCRIPTION
NO.
1 LC DL GLOB Y C 15.50 -0.179 -1.00 CANOPY LOAD
2 LC LL GLOB Y C 15.50 -0.793 -1.00 CANOPY LOAD
3 LC LS GLOB Y C 15.50 0.000 -1.00 CANOPY LOAD
4 LC RS GLOB Y C 15.50 0.000 -1.00 CANOPY LOAD
5 LC WL1 GLOB Y C 15.50 0.379 -1.00 CANOPY LOAD
6 LC WL1 GLOB X C 15.50 -0.126 0.00 CANOPY LOAD
7 LC WL2 GLOB Y C 15.50 0.379 -1.00 CANOPY LOAD
8 LC WL2 GLOB X C 15.50 -0.126 0.00 CANOPY LOAD
9 LC LWL1 GLOB Y C 15.50 0.299 -1.00 CANOPY LOAD
10 LC LWL1 GLOB X C 15.50 -0.100 0.00 CANOPY LOAD
11 LC LWL2 GLOB Y C 15.50 0.557 -1.00 CANOPY LOAD
12 LC LWL2 GLOB X C 15.50 -0.186 0.00 CANOPY LOAD
13 LC LWL3 GLOB Y C 15.50 -0.589 -1.00 CANOPY LOAD
14 LC LWL3 GLOB X C 15.50 0.196 0.00 CANOPY LOAD
15 LC LWL4 GLOB Y C 15.50 -0.331 -1.00 CANOPY LOAD
16 LC LWL4 GLOB X C 15.50 0.110 0.00 CANOPY LOAD
17 LC MWL1 GLOB Y C 15.50 0.379 -1.00 CANOPY LOAD
18 LC MWL1 GLOB X C 15.50 -0.126 0.00 CANOPY LOAD
19 LC MWL2 GLOB Y C 15.50 1.122 -1.00 CANOPY LOAD
Metallic Building Systems User: mmfarahani Page: F1- 10
R-Frame Design Program - Version V8.15 Job : 31650A
Continued Canopy Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
* CANOPY LOADS GENERATED (continued)
-------------------------
LOAD MEM NAME SYS DIR TYP DIST. INTENSITY ECCEN. DESCRIPTION
NO.
20 LC MWL2 GLOB X C 15.50 -0.374 0.00 CANOPY LOAD
21 LC WL3 GLOB Y C 15.50 1.122 -1.00 CANOPY LOAD
22 LC WL3 GLOB X C 15.50 -0.374 0.00 CANOPY LOAD
23 LC WL4 GLOB Y C 15.50 1.122 -1.00 CANOPY LOAD
24 LC WL4 GLOB X C 15.50 -0.374 0.00 CANOPY LOAD
25 LC WL1D GLOB Y C 15.50 0.171 -1.00 CANOPY LOAD
26 LC WL1D GLOB X C 15.50 -0.057 0.00 CANOPY LOAD
27 LC WL2D GLOB Y C 15.50 0.171 -1.00 CANOPY LOAD
28 LC WL2D GLOB X C 15.50 -0.057 0.00 CANOPY LOAD
29 LC LWL1D GLOB Y C 15.50 0.135 -1.00 CANOPY LOAD
30 LC LWL1D GLOB X C 15.50 -0.045 0.00 CANOPY LOAD
31 LC LWL2D GLOB Y C 15.50 0.251 -1.00 CANOPY LOAD
32 LC LWL2D GLOB X C 15.50 -0.084 0.00 CANOPY LOAD
33 LC LWL3D GLOB Y C 15.50 -0.265 -1.00 CANOPY LOAD
34 LC LWL3D GLOB X C 15.50 0.088 0.00 CANOPY LOAD
35 LC LWL4D GLOB Y C 15.50 -0.149 -1.00 CANOPY LOAD
36 LC LWL4D GLOB X C 15.50 0.050 0.00 CANOPY LOAD
37 LC WL3D GLOB Y C 15.50 0.505 -1.00 CANOPY LOAD
38 LC WL3D GLOB X C 15.50 -0.168 0.00 CANOPY LOAD
39 LC WL4D GLOB Y C 15.50 0.505 -1.00 CANOPY LOAD
40 LC WL4D GLOB X C 15.50 -0.168 0.00 CANOPY LOAD
Metallic Building Systems User: mmfarahani Page: F1- 11
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
* GENERAL LOAD CARDS GENERATED -
--------------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
1 LC DL GLOB Y C 15.504 -0.1790 N/A -1.000
2 LC LL GLOB Y C 15.504 -0.7930 N/A -1.000
3 LC LS GLOB Y C 15.504 0.0000 N/A -1.000
4 LC RS GLOB Y C 15.504 0.0000 N/A -1.000
5 LC WL1 GLOB Y C 15.504 0.3790 N/A -1.000
6 LC WL1 GLOB X C 15.504 -0.1260 N/A 0.000
7 LC WL2 GLOB Y C 15.504 0.3790 N/A -1.000
8 LC WL2 GLOB X C 15.504 -0.1260 N/A 0.000
9 LC LWL1 GLOB Y C 15.504 0.2990 N/A -1.000
10 LC LWL1 GLOB X C 15.504 -0.1000 N/A 0.000
11 LC LWL2 GLOB Y C 15.504 0.5570 N/A -1.000
12 LC LWL2 GLOB X C 15.504 -0.1860 N/A 0.000
13 LC LWL3 GLOB Y C 15.504 -0.5890 N/A -1.000
14 LC LWL3 GLOB X C 15.504 0.1960 N/A 0.000
15 LC LWL4 GLOB Y C 15.504 -0.3310 N/A -1.000
16 LC LWL4 GLOB X C 15.504 0.1100 N/A 0.000
17 LC MWL1 GLOB Y C 15.504 0.3790 N/A -1.000
18 LC MWL1 GLOB X C 15.504 -0.1260 N/A 0.000
19 LC MWL2 GLOB Y C 15.504 1.1220 N/A -1.000
20 LC MWL2 GLOB X C 15.504 -0.3740 N/A 0.000
21 LC WL3 GLOB Y C 15.504 1.1220 N/A -1.000
22 LC WL3 GLOB X C 15.504 -0.3740 N/A 0.000
23 LC WL4 GLOB Y C 15.504 1.1220 N/A -1.000
24 LC WL4 GLOB X C 15.504 -0.3740 N/A 0.000
25 LC WL1D GLOB Y C 15.504 0.1710 N/A -1.000
26 LC WL1D GLOB X C 15.504 -0.0570 N/A 0.000
27 LC WL2D GLOB Y C 15.504 0.1710 N/A -1.000
28 LC WL2D GLOB X C 15.504 -0.0570 N/A 0.000
29 LC LWL1D GLOB Y C 15.504 0.1350 N/A -1.000
30 LC LWL1D GLOB X C 15.504 -0.0450 N/A 0.000
31 LC LWL2D GLOB Y C 15.504 0.2510 N/A -1.000
32 LC LWL2D GLOB X C 15.504 -0.0840 N/A 0.000
33 LC LWL3D GLOB Y C 15.504 -0.2650 N/A -1.000
34 LC LWL3D GLOB X C 15.504 0.0880 N/A 0.000
35 LC LWL4D GLOB Y C 15.504 -0.1490 N/A -1.000
36 LC LWL4D GLOB X C 15.504 0.0500 N/A 0.000
37 LC WL3D GLOB Y C 15.504 0.5050 N/A -1.000
38 LC WL3D GLOB X C 15.504 -0.1680 N/A 0.000
39 LC WL4D GLOB Y C 15.504 0.5050 N/A -1.000
40 LC WL4D GLOB X C 15.504 -0.1680 N/A 0.000
41 LR DL XREF Y U 0.000 -0.0557 N/A 0.000
42 LC SW GLOB Y U 0.000 -0.0221 N/A 0.000
43 LR SW GLOB Y U 0.000 -0.0118 N/A 0.000
44 LR LL XREF Y U 0.000 -0.3990 N/A 0.000
45 LR PLLR1 XREF Y U 0.000 -0.3990 N/A 12.000
46 LR COLL XREF Y U 0.000 -0.0210 N/A 0.000
47 LC WL1 MEMB Y U 0.000 0.4146 N/A 0.000
48 LR WL1 MEMB Y U 0.000 0.4360 N/A 0.000
49 LC WL2 MEMB Y U 0.000 -0.0556 N/A 0.000
50 LR WL2 MEMB Y U 0.000 -0.0342 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F1- 12
R-Frame Design Program - Version V8.15 Job : 31650A
Load Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
51 LC LWL1 MEMB Y U 0.000 0.4274 N/A 0.000
52 LR LWL1 MEMB Y U 0.000 0.3932 N/A 0.000
53 LC LWL2 MEMB Y U 0.000 0.4274 N/A 0.000
54 LR LWL2 MEMB Y U 0.000 0.5300 N/A 0.000
55 LC LWL3 MEMB Y U 0.000 -0.0427 N/A 0.000
56 LR LWL3 MEMB Y U 0.000 -0.0769 N/A 0.000
57 LC LWL4 MEMB Y U 0.000 -0.0427 N/A 0.000
58 LR LWL4 MEMB Y U 0.000 0.0598 N/A 0.000
59 LC MWL1 MEMB Y U 0.000 0.1680 N/A 0.000
60 LR MWL1 GLOB X U 0.000 -0.0531 N/A 12.649
61 LC MWL2 MEMB Y U 0.000 -0.1680 N/A 0.000
62 LR MWL2 GLOB X U 0.000 0.0531 N/A 12.649
63 LC WL3 MEMB Y U 0.000 0.0128 N/A 0.000
64 LR WL3 MEMB Y U 0.000 0.5300 N/A 0.000
65 LC WL4 MEMB Y U 0.000 -0.4573 N/A 0.000
66 LR WL4 MEMB Y U 0.000 0.0598 N/A 0.000
67 LC WL1D MEMB Y U 0.000 0.1868 N/A 0.000
68 LR WL1D MEMB Y U 0.000 0.1964 N/A 0.000
69 LC WL2D MEMB Y U 0.000 -0.0250 N/A 0.000
70 LR WL2D MEMB Y U 0.000 -0.0154 N/A 0.000
71 LC LWL1D MEMB Y U 0.000 0.1925 N/A 0.000
72 LR LWL1D MEMB Y U 0.000 0.1771 N/A 0.000
73 LC LWL2D MEMB Y U 0.000 0.1925 N/A 0.000
74 LR LWL2D MEMB Y U 0.000 0.2387 N/A 0.000
75 LC LWL3D MEMB Y U 0.000 -0.0193 N/A 0.000
76 LR LWL3D MEMB Y U 0.000 -0.0347 N/A 0.000
77 LC LWL4D MEMB Y U 0.000 -0.0193 N/A 0.000
78 LR LWL4D MEMB Y U 0.000 0.0270 N/A 0.000
79 LC WL3D MEMB Y U 0.000 0.0058 N/A 0.000
80 LR WL3D MEMB Y U 0.000 0.2387 N/A 0.000
81 LC WL4D MEMB Y U 0.000 -0.2060 N/A 0.000
82 LR WL4D MEMB Y U 0.000 0.0270 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F1- 13
R-Frame Design Program - Version V8.15 Job : 31650A
Seismic Summary Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Seismic Force Resisting System Per :
ASCE 7 Standard
2016 Edition
Standard Risk Category Building for Seismic Loadings
Seismic Loads Required for Building ................................ Yes
Response Acceleration Coeff., for Short Periods [Ss] (%g) .......... 118.3000
Response Acceleration Coeff., for 1 sec. Periods [S1] (%g) ......... 42.5000
Long-period Transition Period Time [TL] (seconds) .................. 16.0000
Seismic Design Category ............................................ D
Soil Profile Type .................................................. D
Seismic Site Coefficient [Fa] ...................................... 1.2000
Seismic Site Coefficient [Fv] ...................................... 1.8750
Maximum Spectral Response Accel., for Short Periods [Sms] (g) ...... 1.4196
Maximum Spectral Response Accel., for 1 sec. Periods [Sm1] (g) ..... 0.7969
Design Spectral Response Accel., for Short Periods [Sds] (g) ....... 0.9464
Design Spectral Response Accel., for 1 sec. Periods [Sd1] (g) ...... 0.5312
Sds and Sd1 values .......................................... Code-calculated
Seismic Response Modification Factor [R] ........................... 3.5000
Seismic Importance Factor [I] ...................................... 1.0000
Storage/Equipment Areas and/or Service Rooms Exist ................. No
Seismic Story Height [hn] (feet) ................................... 18.0000
Seismic Fundamental Period [T] Used (seconds) ...................... 0.2827
Seismic Overstrength Factor [OMEGAo] ............................... 2.5000
Longitudinal Seismic Redundancy/Reliability Factor [L-rho] ......... 1.3000
Seismic Redundancy/Reliability Factor [rho] ........................ 1.5000
Snow in Seismic Force Calculations [Used] (%) ...................... 0.00
Snow in Seismic Force Calculations [Min. Required] (%) ............. 0.00
Snow in Seismic Load Combinations [Used] (%) ....................... 0.00
Snow in Seismic Load Combinations [Min. Required] (%) .............. 0.00
Mezz. Live load in Seismic Force Calculations [Used] (%) ........... 0.00
Mezz. Live load in Seismic Force Calculations [Min. Required] (%) .. 0.00
Mezz. Live load in Seismic Load Combinations [Used] (%) ............ 100.00
Mezz. Live load in Seismic Load Combinations [Min. Required] (%) ... 100.00
Building Height Limit (feet) ....................................... 65.0000
Seismic Story Drift Limit Factor ................................... 0.0250
Seismic Story Drift Limit (in) ..................................... 6.0000
Seismic Deflection Amplification Factor [Cd] ....................... 3.0000
Seismic Response Coefficient [Cs] Used ............................. 0.2704
Seismic Story Drift [Cd*Drift/Importance Factor] (in) .............. 0.001
Theta [Px*Ie*Delta/Vx/hx/Cd]........................................ 0.000
Theta Max [.5/BETA/Cd] where BETA=1.0............................... 0.167
Roof Dead Load = 1.047
Wall Weight = 0.000
Collateral Load = 0.143
Snow Load = 0.000
Rafter Crane Weight = 0.000
-------------------------------------
Total Roof Weight = 1.190 kips
Total Roof Weight = 1.190
Mezzanine Weight = 0.000
Col. Crane Weight = 0.000
-------------------------------------
TOTAL Bldg Weight = 1.190 kips
X X
Seismic Coeff. = 0.2704
-------------------------------------
BASE SHEAR = 0.3218 kips
Seismic Load for Roof at col # 1 = 0.3218 kips
Seismic Load for Roof at col # 2 = 0.0000 kips
---------------------------------------------------
SEISMIC LOAD for Roof in TOTAL = 0.3218 kips
* SEISMIC GENERAL LOAD CARDS GENERATED
--------------------------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
83 LC EQ YREF X C 15.213 0.3218 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F1- 14
R-Frame Design Program - Version V8.15 Job : 31650A
Forces and Allowable Stresses Summary File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Left Column Analysis Length = 15.21 ft Kx = 1.00 Weight = 336. lbs
Part Length Mem Depths at Member Description Web Fy
No. (ft) Start(in) End(in) Thickness (ksi)
1 10.00 10.200 10.200 W10X22 0.2400 in 50.0
2 4.92 10.200 10.200 W10X22 0.2400 in 50.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
105 -0.7 7.4 0.1 7.6 20.0 33.6 20.0 0.00 0.20 0.12 0.20 43
201 -3.3 5.4 -0.5 7.6 19.7 33.6 20.0 0.01 0.18 0.12 0.18 51
--------------------------------------------------------------------------------
Left Rafter Analysis Length = 11.03 ft Kx = 1.00 Weight = 133. lbs
Part Length Mem Depths at Member Description Web Fy
No. (ft) Start(in) End(in) Thickness (ksi)
3 11.30 9.870 9.870 W10X12 0.1900 in 50.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
308 -0.1 6.6 0.2 11.5 33.4 26.6 20.0 0.00 0.22 0.28 0.28 2
--------------------------------------------------------------------------------
TOTAL MEMBER WEIGHT = 469. lbs
Metallic Building Systems User: mmfarahani Page: F1- 15
R-Frame Design Program - Version V8.15 Job : 31650A
Anchor Rod and Base Plate Design File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
LEFT EXTERIOR COLUMN ANCHOR RODS AND BASE PLATE DESIGN
======================================================
Anchor Rod & Base Plate Design Sizes >>
---------------------------------------
Use ( 4)- 0.750 in. Dia. F1554, Gr. 36 Anchor Rods
Rod Gage : 4.000 in. Rod Spacing (in.): 3.0000, 1 @ 4.0000, 3.2000
Plate Size : 6.0000 x 10.2000 x 0.3750 in. (Width x Depth x Thickness)
Controlling Reactions for Anchor Rod Design >>
----------------------------------------------
Shear Tension Allowable Load Check
Loading Type (kips) (kips) (kips) No. Ratio
-----------------------------------------------------------------
Rod Tension 0.000 2.905 38.436 29 0.08
Rod Shear 2.025 0.000 23.061 25 0.09
Standard Base Plate Welding >> (Using E70 Electrodes)
------------------------------
Fillet Weld Weld Weld Design Weld
Weld Size Length Capacity Force Load Check
Location (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------
Inner Flg 0.31250 5.750 26.682 0.937 29 0.04
Outer Flg 0.31250 5.750 26.682 0.937 29 0.04
Web Plate 0.18750 9.480 26.395 2.209 29 0.08
Metallic Building Systems User: mmfarahani Page: F1- 16
R-Frame Design Program - Version V8.15 Job : 31650A
Leanto Boss Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
BOSS DESIGN
SEGMENT STARTING ENDING WEB OUTER FLANGE INNER FLANGE
SEG LENGTH WEB DEPTH WEB DEPTH THICKNESS WIDTH THICKNESS WIDTH THICKNESS
NUM (FEET) (INCHES) (INCHES) (INCHES) (IN.) (IN.) (IN.) (IN.)
--- ------ --------- --------- --------- --------------- ---------------
1 0.725 12.2000 9.4500 0.1340 5.00 x 0.2500 5.00 x 0.2500
FY= 55.00 KSI FU= 70.00 KSI LENGTH= 8.70 INCHES WEIGHT= 9.7 LBS.
Metallic Building Systems User: mmfarahani Page: F1- 17
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Vertical Knee Connection @ Left Rafter Depth 1
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 2 rows P. Depth - 1/2 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 5.75 x 0.3600 in. Plate: 5.00 x 0.2500 in.
Fy(Min) 55.0 ksi Fy(Min) 55.0 ksi
Fu 70.0 ksi Fu 70.0 ksi
Flanges:
O.S. - 3.96 x 0.2100 in.
I.S. - 3.96 x 0.2100 in.
Web Depth - 9.961 in.
Web Thickness 0.190 in.
Gage - 2.500 in.
Center of Bolt to Flange:
Pf top (ins) - 2.049 in.
BFCD top (ins) - 1.500 in.
Rise top (ins) - 0.302 in.
XTI top (ins) - 1.966 in.
Bolt Spacing - 2.500 in.
Angle top -108.4 degrees
Angle bot - 71.6 degrees
Plate Length - 6.049 in.
Left Side Conn Right Side Conn
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
21) DL +0.6LWL2 0.00 2.43 -2.30 0.00 2.43 -2.30
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.1211 Plate Unity Check (O.S.) = 0.3171
Weld Unity Check = 0.1847
Metallic Building Systems User: mmfarahani Page: F1- 18
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Peak Connection @ Left Rafter Depth 2
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 2 rows P. Depth - 1/2 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 5.00 x 0.2500 in. Plate: 5.00 x 0.2500 in.
Fy(Min) 55.0 ksi Fy(Min) 55.0 ksi
Fu 70.0 ksi Fu 70.0 ksi
Flanges: Flanges:
O.S. - 3.96 x 0.2100 in. O.S. - 5.00 x 0.2500 in.
I.S. - 3.96 x 0.2100 in. I.S. - 5.00 x 0.2500 in.
Web Depth - 9.961 in. Web Depth - 9.961 in.
Web Thickness 0.190 in. Web Thickness 0.190 in.
Gage - 2.500 in. Gage - 2.500 in.
Center of Bolt to Flange: Center of Bolt to Flange:
Pf top (ins) - 1.841 in. Pf top (ins) - 2.007 in.
BFCD top (ins) - 1.500 in. BFCD top (ins) - 1.500 in.
Rise top (ins) - 0.302 in. Rise top (ins) - 0.302 in.
XTI top (ins) - 1.924 in. XTI top (ins) - 1.924 in.
Bolt Spacing - 2.500 in. Bolt Spacing - 2.500 in.
Angle top - 71.6 degrees Angle top -108.4 degrees
Angle bot -108.4 degrees Angle bot - 90.0 degrees
Plate Length - 6.007 in. Plate Length - 6.007 in.
Left Side Conn Right Side Conn
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
21) DL +0.6LWL2 -0.00 3.54 0.31
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.1216 Plate Unity Check (O.S.) = 0.4619
Weld Unity Check = 0.1723
Required Connection Plate Welding >> (Using E70 Electrodes)
------------------------------------
Welded Weld Weld Weld Design Weld
Joint Size Length Capacity Force Load Check
Weld Location Type (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------------------
Left Side of Conn
Inner Flg Fillet-BS 0.1875 7.9200 33.0767 0.8276 21 0.0250
Outer Flg Fillet-BS 0.1875 7.9200 33.0767 0.8276 21 0.0250
Web Plate Fillet-BS 0.1875 19.9223 55.4685 2.5798 3 0.0465
------------------------------------------------------------------------------
NS - Near side weld, FS - Far side weld, BS - Both sides weld.
Metallic Building Systems User: mmfarahani Page: F1- 19
R-Frame Design Program - Version V8.15 Job : 31650A
Knee and Stiffener Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Left Knee Design
================
Knee Web Thickness : Use 0.2400 in. Thick Web
Column Cap Plate : 6.0000 X 0.2500 in.
Metallic Building Systems User: mmfarahani Page: F1- 20
R-Frame Design Program - Version V8.15 Job : 31650A
Flange Brace Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
Girt Spaces - Vertical Measurements
Left Column Right Column
1 @ 16'0 @ FLOOR
Purlin Spaces - Horizontal Measurements
Left Rafter Right Rafter
2 @ 3'0 @ EAVE
1 @ 4'0
1 @ 2'0 @ PEAK
--------------------------------------------------------------------------------
Member Distance to Brace Points (feet)
- Left Rafter : Measured along T.F. from left steel line
- Right Rafter : Measured along T.F. from right steel line
- Ext. Columns : Measured along T.F. from base
--------------------------------------------------------------------------------
LFT RAFTER 3.16 6.32 10.54
(C) (N) (C)
--------------------------------------------------------------------------------
"N" Indicates that No flange braces are located at the brace point
"C" Indicates that One 2"x2"x14 ga flange brace is located at the brace point
--------------------------------------------------------------------------------
Metallic Building Systems User: mmfarahani Page: F1- 21
R-Frame Design Program - Version V8.15 Job : 31650A
Primary Deflection Report File: ltfrar_2-4.fra Date: 9/22/21
lt 12./16./20. 20./100./0. Start Time: 18:28:34
--------------------------------------------------------------------------------
COLUMN TOP DEFLECTIONS for LOAD COMBS. (Positive = X: Right Y:Upward) (Inches)
==============================================================================
Ext. Left Col Ext Right Col
X-Def Y-Def X-Def Y-Def
------------------------------------------------------------------------------
Neg. Max -0.004 -0.004
Load Comb 58 3
Defl. H/999
==============================================================================
MAX RAFTER DEFLECTIONS for SPAN #1. (Positive = Y:Upw ard)
==============================================================================
Max. Downward Deflection Max. Upward Deflection
Y-Def. X-Dist. from Left S.L. Y-Def. X-Dist. from Left S.L.
------------------------------------------------------------------------------
Max. Def -0.090 in. 6.38 ft. 0.049 in. 6.38 ft.
Load Comb 2 61
Defl. L/999 L/999
==============================================================================
Vertical Clearance at the Left Knee is 14.9278 feet
Vertical Clearance at the Right Knee is 17.8889 feet
Metallic Page: 1
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Windforce-resistance System Per:
2016 ASCE 7
Longitudinal wind loading case 1
(Endwall EWB is windward endwall)
100 mph Main framing wind load and coefficients
Enclosed Building, Normal Building Category, EXPOSURE C
90% of endwall surfaces in interior zone
10% of endwall surfaces in end zone within 6 feet of wall corners
Velocity pressure coefficient ( Kh )................................ 0.928588
Ground Elevation Factor ( Ke )...................................... 0.996603
Directionality Factor ( Kd )........................................ 0.85
Basic Pressure ( Qh )............................................... 20.13743
Topographic factor - at mean roof height = 1.0000
Windward wall...................... [GCpf-GCpi]= 0.6947 P= 13.990 psf
Leeward wall....................... [GCpf-GCpi]= -0.1235 P= -2.488 psf
Roof Brace External loading .6*W Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPC:
1 1.648 TOTAL
1.399 @ FRAME LINE 1
0.249 @ FRAME LINE 4 0.5000" ROD
20.000' Transfered = 1.977 2.87 2.87 4.79
2 3.296 TOTAL
2.798 @ FRAME LINE 1
0.498 @ FRAME LINE 4 0.5000" ROD
5.000' Transfered = 0.000 0.00 0.00 4.79
3 0.000 TOTAL
0.5000" ROD
5.000' Transfered = 0.000 0.00 0.00 4.79
4 3.296 TOTAL
2.798 @ FRAME LINE 1
0.498 @ FRAME LINE 4 0.5000" ROD
20.000' Transfered = 1.977 2.87 2.87 4.79
5 2.522 TOTAL
2.571 @ FRAME LINE 1
-0.049 @ FRAME LINE 4
PLANE RPA:
--------- ----- --------------------------- ------ ------ ------
Metallic Page: 2
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING SIDEWALL LONGITUDINAL BRACING DESIGN ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWC:
Line 1
3.296 Transfered from roof
Tier 1 20.00' 1.648 TOTAL
1.399 @ FRAME LINE 1
0.249 @ FRAME LINE 4
Transfered = 4.944
0.6*W = 0.6 * 4.944 = 2.97
Load / Bay = 2.97 / 1 bays = 2.97
Brace T / Bay = 4.19
Rod Design = 0.7500" ROD
Brace Allowable = 10.60
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWA:
Line 5
3.995 Transfered from roof
Tier 1 20.00' 2.522 TOTAL
2.571 @ FRAME LINE 1
-0.049 @ FRAME LINE 4
Transfered = 6.518
** See portal frame for load application
Metallic Page: 3
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Windforce-resistance System Per:
2016 ASCE 7
Longitudinal wind loading case 2
(Endwall EWD is windward endwall)
100 mph Main framing wind load and coefficients
Enclosed Building, Normal Building Category, EXPOSURE C
90% of endwall surfaces in interior zone
10% of endwall surfaces in end zone within 6 feet of wall corners
Velocity pressure coefficient ( Kh )................................ 0.928588
Ground Elevation Factor ( Ke )...................................... 0.996603
Directionality Factor ( Kd )........................................ 0.85
Basic Pressure ( Qh )............................................... 20.13743
Topographic factor - at mean roof height = 1.0000
Windward wall...................... [GCpf-GCpi]= 0.6947 P= 13.990 psf
Leeward wall....................... [GCpf-GCpi]= -0.1235 P= -2.488 psf
Roof Brace External loading .6*W Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPC:
1 1.648 TOTAL
0.249 @ FRAME LINE 1
1.399 @ FRAME LINE 4 0.5000" ROD
20.000' Transfered = 1.977 2.87 2.87 4.79
2 3.296 TOTAL
0.498 @ FRAME LINE 1
2.798 @ FRAME LINE 4 0.5000" ROD
5.000' Transfered = 0.000 0.00 0.00 4.79
3 0.000 TOTAL
0.5000" ROD
5.000' Transfered = 0.000 0.00 0.00 4.79
4 3.296 TOTAL
0.498 @ FRAME LINE 1
2.798 @ FRAME LINE 4 0.5000" ROD
20.000' Transfered = 1.977 2.87 2.87 4.79
5 2.522 TOTAL
-0.049 @ FRAME LINE 1
2.571 @ FRAME LINE 4
PLANE RPA:
--------- ----- --------------------------- ------ ------ ------
Metallic Page: 4
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING SIDEWALL LONGITUDINAL BRACING DESIGN ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWC:
Line 1
3.296 Transfered from roof
Tier 1 20.00' 1.648 TOTAL
0.249 @ FRAME LINE 1
1.399 @ FRAME LINE 4
Transfered = 4.944
0.6*W = 0.6 * 4.944 = 2.97
Load / Bay = 2.97 / 1 bays = 2.97
Brace T / Bay = 4.19
Rod Design = 0.7500" ROD
Brace Allowable = 10.60
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWA:
Line 5
3.995 Transfered from roof
Tier 1 20.00' 2.522 TOTAL
-0.049 @ FRAME LINE 1
2.571 @ FRAME LINE 4
Transfered = 6.518
** See portal frame for load application
Metallic Page: 5
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Seismic-resistance System Per:
2016 ASCE 7
Longitudinal seismic loading case 1
(PLANE EWB endwall to opposite endwall is force direction)
Soil Profile Type................................................... D
Seismic design category............................................. D
Mapped spectral response accel. for short periods (Ss).............. 1.183
Mapped spectral response accel. for 1 second periods (S1)........... 0.425
Design, 5% damped, spectral response accel. at short periods (Sds).. 0.9464
Design, 5% damped, spectral response accel. at period 1 sec. (Sd1).. 0.53125
Sds and Sd1 values.............................................Code-Calculated
Longitudinal Building Period (T).................................... 0.209
Seismic Reliability/Redundancy Factor............................... 1.3
Seismic Importance Factor (I)....................................... 1
Building minimum longitudinal R value............................... 3.25
Building minimum transverse R value................................. 3.25
Roof dead load included in Seismic force "W" (psf) ................. 4.618
Roof collateral load included in Seismic force "W" (psf) ........... 5.000
Roof Brace External loading (W) .7rhoV Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPC:
1 7.330 TOTAL
0.492 @ FRAME LINE 1, 4
2.115 @ BAY 1, 2, 3 0.5000" ROD
20.000' Transfered = 10.446 2.77 4.02 4.02 4.79
2 8.694 TOTAL
0.740 @ FRAME LINE 1, 4
2.405 @ BAY 1, 2, 3 0.5000" ROD
5.000' Transfered = 1.751 0.46 0.48 0.48 4.79
3 3.503 TOTAL
0.309 @ FRAME LINE 1, 4
0.962 @ BAY 1, 2, 3 0.5000" ROD
5.000' Transfered = 1.751 0.46 0.48 0.48 4.79
4 8.694 TOTAL
0.740 @ FRAME LINE 1, 4
2.405 @ BAY 1, 2, 3 0.5000" ROD
20.000' Transfered = 10.446 2.77 4.02 4.02 4.79
5 8.924 TOTAL
0.492 @ FRAME LINE 1, 4
0.068 @ FRAME LINE 2, 3
2.601 @ BAY 1, 2, 3
PLANE RPA:
--------- ----- --------------------------- ------ ------ ------ ------
- Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
Roof bracing load E=rhoV; rho=1.30
Metallic Page: 6
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING SIDEWALL LONGITUDINAL BRACING DESIGN ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWC:
Line 1
10.446 Transfered from roof
Tier 1 20.00' 7.330 TOTAL
0.492 @ FRAME LINE 1, 4
2.115 @ BAY 1, 2, 3
Transfered = 17.776 Weight (W)
V = Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
V = (0.95)/((3.25)/(1.00))(17.78) = 5.18
0.7*Omega*V = 0.7*2.00*5.176 = 7.25
Brace T = 10.25
Brace T / Bay = 10.25 / 1 bays =10.25
Rod Design = 0.7500" ROD
Brace Allowable = 12.72
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWA:
Line 5
13.189 Transfered from roof
Tier 1 20.00' 8.924 TOTAL
0.492 @ FRAME LINE 1, 4
0.068 @ FRAME LINE 2, 3
2.601 @ BAY 1, 2, 3
Transfered = 22.114 Weight (W)
V = Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
V = (0.95)/((3.25)/(1.00))(22.11) = 6.44
** See portal frame for load application
Metallic Page: 7
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Seismic-resistance System Per:
2016 ASCE 7
Longitudinal seismic loading case 2
(PLANE EWD endwall to opposite endwall is force direction)
Soil Profile Type................................................... D
Seismic design category............................................. D
Mapped spectral response accel. for short periods (Ss).............. 1.183
Mapped spectral response accel. for 1 second periods (S1)........... 0.425
Design, 5% damped, spectral response accel. at short periods (Sds).. 0.9464
Design, 5% damped, spectral response accel. at period 1 sec. (Sd1).. 0.53125
Sds and Sd1 values.............................................Code-Calculated
Longitudinal Building Period (T).................................... 0.209
Seismic Reliability/Redundancy Factor............................... 1.3
Seismic Importance Factor (I)....................................... 1
Building minimum longitudinal R value............................... 3.25
Building minimum transverse R value................................. 3.25
Roof dead load included in Seismic force "W" (psf) ................. 4.618
Roof collateral load included in Seismic force "W" (psf) ........... 5.000
Roof Brace External loading (W) .7rhoV Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPC:
1 7.330 TOTAL
0.492 @ FRAME LINE 1, 4
2.115 @ BAY 1, 2, 3 0.5000" ROD
20.000' Transfered = 10.446 2.77 4.02 4.02 4.79
2 8.694 TOTAL
0.740 @ FRAME LINE 1, 4
2.405 @ BAY 1, 2, 3 0.5000" ROD
5.000' Transfered = 1.751 0.46 0.48 0.48 4.79
3 3.503 TOTAL
0.309 @ FRAME LINE 1, 4
0.962 @ BAY 1, 2, 3 0.5000" ROD
5.000' Transfered = 1.751 0.46 0.48 0.48 4.79
4 8.694 TOTAL
0.740 @ FRAME LINE 1, 4
2.405 @ BAY 1, 2, 3 0.5000" ROD
20.000' Transfered = 10.446 2.77 4.02 4.02 4.79
5 8.924 TOTAL
0.492 @ FRAME LINE 1, 4
0.068 @ FRAME LINE 2, 3
2.601 @ BAY 1, 2, 3
PLANE RPA:
--------- ----- --------------------------- ------ ------ ------ ------
- Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
Roof bracing load E=rhoV; rho=1.30
Metallic Page: 8
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING SIDEWALL LONGITUDINAL BRACING DESIGN ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWC:
Line 1
10.446 Transfered from roof
Tier 1 20.00' 7.330 TOTAL
0.492 @ FRAME LINE 1, 4
2.115 @ BAY 1, 2, 3
Transfered = 17.776 Weight (W)
V = Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
V = (0.95)/((3.25)/(1.00))(17.78) = 5.18
0.7*Omega*V = 0.7*2.00*5.176 = 7.25
Brace T = 10.25
Brace T / Bay = 10.25 / 1 bays =10.25
Rod Design = 0.7500" ROD
Brace Allowable = 12.72
Wall Brace External loading
strut elev applied to strut line
--------- ----- ---------------------------
PLANE SWA:
Line 5
13.189 Transfered from roof
Tier 1 20.00' 8.924 TOTAL
0.492 @ FRAME LINE 1, 4
0.068 @ FRAME LINE 2, 3
2.601 @ BAY 1, 2, 3
Transfered = 22.114 Weight (W)
V = Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
V = (0.95)/((3.25)/(1.00))(22.11) = 6.44
** See portal frame for load application
Metallic Page: 9
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:51
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
ROOF STRUT LINE DESIGN
BLDG-A ROOF BRACING PURLIN STRUT NO. 2
ANALYSIS OF PURLIN LINE 6 ON ROOF PLANE RPC
LOAD COMBINATIONS : 1) 0.60D + 0.60W3-1 2) 0.60D + 0.60W3-2
3) 0.60D + 0.60W4-1 4) 0.60D + 0.60W4-2
5) D + C + 3/4L + 0.45W3-1 6) D + C + 3/4L + 0.45W3-2
7) D + C + 3/4L + 0.45W4-1 8) D + C + 3/4L + 0.45W4-2
9) D + C + 0.45W3-1 10) D + C + 0.45W3-2
11) D + C + 0.45W4-1 12) D + C + 0.45W4-2
13) 1.13D + 1.13C + 0.91E3-1 14) 1.13D + 1.13C + 0.91E4-1
WHERE : D = Dead load
C = Collateral load
L = Live load
W3-1= Wind Case 1, Positive internal pressure
W3-2= Wind Case 1, Negative internal pressure
W4-1= Wind Case 2, Positive internal pressure
W4-2= Wind Case 2, Negative internal pressure
E3-1= Seismic load Case 1
E4-1= Seismic load Case 2
Span Length Member, Avg Spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
LE 2.333 8X2.5Z16 4.333 3 0.068 shear+bending
6 L/ 140 deflection
1 19.667 8X2.5Z16 4.333 0 1.4791 3 0.585 axial+bending
& 2 discrete brace pt 6 L/ 503 deflection
2 20.000 8X2.5Z16 4.333 1.4791 1.4791 6 0.525 axial+bending
& 2 discrete brace pt 3 L/4423 deflection
3 19.667 8X2.5Z16 4.333 1.479 1 0.585 axial+bending
& 2 discrete brace pt 8 L/ 503 deflection
RE 2.333 8X2.5Z16 4.333 1 0.068 shear+bending
8 L/ 140 deflection
Total line design weight is 195.5 lbs.
Metallic Page: 10
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:52
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
ROOF STRUT LINE DESIGN
BLDG-A ROOF BRACING PURLIN STRUT NO. 3
ANALYSIS OF PURLIN LINE 7 ON ROOF PLANE RPC
LOAD COMBINATIONS : 1) 0.60D + 0.60W3-1 2) 0.60D + 0.60W3-2
3) 0.60D + 0.60W4-1 4) 0.60D + 0.60W4-2
5) D + C + 3/4L + 0.45W3-1 6) D + C + 3/4L + 0.45W3-2
7) D + C + 3/4L + 0.45W4-1 8) D + C + 3/4L + 0.45W4-2
9) D + C + 0.45W3-1 10) D + C + 0.45W3-2
11) D + C + 0.45W4-1 12) D + C + 0.45W4-2
13) 1.13D + 1.13C + 0.91E3-1 14) 1.13D + 1.13C + 0.91E4-1
WHERE : D = Dead load
C = Collateral load
L = Live load
W3-1= Wind Case 1, Positive internal pressure
W3-2= Wind Case 1, Negative internal pressure
W4-1= Wind Case 2, Positive internal pressure
W4-2= Wind Case 2, Negative internal pressure
E3-1= Seismic load Case 1
E4-1= Seismic load Case 2
Span Length Member, Avg Spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
LE 2.333 8X2.5Z16 3.214 3 0.050 shear+bending
6 L/ 186 deflection
1 19.667 8X2.5Z16 3.214 0 1.4791 6 0.356 shear+bending
& 2 discrete brace pt 6 L/ 669 deflection
2 20.000 8X2.5Z16 3.214 1.4791 1.4791 6 0.357 shear+bending
& 2 discrete brace pt 1 L/6000 deflection
3 19.667 8X2.5Z16 3.214 1.479 8 0.356 shear+bending
& 2 discrete brace pt 8 L/ 669 deflection
RE 2.333 8X2.5Z16 3.214 1 0.050 shear+bending
8 L/ 186 deflection
Total line design weight is 195.5 lbs.
Metallic Page: 11
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:52
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
ROOF STRUT LINE DESIGN
BLDG-A ROOF BRACING PURLIN STRUT NO. 4
ANALYSIS OF PURLIN LINE 6 ON ROOF PLANE RPA
LOAD COMBINATIONS : 1) 0.60D + 0.60W3-1 2) 0.60D + 0.60W3-2
3) 0.60D + 0.60W4-1 4) 0.60D + 0.60W4-2
5) D + C + 3/4L + 0.45W3-1 6) D + C + 3/4L + 0.45W3-2
7) D + C + 3/4L + 0.45W4-1 8) D + C + 3/4L + 0.45W4-2
9) D + C + 0.45W3-1 10) D + C + 0.45W3-2
11) D + C + 0.45W4-1 12) D + C + 0.45W4-2
13) 1.13D + 1.13C + 0.91E3-1 14) 1.13D + 1.13C + 0.91E4-1
WHERE : D = Dead load
C = Collateral load
L = Live load
W3-1= Wind Case 1, Positive internal pressure
W3-2= Wind Case 1, Negative internal pressure
W4-1= Wind Case 2, Positive internal pressure
W4-2= Wind Case 2, Negative internal pressure
E3-1= Seismic load Case 1
E4-1= Seismic load Case 2
Span Length Member, Avg Spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
LE 2.333 8X2.5Z16 4.333 1 0.068 shear+bending
8 L/ 140 deflection
1 19.667 8X2.5Z16 4.333 0 1.4791 1 0.585 axial+bending
& 2 discrete brace pt 8 L/ 503 deflection
2 20.000 8X2.5Z16 4.333 1.4791 1.4791 6 0.525 axial+bending
& 2 discrete brace pt 3 L/4423 deflection
3 19.667 8X2.5Z16 4.333 1.479 3 0.585 axial+bending
& 2 discrete brace pt 6 L/ 503 deflection
RE 2.333 8X2.5Z16 4.333 3 0.068 shear+bending
6 L/ 140 deflection
Total line design weight is 195.5 lbs.
Metallic Page: 12
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
EAVE STRUT LINE DESIGN
BLDG-A ROOF BRACING EAVE STRUT NO. 1
ANALYSIS OF EAVE STRUT LINE ON WALL PLANE SWC
LOAD COMBINATIONS : 1) 0.60WS3 2) 0.60WS4
3) 1.40ES3 4) 1.40ES4
WHERE : WS3 = Wind load from plane EWB
WS4 = Wind load from plane EWD
ES3 = Seismic load from plane EWB
ES4 = Seismic load from plane EWD
Span Length Member, Avg spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
1 19.667 8X3.5E14 4 0.070 axial
3 0.191 connection
2 20.000 8X3.5E14 3 0.408 axial
1 0.607 connection
3 19.667 8X3.5E14 3 0.070 axial
4 0.191 connection
Metallic Page: 13
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING ROOF LONGITUDINAL BRACING DESIGN ****
EAVE STRUT LINE DESIGN
BLDG-A ROOF BRACING EAVE STRUT NO. 5
ANALYSIS OF EAVE STRUT LINE ON WALL PLANE SWA
LOAD COMBINATIONS : 1) 0.60WS3 2) 0.60WS4
3) 1.40ES3 4) 1.40ES4
WHERE : WS3 = Wind load from plane EWB
WS4 = Wind load from plane EWD
ES3 = Seismic load from plane EWB
ES4 = Seismic load from plane EWD
Span Length Member, Avg spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
1 19.667 8X3.5E14 1 0.122 axial
1 0.332 connection
2 20.000 8X3.5E14 3 0.509 axial
1 0.849 connection
3 19.667 8X3.5E14 3 0.000 axial
1 NaN connection
Metallic Page: 14
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** MAIN BUILDING LONGITUDINAL BRACING DESIGN ****
LONGITUDINAL BRACING DESIGN SUMMARY
Roof Bracing:
Brace Bay 3 Bay 2 Bay 1
Strut Spans 20.000 feet 20.000 feet 20.000 feet
---------- ----- ------------- ------------- -------------
PLANE RPC:
1 8X3.5E14 8X3.5E14 8X3.5E14
20.000' 0.5000" ROD
2 8X2.5Z16 8X2.5Z16 8X2.5Z16
5.000' 0.5000" ROD
3 8X2.5Z16 8X2.5Z16 8X2.5Z16
5.000' 0.5000" ROD
4 8X2.5Z16 8X2.5Z16 8X2.5Z16
20.000' 0.5000" ROD
5 8X3.5E14 8X3.5E14 8X3.5E14
PLANE RPA:
---------- ----- ------------- ------------- -------------
Brace Bay 1 Bay 2 Bay 3
Sidewall Bracing:
Brace Bay 3 Bay 2 Bay 1
Strut Spans 20.000 feet 20.000 feet 20.000 feet
---------- ----- ------------- ------------- -------------
PLANE SWC:
1 8X3.5E14 8X3.5E14 8X3.5E14
20.000' 0.7500" ROD
---------- ----- ------------- ------------- -------------
Brace Bay 1 Bay 2 Bay 3
Strut Spans 20.000 feet 20.000 feet 20.000 feet
---------- ----- ------------- ------------- -------------
PLANE SWA:
5 8X3.5E14 8X3.5E14 8X3.5E14
20.000' PORTAL FRAME
---------- ----- ------------- ------------- -------------
Metallic Page: 15
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** RPA LEANTO ROOF LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Windforce-resistance System Per:
2016 ASCE 7
Longitudinal wind loading case 1
(Endwall EWB is windward endwall)
100 mph Main framing wind load and coefficients
Partially Enclosed Building, Normal Building Category, EXPOSURE C
90% of endwall surfaces in interior zone
10% of endwall surfaces in end zone within 6 feet of wall corners
Velocity pressure coefficient ( Kh )................................ 0.928588
Ground Elevation Factor ( Ke )...................................... 0.996603
Directionality Factor ( Kd )........................................ 0.85
Basic Pressure ( Qh )............................................... 20.13743
Topographic factor - at mean roof height = 1.0000
Windward wall...................... [GCpf-GCpi]= 0.9703 P= 19.540 psf
Leeward wall....................... [GCpf-GCpi]= 0.2465 P= 4.963 psf
Roof Brace External loading .6*W Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPA:
6 0.700 TOTAL
0.938 @ FRAME LINE 1
-0.238 @ FRAME LINE 4 0.5000" ROD
12.000' Transfered = 0.420 0.00 0.50 4.79
--------- ----- --------------------------- ------ ------ ------
Metallic Page: 16
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** SWA LEANTO SIDEWALL LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Brace External loading
strut elev applied to strut line
--------- ----- --------------------------- --------- --------- ---------
PLANE SWA:
Line 6
0.000 Transfered from roof
Tier 1 16.00' 0.700 TOTAL
0.938 @ FRAME LINE 1
-0.238 @ FRAME LINE 4
16.000' Transfered = 0.000 Stability By Other Const.
--------- ----- --------------------------- --------- --------- ---------
kips
Metallic Page: 17
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** RPA LEANTO ROOF LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Windforce-resistance System Per:
2016 ASCE 7
Longitudinal wind loading case 2
(Endwall EWD is windward endwall)
100 mph Main framing wind load and coefficients
Partially Enclosed Building, Normal Building Category, EXPOSURE C
90% of endwall surfaces in interior zone
10% of endwall surfaces in end zone within 6 feet of wall corners
Velocity pressure coefficient ( Kh )................................ 0.928588
Ground Elevation Factor ( Ke )...................................... 0.996603
Directionality Factor ( Kd )........................................ 0.85
Basic Pressure ( Qh )............................................... 20.13743
Topographic factor - at mean roof height = 1.0000
Windward wall...................... [GCpf-GCpi]= 0.9703 P= 19.540 psf
Leeward wall....................... [GCpf-GCpi]= 0.2465 P= 4.963 psf
Roof Brace External loading .6*W Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPA:
6 0.700 TOTAL
-0.238 @ FRAME LINE 1
0.938 @ FRAME LINE 4 0.5000" ROD
12.000' Transfered = 0.420 0.00 0.50 4.79
--------- ----- --------------------------- ------ ------ ------
Metallic Page: 18
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** SWA LEANTO SIDEWALL LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Brace External loading
strut elev applied to strut line
--------- ----- --------------------------- --------- --------- ---------
PLANE SWA:
Line 6
0.000 Transfered from roof
Tier 1 16.00' 0.700 TOTAL
-0.238 @ FRAME LINE 1
0.938 @ FRAME LINE 4
16.000' Transfered = 0.000 Stability By Other Const.
--------- ----- --------------------------- --------- --------- ---------
kips
Metallic Page: 19
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** RPA LEANTO ROOF LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Seismic-resistance System Per:
2016 ASCE 7
Longitudinal seismic loading case 1
(PLANE EWB endwall to opposite endwall is force direction)
Soil Profile Type................................................... D
Seismic design category............................................. D
Mapped spectral response accel. for short periods (Ss).............. 1.183
Mapped spectral response accel. for 1 second periods (S1)........... 0.425
Design, 5% damped, spectral response accel. at short periods (Sds).. 0.9464
Design, 5% damped, spectral response accel. at period 1 sec. (Sd1).. 0.53125
Sds and Sd1 values.............................................Code-Calculated
Longitudinal Building Period (T).................................... 0.209
Seismic Reliability/Redundancy Factor............................... 1.3
Seismic Importance Factor (I)....................................... 1
Building minimum longitudinal R value............................... 3.25
Building minimum transverse R value................................. 3.25
Roof dead load included in Seismic force "W" (psf) ................. 4.648
Roof collateral load included in Seismic force "W" (psf) ........... 1.000
Roof Brace External loading (W) .7rhoV Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPA:
6 2.743 TOTAL
0.068 @ FRAME LINE 2, 3
0.869 @ BAY 1, 2, 3 0.5000" ROD
12.000' Transfered = 2.743 0.73 0.00 0.86 4.79
--------- ----- --------------------------- ------ ------ ------ ------
- Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
Roof bracing load E=rhoV; rho=1.30
Metallic Page: 20
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** SWA LEANTO SIDEWALL LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Brace External loading
strut elev applied to strut line
--------- ----- --------------------------- --------- --------- ---------
PLANE SWA:
Line 6
0.000 Transfered from roof
Tier 1 16.00' 2.743 TOTAL
0.068 @ FRAME LINE 2, 3
0.869 @ BAY 1, 2, 3
16.000' Transfered = 0.000 Stability By Other Const.
--------- ----- --------------------------- --------- --------- ---------
kips
Metallic Page: 21
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** RPA LEANTO ROOF LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
ROOF STRUT LOADING AND FORCE TRANSMISSION
Main Code Requirements Per:
2019 California Building Code
(Reference 2018 International Building Code)
Seismic-resistance System Per:
2016 ASCE 7
Longitudinal seismic loading case 2
(PLANE EWD endwall to opposite endwall is force direction)
Soil Profile Type................................................... D
Seismic design category............................................. D
Mapped spectral response accel. for short periods (Ss).............. 1.183
Mapped spectral response accel. for 1 second periods (S1)........... 0.425
Design, 5% damped, spectral response accel. at short periods (Sds).. 0.9464
Design, 5% damped, spectral response accel. at period 1 sec. (Sd1).. 0.53125
Sds and Sd1 values.............................................Code-Calculated
Longitudinal Building Period (T).................................... 0.209
Seismic Reliability/Redundancy Factor............................... 1.3
Seismic Importance Factor (I)....................................... 1
Building minimum longitudinal R value............................... 3.25
Building minimum transverse R value................................. 3.25
Roof dead load included in Seismic force "W" (psf) ................. 4.648
Roof collateral load included in Seismic force "W" (psf) ........... 1.000
Roof Brace External loading (W) .7rhoV Brc T Brc T Brc
strut spans applied to strut line Total /bay Allow
--------- ----- --------------------------- ------ ------ ------ ------
PLANE RPA:
6 2.743 TOTAL
0.068 @ FRAME LINE 2, 3
0.869 @ BAY 1, 2, 3 0.5000" ROD
12.000' Transfered = 2.743 0.73 0.00 0.86 4.79
--------- ----- --------------------------- ------ ------ ------ ------
- Using ASCE7-16 Eq(12.8-2) Sds/(R/I)W ; R=3.25
Roof bracing load E=rhoV; rho=1.30
Metallic Page: 22
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** SWA LEANTO SIDEWALL LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
WALL STRUT LOADING AND FORCE TRANSMISSION
Brace External loading
strut elev applied to strut line
--------- ----- --------------------------- --------- --------- ---------
PLANE SWA:
Line 6
0.000 Transfered from roof
Tier 1 16.00' 2.743 TOTAL
0.068 @ FRAME LINE 2, 3
0.869 @ BAY 1, 2, 3
16.000' Transfered = 0.000 Stability By Other Const.
--------- ----- --------------------------- --------- --------- ---------
kips
Metallic Page: 23
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** RPA LEANTO ROOF LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
ROOF STRUT LINE DESIGN
BLDG-B ROOF BRACING EAVE STRUT NO. 6
ANALYSIS OF EAVE STRUT LINE 1 ON ROOF PLANE RPC
LOAD COMBINATIONS : 1) 0.60D + 0.60W3-1 2) 0.60D + 0.60W3-2
3) 0.60D + 0.60W4-1 4) 0.60D + 0.60W4-2
5) D + C + 3/4L + 0.45W3-1 6) D + C + 3/4L + 0.45W3-2
7) D + C + 3/4L + 0.45W4-1 8) D + C + 3/4L + 0.45W4-2
9) D + C + 0.45W3-1 10) D + C + 0.45W3-2
11) D + C + 0.45W4-1 12) D + C + 0.45W4-2
13) 1.13D + 1.13C + 1.40E4-1 14) 1.13D + 1.13C + 1.40E3-1
WHERE : D = Dead load
C = Collateral load
L = Live load
W3-1= Wind Case 1, Positive internal pressure
W3-2= Wind Case 1, Negative internal pressure
W4-1= Wind Case 2, Positive internal pressure
W4-2= Wind Case 2, Negative internal pressure
E4-1= Seismic load Case 2
E3-1= Seismic load Case 1
Span Length Member, Avg Spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
LE 2.333 8X3.5E14 2.500 6 0.249 crippling
6 L/ 205 deflection
3 19.667 8X3.5E14 2.500 6 0.381 crippling
& 2 discrete brace pt 6 L/ 639 deflection
Total line design weight is 93.9 lbs.
Metallic Page: 24
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** RPA LEANTO ROOF LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
ROOF STRUT LINE DESIGN
BLDG-B ROOF BRACING EAVE STRUT NO. 6
ANALYSIS OF EAVE STRUT LINE 1 ON ROOF PLANE RPC
LOAD COMBINATIONS : 1) 0.60D + 0.60W3-1 2) 0.60D + 0.60W3-2
3) 0.60D + 0.60W4-1 4) 0.60D + 0.60W4-2
5) D + C + 3/4L + 0.45W3-1 6) D + C + 3/4L + 0.45W3-2
7) D + C + 3/4L + 0.45W4-1 8) D + C + 3/4L + 0.45W4-2
9) D + C + 0.45W3-1 10) D + C + 0.45W3-2
11) D + C + 0.45W4-1 12) D + C + 0.45W4-2
13) 1.13D + 1.13C + 1.40E4-1 14) 1.13D + 1.13C + 1.40E3-1
WHERE : D = Dead load
C = Collateral load
L = Live load
W3-1= Wind Case 1, Positive internal pressure
W3-2= Wind Case 1, Negative internal pressure
W4-1= Wind Case 2, Positive internal pressure
W4-2= Wind Case 2, Negative internal pressure
E4-1= Seismic load Case 2
E3-1= Seismic load Case 1
Span Length Member, Avg Spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
2 20.000 8X3.5E14 2.500 simple span 8 0.393 crippling
& 2 discrete brace pt 8 L/ 587 deflection
Total line design weight is 85.4 lbs.
Metallic Page: 25
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:53
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** RPA LEANTO ROOF LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
ROOF STRUT LINE DESIGN
BLDG-B ROOF BRACING EAVE STRUT NO. 6
ANALYSIS OF EAVE STRUT LINE 1 ON ROOF PLANE RPC
LOAD COMBINATIONS : 1) 0.60D + 0.60W3-1 2) 0.60D + 0.60W3-2
3) 0.60D + 0.60W4-1 4) 0.60D + 0.60W4-2
5) D + C + 3/4L + 0.45W3-1 6) D + C + 3/4L + 0.45W3-2
7) D + C + 3/4L + 0.45W4-1 8) D + C + 3/4L + 0.45W4-2
9) D + C + 0.45W3-1 10) D + C + 0.45W3-2
11) D + C + 0.45W4-1 12) D + C + 0.45W4-2
13) 1.13D + 1.13C + 1.40E4-1 14) 1.13D + 1.13C + 1.40E3-1
WHERE : D = Dead load
C = Collateral load
L = Live load
W3-1= Wind Case 1, Positive internal pressure
W3-2= Wind Case 1, Negative internal pressure
W4-1= Wind Case 2, Positive internal pressure
W4-2= Wind Case 2, Negative internal pressure
E4-1= Seismic load Case 2
E3-1= Seismic load Case 1
Span Length Member, Avg Spacing Bearing Controlling Conditions
No. (feet) & Ext. Lengths (feet) StifReq Combination & Check Ratio
---- ------ ---------------------------- ------- -------------------------
1 19.667 8X3.5E14 2.500 8 0.381 crippling
& 2 discrete brace pt 8 L/ 639 deflection
RE 2.333 8X3.5E14 2.500 8 0.249 crippling
8 L/ 205 deflection
Total line design weight is 93.9 lbs.
Metallic Page: 26
Bracing Design Program User: mmfarahani Job Number: 31650A
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:46:54
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
**** LEANTO LONGITUDINAL BRACING DESIGN AT WALL PLANE SWA ****
LONGITUDINAL BRACING DESIGN SUMMARY
Roof Bracing:
Brace Bay 1 Bay 2 Bay 3
Strut Spans 20.000 feet 20.000 feet 20.000 feet
---------- ----- ------------- ------------- -------------
PLANE RPA:
6 8X3.5E14 8X3.5E14 8X3.5E14
12.000' 0.5000" ROD
---------- ----- ------------- ------------- -------------
Brace Bay 1 Bay 2 Bay 3
Sidewall Bracing:
Metallic Building Systems User: mmfarahani Page: F5- 1
R-Frame Design Program - Version V8.15 Job : 31650A
Input Data Echo File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
--------------------------------------------------------------------------------
VERSION V8.15
BRAND METALLIC
DESCRIPTION pf 19.667/20. main building at plane SWA
FRAME_ID 5
PRINT echo code summary detail react profile deflect base conn flg_brace \
stiff seismic
DATASET base brace combinations connection members wind_array
OPTIMIZATION depth *PLANT ATW *JOB 31650A
LOCATION bays 3-(Gridline B) *NUMBER FRAMES 1 *PRICE summary
LATERAL GRID LABEL B
LONGITUDINAL GRID LABEL LEFT RIGHT
FRAME TYPE pf p cs 60.00 60.00
WIDTH 19.667
EAVE HEIGHT 20.
GIRT DEPTH 0. 4.25 *PURLIN DEPTH 0. 14.
BUILDING CODE IB18 U=Normal P=N
SEISMIC LOAD S1=42.5 Ss=118.3 TL=16.0 %CR=NORM %SR=NORM RHO=1.3 R=3.25 \
CT=0.028 CD=3.0 TOF=2.5 LOF=2.5
SOIL PROFILE D
CODE LABEL 2019 California Building Code
DEFLECTION WALL L=60 S=60 E=40 C=100 G=60 W=60 TE=40
SYMMETRICAL
LOADS
LC LWL1 GLOB X C 18.833 6.518 0.000
RC LWL2 GLOB X C 18.833 -6.518 0.000
LC LWL1D GLOB X C 18.833 2.926 0.000
RC LWL2D GLOB X C 18.833 -2.926 0.000
LC LEQ GLOB X C 18.833 6.439 0.000
END
Metallic Building Systems User: mmfarahani Page: F5- 2
R-Frame Design Program - Version V8.15 Job : 31650A
Building Grid label legend File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Building Grid Label Legend
==========================
Building :
Frame Number : 5
No. of Frames : 1
Left Column : Column @ * - LEFT
Right Column : Column @ * - RIGHT
*Frames located @ B
Metallic Building Systems User: mmfarahani Page: F5- 3
R-Frame Design Program - Version V8.15 Job : 31650A
Code Summary Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Building :
Frame Number :5 Location: bays 3-(Gridline B)
No. of Frames: 1
2019 CALIFORNIA BUILDING CODE
Main Code Requirements Per :
International Building Code
2018 Edition
Supporting Design Manual(s):
2016 AISC Specification for Structural Steel Buildings,Allowable Strength Design
2010 AISC Seismic Provisions for Structural Steel Buildings
Frame Data
----------
Eave height Left & Right (feet)..................................... 20.000
Horizontal width from left to right steel line (feet)............... 19.667
Horizontal distance to ridge from left side (feet).................. 19.667
Roof Slope Left & Right (rise:12)................................... 0.000
Column Slope Left & Right (lat:12).................................. 0.000
Purlin depth left & right side (inches)............................. 0.000
Frame Rafter Inset left & right side (inches)....................... 14.000
Girt depth left & right side (inches)............................... 0.000
Frame Column Inset left & right side (inches)....................... 4.250
Tributary Width left & right side (feet)............................ 0.000
..................................from Height 0.00 to Height 0.00
Tributary Width roof (feet)......................................... 0.000
Tension Flange Bolt Hole Reduction.................................. Yes
Tension Field Action at Knee........................................ Yes
Second order analysis method........................................ C2.2b
Frame Design Loads
------------------
Ground Snow Load Entered [Pg] (psf)................................. 0.000
Snow Exposure Factor [Ce] .......................................... 1.000
Snow Importance Factor [I] -- Standard Use Category................. 1.000
Snow Thermal Factor Used [Ct]Heated Building........................ 1.000
Slippery & Unobstructed Roof Surface................................ Yes
Roof Snow Load [Pf = I*Pg] (psf).................................... 0.000
Snow Slope Factor [Cs].............................................. 1.000
Sloped Roof Snow Load Used [Ps = Cs*Pf] (psf)....................... 0.000
UNBALANCED SNOW LOADING(s)
--------------------------
No Unbalanced Roof Snow Loadings.
Metallic Building Systems User: mmfarahani Page: F5- 4
R-Frame Design Program - Version V8.15 Job : 31650A
Wind Summary Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
Eave height Left & Right (feet)..................................... 20.000
Wind Elevation on left column (feet)................................ 20.000
Wind Elevation on right column (feet)............................... 20.000
Total frame width (feet)............................................ 19.667
Number of primary wind loadings .................................... 4
Building Enclosure Classification ............................. Partially Open
Metallic Building Systems User: mmfarahani Page: F5- 5
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Wind Summary Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Windforce-resisting system Per :
ASCE 7 Standard
2016 Edition
*** PRIMARY WIND COEFFICIENTS FOR MAIN FRAME ***
--------------------------------------------------------------------------------
Wind Load User entered coefficient
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.000 0.000( 0.0%) 0.000(100.0%) 0.000
--------------------------------------------------------------------------------
Wind Load User entered coefficient
******************* Left Wall Left Rafter Right Rafter Right Wall
Primary Coeff. (Cp) 0.000 0.000( 0.0%) 0.000(100.0%) 0.000
--------------------------------------------------------------------------------
Notes :
1. Wind coefficients applied to the roof may be located as a percentage
of the total frame width (xx.x%). If not shown the coefficients are
applied fully to their respective rafter.
Deflection Design Limits >>
---------------------------
Rafter deflection limit for Live load only [L/{x}] ................. NONE
Rafter deflection limit for Snow load only [L/{x}] ................. NONE
Rafter deflection limit for Serviceability Wind load only [L/{x}] .. NONE
Rafter deflection limit for Gravity load conditions [L/{x}] ........ NONE
Column sway deflection limit for Live load only [L/{x}] ............ 60.000
Column sway deflection limit for Snow load only [L/{x}] ............ 60.000
Column sway deflection limit for Serviceability Wind load only [L/{x}] 60.000
Column sway deflection limit for Seismic load only [L/{x}] ......... 40.000
Column sway deflection limit for Crane load conditions [L/{x}] ..... 100.000
Column sway deflection limit for Gravity load conditions [L/{x}] ... 60.000
Column sway deflection limit for Seismic load conditions [L/{x}] ... 40.000
Metallic Building Systems User: mmfarahani Page: F5- 6
R-Frame Design Program - Version V8.15 Job : 31650A
Load Combinations Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Load Combination :
------------------
1) DL (SOA-L) N A P
2) DL (SOA-R) N A P
3) 1.1325DL +0.91LEQ (SOA-L) N A P
4) 1.1325DL +0.91LEQ (SOA-R) N A P
5) 1.1325DL -0.91LEQ (SOA-L) N A P
6) 1.1325DL -0.91LEQ (SOA-R) N A P
7) 0.4675DL +0.91LEQ (SOA-L) N A P
8) 0.4675DL +0.91LEQ (SOA-R) N A P
9) 0.4675DL -0.91LEQ (SOA-L) N A P
10) 0.4675DL -0.91LEQ (SOA-R) N A P
11) 0.7107DL +2.5LEQ (SOA-L) N C R P
12) 0.7107DL +2.5LEQ (SOA-R) N C R P
13) 0.7107DL -2.5LEQ (SOA-L) N C R P
14) 0.7107DL -2.5LEQ (SOA-R) N C R P
15) 1.3893DL +2.5LEQ (SOA-L) N C R P
16) 1.3893DL +2.5LEQ (SOA-R) N C R P
17) 1.3893DL -2.5LEQ (SOA-L) N C R P
18) 1.3893DL -2.5LEQ (SOA-R) N C R P
19) 0.7107DL +2.5LEQ (SOA-L) N B R P
20) 0.7107DL +2.5LEQ (SOA-R) N B R P
21) 0.7107DL -2.5LEQ (SOA-L) N B R P
22) 0.7107DL -2.5LEQ (SOA-R) N B R P
23) 1.3893DL +2.5LEQ (SOA-L) N B R P
24) 1.3893DL +2.5LEQ (SOA-R) N B R P
25) 1.3893DL -2.5LEQ (SOA-L) N B R P
26) 1.3893DL -2.5LEQ (SOA-R) N B R P
27) 0.7107DL +3.25LEQ (SOA-L) N K R P
28) 0.7107DL +3.25LEQ (SOA-R) N K R P
29) 0.7107DL -3.25LEQ (SOA-L) N K R P
30) 0.7107DL -3.25LEQ (SOA-R) N K R P
31) 1.3893DL +3.25LEQ (SOA-L) N K R P
32) 1.3893DL +3.25LEQ (SOA-R) N K R P
33) 1.3893DL -3.25LEQ (SOA-L) N K R P
34) 1.3893DL -3.25LEQ (SOA-R) N K R P
35) DL +0.6LWL1 (SOA-L) N A P
36) DL +0.6LWL1 (SOA-R) N A P
37) DL +0.6LWL2 (SOA-L) N A P
38) DL +0.6LWL2 (SOA-R) N A P
39) 0.6DL +0.6LWL1 (SOA-L) N A P
40) 0.6DL +0.6LWL1 (SOA-R) N A P
41) 0.6DL +0.6LWL2 (SOA-L) N A P
42) 0.6DL +0.6LWL2 (SOA-R) N A P
43) LWL1D (deflection only) D
44) LWL2D (deflection only) D
45) 1.3893DL+LEQ (deflection only) D E
46) 1.3893DL-LEQ (deflection only) D E
47) 0.7107DL+LEQ (deflection only) D E
48) 0.7107DL-LEQ (deflection only) D E
Metallic Building Systems User: mmfarahani Page: F5- 7
R-Frame Design Program - Version V8.15 Job : 31650A
Continue Load Comb Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Where :
-------
DL = Roof Dead Load
LEQ = Longitudinal Seismic Load
LWL1 = Wind from Left to Right with +GCpi
LWL2 = Wind from Right to Left with -GCpi
LWL1D = Wind from Left to Right with +GCpi at Service Level
LWL2D = Wind from Right to Left with -GCpi at Service Level
Combination Descriptions :
--------------------------
N= No 1/3 Increase in Allowable for Combination
B= Base Only Combination
K= Knee Connection Only Combination
A= Allowable Strength Design Combination - ASD16
C= Column Only Combination for Seismic
D= Deflection Only Combination
P= Second Order Analysis Combination - SOA
R= Load and Resistance Factor Design Combination - LRFD
E= Cd is applied and Ie is omitted from frame drift calculations
Metallic Building Systems User: mmfarahani Page: F5- 8
R-Frame Design Program - Version V8.15 Job : 31650A
User Load Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
* USER INPUT LOADS
-------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
1 LC LWL1 GLOB X C 18.833 6.5180 0.0000 0.000
2 RC LWL2 GLOB X C 18.833 -6.5180 0.0000 0.000
3 LC LWL1D GLOB X C 18.833 2.9260 0.0000 0.000
4 RC LWL2D GLOB X C 18.833 -2.9260 0.0000 0.000
5 LC LEQ GLOB X C 18.833 6.4390 0.0000 0.000
Metallic Building Systems User: mmfarahani Page: F5- 9
R-Frame Design Program - Version V8.15 Job : 31650A
Seismic Summary Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
2019 CALIFORNIA BUILDING CODE
Main Seismic Force Resisting System Per :
ASCE 7 Standard
2016 Edition
Standard Risk Category Building for Seismic Loadings
Seismic Loads Required for Building ................................ Yes
Response Acceleration Coeff., for Short Periods [Ss] (%g) .......... 118.3000
Response Acceleration Coeff., for 1 sec. Periods [S1] (%g) ......... 42.5000
Long-period Transition Period Time [TL] (seconds) .................. 16.0000
Seismic Design Category ............................................ D
Soil Profile Type .................................................. D
Seismic Site Coefficient [Fa] ...................................... 1.2000
Seismic Site Coefficient [Fv] ...................................... 1.8750
Maximum Spectral Response Accel., for Short Periods [Sms] (g) ...... 1.4196
Maximum Spectral Response Accel., for 1 sec. Periods [Sm1] (g) ..... 0.7969
Design Spectral Response Accel., for Short Periods [Sds] (g) ....... 0.9464
Design Spectral Response Accel., for 1 sec. Periods [Sd1] (g) ...... 0.5312
Sds and Sd1 values .......................................... Code-calculated
Seismic Response Modification Factor [R] ........................... 3.2500
Seismic Importance Factor [I] ...................................... 1.0000
Storage/Equipment Areas and/or Service Rooms Exist ................. No
Seismic Story Height [hn] (feet) ................................... 20.0000
Seismic Fundamental Period [T] Used (seconds) ...................... 0.3076
Longitudinal Seismic Overstrength Factor [OMEGA] ................... 2.5000
Seismic Overstrength Factor [OMEGAo] ............................... 2.5000
Longitudinal Seismic Redundancy/Reliability Factor [L-rho] ......... 1.3000
Seismic Redundancy/Reliability Factor [rho] ........................ 1.3000
Snow in Seismic Force Calculations [Used] (%) ...................... 0.00
Snow in Seismic Force Calculations [Min. Required] (%) ............. 0.00
Snow in Seismic Load Combinations [Used] (%) ....................... 0.00
Snow in Seismic Load Combinations [Min. Required] (%) .............. 0.00
Mezz. Live load in Seismic Force Calculations [Used] (%) ........... 0.00
Mezz. Live load in Seismic Force Calculations [Min. Required] (%) .. 0.00
Mezz. Live load in Seismic Load Combinations [Used] (%) ............ 100.00
Mezz. Live load in Seismic Load Combinations [Min. Required] (%) ... 100.00
Building Height Limit (feet) ....................................... 65.0000
Seismic Story Drift Limit Factor ................................... 0.0250
Seismic Story Drift Limit (in) ..................................... 6.0000
Seismic Deflection Amplification Factor [Cd] ....................... 3.0000
Seismic Response Coefficient [Cs] Used ............................. 0.2912
Roof Dead Load = 1.466
Wall Weight = 0.000
Collateral Load = 0.000
Snow Load = 0.000
Rafter Crane Weight = 0.000
-------------------------------------
Total Roof Weight = 1.466 kips
Total Roof Weight = 1.466
Mezzanine Weight = 0.000
Col. Crane Weight = 0.000
-------------------------------------
TOTAL Bldg Weight = 1.466 kips
X X
Seismic Coeff. = 0.2912
-------------------------------------
BASE SHEAR = 0.4268 kips
Seismic Load for Roof at col # 1 = 0.2134 kips
Seismic Load for Roof at col # 2 = 0.2134 kips
---------------------------------------------------
SEISMIC LOAD for Roof in TOTAL = 0.4268 kips
* SEISMIC GENERAL LOAD CARDS GENERATED
--------------------------------------
LOAD MEM NAME SYS DIR TYP DISTANCE INTENSITY LENGTH
NO. START END
9 LC LEQ YREF X C 18.104 0.2134 N/A 0.000
10 RC LEQ YREF X C 18.104 0.2134 N/A 0.000
Metallic Building Systems User: mmfarahani Page: F5- 10
R-Frame Design Program - Version V8.15 Job : 31650A
Forces and Allowable Stresses Summary File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Left Column Analysis Length = 18.10 ft Kx = 1.00 Weight = 483. lbs
Effective Ix = 461.4 in4
Part Length Web Height at Outer Flange Web Inner Flange Taper Fy
No. (ft) Start(in) End(in) (in) Thick (in) Angle (ksi)
1 10.00 17.500 17.500 6.00x 0.2500 0.1560 6.00x 0.3125 0.00 55.0
2 7.29 17.500 17.500 6.00x 0.3750 0.3125 6.00x 0.3750 0.00 55.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
107 6.7 31.3 3.1 32.9 12.1 34.9 10.3 0.11 0.90 0.29 0.90 8
206 -7.2 -54.7 -3.1 4.0 38.6 15.1 19.8 0.03 0.40 0.89 0.89 5
--------------------------------------------------------------------------------
Left Rafter Analysis Length = 17.44 ft Kx = 1.00 Weight = 367. lbs
Effective Ix = 356.0 in4
Part Length Web Height at Outer Flange Web Inner Flange Taper Fy
No. (ft) Start(in) End(in) (in) Thick (in) Angle (ksi)
3 15.92 18.000 18.000 6.00x 0.3125 0.1560 6.00x 0.2500 0.00 55.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
310 -3.0 -54.5 -7.1 4.4 35.0 22.8 10.0 0.25 0.51 0.85 0.85 4
--------------------------------------------------------------------------------
Right Column Analysis Length = 18.10 ft Kx = 1.00 Weight = 483. lbs
Effective Ix = 461.4 in4
Part Length Web Height at Outer Flange Web Inner Flange Taper Fy
No. (ft) Start(in) End(in) (in) Thick (in) Angle (ksi)
4 10.00 17.500 17.500 6.00x 0.2500 0.1560 6.00x 0.3125 0.00 55.0
5 7.29 17.500 17.500 6.00x 0.3750 0.3125 6.00x 0.3750 0.00 55.0
--------------------------------------------------------------------------------
Point ---Actual Forces---- --Allowable Stresses-- -------Unity Checks--------
No. Axial Moment Shear Fa Fbo Fbi Fv Shear Axial+Bend Comb Load
(kip) (k-ft) (kip) (ksi) (ksi) (ksi) (ksi) Oflg Iflg Max Comb
--------------------------------------------------------------------------------
407 6.7 32.8 3.3 32.9 12.1 34.9 10.3 0.11 0.94 0.30 0.94 9
506 -7.2 -57.2 -3.3 4.0 38.6 15.1 19.8 0.03 0.42 0.92 0.92 4
--------------------------------------------------------------------------------
TOTAL MEMBER WEIGHT = 1332. lbs
Metallic Building Systems User: mmfarahani Page: F5- 11
R-Frame Design Program - Version V8.15 Job : 31650A
Reactions Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
General Reaction Notes :
----------------------
1. Vertical column reactions are positive in the upward direction.
2. Transverse horizontal column reactions are positive to the right on all
columns.
3. Longitudinal horizontal reactions are perpendicular to the transverse
horizontal reactions, and the positive direction is inward to the page.
4. Fixed base moments are positive in the counter-clockwise direction on
all columns.
5. Reactions for a particular load combination may be obtained by summing-up
individual load reactions that have been multiplied by their load factors.
6. Forces on the foundations will act in the opposite direction to the
direction of the column reactions.
7. These reactions are from loads determined from the applicable code for ASD
design. Seismic loads are limit state and include magnification factors when
so required by the seismic provisions of the applicable code for ASD design.
It is the responsibility of the foundation designer to apply the load factors
and load combinations appropriate for the concrete foundation design.
8. Seismic overstrength factor is not included in the LEQ Load Group reactions.
Seismic BASE-ONLY comb. reactions include an overstrength factor of: 2.500
Reactions for Load Combinations
-------------------------------
Vertical Horizontal Longi-
Load Reaction Reaction tudinal Moment
Comb. Member (Kips) (Kips) (Kips) (Kip-Ft)
----- ------ -------- -------- -------- ------
1 Left Column 0.669 0.019 0.000 0.000
Right Column 0.664 -0.017 0.000 0.000
2 Left Column 0.664 0.017 0.000 0.000
Right Column 0.669 -0.019 0.000 0.000
3 Left Column -5.863 -2.957 0.000 0.000
Right Column 7.372 -3.147 0.000 0.000
4 Left Column -6.163 -3.101 0.000 0.000
Right Column 7.672 -3.291 0.000 0.000
5 Left Column 7.673 3.142 0.000 0.000
Right Column -6.164 3.250 0.000 0.000
6 Left Column 7.371 2.998 0.000 0.000
Right Column -5.862 3.106 0.000 0.000
7 Left Column -6.308 -2.970 0.000 0.000
Right Column 6.931 -3.136 0.000 0.000
8 Left Column -6.604 -3.112 0.000 0.000
Right Column 7.226 -3.278 0.000 0.000
Metallic Building Systems User: mmfarahani Page: F5- 12
R-Frame Design Program - Version V8.15 Job : 31650A
Reactions Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Reactions for Load Combinations
-------------------------------
Vertical Horizontal Longi-
Load Reaction Reaction tudinal Moment
Comb. Member (Kips) (Kips) (Kips) (Kip-Ft)
----- ------ -------- -------- -------- ------
9 Left Column 7.227 3.129 0.000 0.000
Right Column -6.604 3.261 0.000 0.000
10 Left Column 6.931 2.987 0.000 0.000
Right Column -6.308 3.119 0.000 0.000
11 Left Column -17.011 -7.834 0.000 0.000
Right Column 17.958 -8.269 0.000 0.000
12 Left Column -19.226 -8.895 0.000 0.000
Right Column 20.173 -9.331 0.000 0.000
13 Left Column 20.176 8.923 0.000 0.000
Right Column -19.229 9.306 0.000 0.000
14 Left Column 17.955 7.858 0.000 0.000
Right Column -17.008 8.243 0.000 0.000
15 Left Column -16.551 -7.818 0.000 0.000
Right Column 18.402 -8.278 0.000 0.000
16 Left Column -18.781 -8.886 0.000 0.000
Right Column 20.632 -9.347 0.000 0.000
17 Left Column 20.635 8.939 0.000 0.000
Right Column -18.784 9.297 0.000 0.000
18 Left Column 18.400 7.867 0.000 0.000
Right Column -16.548 8.227 0.000 0.000
19 Left Column -17.011 -7.834 0.000 0.000
Right Column 17.958 -8.269 0.000 0.000
20 Left Column -19.226 -8.895 0.000 0.000
Right Column 20.173 -9.331 0.000 0.000
21 Left Column 20.176 8.923 0.000 0.000
Right Column -19.229 9.306 0.000 0.000
22 Left Column 17.955 7.858 0.000 0.000
Right Column -17.008 8.243 0.000 0.000
23 Left Column -16.551 -7.818 0.000 0.000
Right Column 18.402 -8.278 0.000 0.000
24 Left Column -18.781 -8.886 0.000 0.000
Right Column 20.632 -9.347 0.000 0.000
Metallic Building Systems User: mmfarahani Page: F5- 13
R-Frame Design Program - Version V8.15 Job : 31650A
Reactions Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Reactions for Load Combinations
-------------------------------
Vertical Horizontal Longi-
Load Reaction Reaction tudinal Moment
Comb. Member (Kips) (Kips) (Kips) (Kip-Ft)
----- ------ -------- -------- -------- ------
25 Left Column 20.635 8.939 0.000 0.000
Right Column -18.784 9.297 0.000 0.000
26 Left Column 18.400 7.867 0.000 0.000
Right Column -16.548 8.227 0.000 0.000
27 Left Column -21.827 -9.983 0.000 0.000
Right Column 22.774 -10.540 0.000 0.000
28 Left Column -25.565 -11.772 0.000 0.000
Right Column 26.512 -12.332 0.000 0.000
29 Left Column 26.517 11.802 0.000 0.000
Right Column -25.570 12.307 0.000 0.000
30 Left Column 22.769 10.005 0.000 0.000
Right Column -21.822 10.513 0.000 0.000
31 Left Column -21.365 -9.966 0.000 0.000
Right Column 23.217 -10.548 0.000 0.000
32 Left Column -25.122 -11.764 0.000 0.000
Right Column 26.973 -12.349 0.000 0.000
33 Left Column 26.978 11.819 0.000 0.000
Right Column -25.127 12.299 0.000 0.000
34 Left Column 23.212 10.013 0.000 0.000
Right Column -21.361 10.497 0.000 0.000
35 Left Column -3.520 -1.859 0.000 0.000
Right Column 4.853 -1.995 0.000 0.000
36 Left Column -3.640 -1.916 0.000 0.000
Right Column 4.972 -2.052 0.000 0.000
37 Left Column 4.972 2.052 0.000 0.000
Right Column -3.640 1.916 0.000 0.000
38 Left Column 4.853 1.995 0.000 0.000
Right Column -3.520 1.859 0.000 0.000
39 Left Column -3.788 -1.867 0.000 0.000
Right Column 4.587 -1.988 0.000 0.000
40 Left Column -3.905 -1.923 0.000 0.000
Right Column 4.705 -2.044 0.000 0.000
Metallic Building Systems User: mmfarahani Page: F5- 14
R-Frame Design Program - Version V8.15 Job : 31650A
Reactions Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Reactions for Load Combinations
-------------------------------
Vertical Horizontal Longi-
Load Reaction Reaction tudinal Moment
Comb. Member (Kips) (Kips) (Kips) (Kip-Ft)
----- ------ -------- -------- -------- ------
41 Left Column 4.705 2.044 0.000 0.000
Right Column -3.905 1.923 0.000 0.000
42 Left Column 4.587 1.988 0.000 0.000
Right Column -3.788 1.867 0.000 0.000
43 Left Column -3.177 -1.426 0.000 0.000
Right Column 3.177 -1.500 0.000 0.000
44 Left Column 3.177 1.500 0.000 0.000
Right Column -3.177 1.426 0.000 0.000
45 Left Column -6.511 -3.326 0.000 0.000
Right Column 8.362 -3.540 0.000 0.000
46 Left Column 8.362 3.376 0.000 0.000
Right Column -6.511 3.490 0.000 0.000
47 Left Column -6.963 -3.338 0.000 0.000
Right Column 7.910 -3.528 0.000 0.000
48 Left Column 7.910 3.364 0.000 0.000
Right Column -6.963 3.502 0.000 0.000
Metallic Building Systems User: mmfarahani Page: F5- 15
R-Frame Design Program - Version V8.15 Job : 31650A
Anchor Rod and Base Plate Design File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
BOTH EXTERIOR COLUMNS ANCHOR RODS AND BASE PLATE DESIGN
=======================================================
Anchor Rod & Base Plate Design Sizes >>
---------------------------------------
Use ( 4)- 0.750 in. Dia. F1554, Gr. 36 Anchor Rods
Rod Gage : 4.000 in. Rod Spacing (in.): 3.0000, 1 @ 4.0000, 11.0625
Plate Size : 6.0000 x 18.0625 x 0.3750 in. (Width x Depth x Thickness)
Controlling Reactions for Anchor Rod Design >>
----------------------------------------------
Shear Tension Allowable Load Check
Loading Type (kips) (kips) (kips) No. Ratio
-----------------------------------------------------------------
Rod Tension 0.000 19.229 57.653 21 0.33
Rod Shear 9.347 0.000 34.592 24 0.27
Standard Base Plate Welding >> (Using E70 Electrodes)
------------------------------
Fillet Weld Weld Weld Design Weld
Weld Size Length Capacity Force Load Check
Location (in.) (in.) (kips) (kips) No. Ratio
------------------------------------------------------------------
Inner Flg 0.31250 6.000 41.763 5.906 21 0.14
Outer Flg 0.25000 6.000 33.411 4.725 21 0.14
Web Plate 0.18750 17.500 73.086 12.670 21 0.17
Metallic Building Systems User: mmfarahani Page: F5- 16
R-Frame Design Program - Version V8.15 Job : 31650A
Connection Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Vertical Knee Connection @ Both Sides
--------------------------------------------------------------------------------
BOLTS A325 H.S. - Fully Tightened
(O.S.) 2 rows Extended - 1 in. Dia. - Standard (2 bolts per row)
(I.S.) 2 rows Extended - 1 in. Dia. - Standard (2 bolts per row)
Left Side of Conn Data: Right Side of Conn Data:
----------------------- ------------------------
Plate: 8.00 x 1.0000 in. Plate: 8.00 x 1.0000 in.
Fy(Min) 50.0 ksi Fy(Min) 50.0 ksi
Fu 65.0 ksi Fu 65.0 ksi
Flanges: Flanges:
O.S. - 6.00 x 0.3125 in. O.S. - 6.00 x 0.3125 in.
I.S. - 5.81 x 0.2500 in. I.S. - 6.00 x 0.2500 in.
Web Depth - 18.000 in. Web Depth - 18.000 in.
Web Thickness 0.312 in. Web Thickness 0.156 in.
Gage - 3.500 in. Gage - 3.500 in.
Center of Bolt to Flange: Center of Bolt to Flange:
Pf top (out) - 2.250 in. Pf top (out) - 2.250 in.
BFCD top (out) - 2.250 in. BFCD top (out) - 2.250 in.
Rise top (out) - 0.000 in. Rise top (out) - 0.000 in.
XTO top (out) - 2.250 in. XTO top (out) - 2.250 in.
Pf top (ins) - 2.438 in. Pf top (ins) - 2.438 in.
BFCD top (ins) - 2.250 in. BFCD top (ins) - 2.250 in.
Rise top (ins) - 0.000 in. Rise top (ins) - 0.000 in.
XTI top (ins) - 2.438 in. XTI top (ins) - 2.438 in.
Pf bot (out) - 2.250 in. Pf bot (out) - 2.250 in.
BFCD bot (out) - 2.250 in. BFCD bot (out) - 2.250 in.
Rise bot (out) - 0.000 in. Rise bot (out) - 0.000 in.
XBO bot (out) - 2.250 in. XBO bot (out) - 2.250 in.
Pf bot (ins) - 2.500 in. Pf bot (ins) - 2.500 in.
BFCD bot (ins) - 2.250 in. BFCD bot (ins) - 2.250 in.
Rise bot (ins) - 0.000 in. Rise bot (ins) - 0.000 in.
XBI bot (ins) - 2.500 in. XBI bot (ins) - 2.500 in.
Bolt Spacing - 3.500 in. Bolt Spacing - 3.500 in.
Controlling Mode : Thick Plate Controlling Mode : Thick Plate
Angle top - 90.0 degrees Angle top - 90.0 degrees
Angle bot - 90.0 degrees Angle bot - 90.0 degrees
Left Side Frame Right Side Frame
Controlling Moments Axial Shear Moments Axial Shear
Load Combinations: (k-ft) (kips) (kips) (k-ft) (kips) (kips)
----------------------------- -------------------------------------------------
33) 1.3893DL -3.25LEQ (SOA-L -210.46 11.61 26.29 204.22 11.61 25.82
29) 0.7107DL -3.25LEQ (SOA-L -210.23 11.61 26.16 204.29 11.61 25.92
Connection Design Summary:
Bolt Unity Check (O.S.) = 0.6844 Plate Unity Check (O.S.) = 0.4485
Bolt Unity Check (I.S.) = 0.6634 Plate Unity Check (I.S.) = 0.4410
Metallic Building Systems User: mmfarahani Page: F5- 17
R-Frame Design Program - Version V8.15 Job : 31650A
Knee and Stiffener Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Left and Right Knee Design
==========================
Knee Web Thickness : Use 0.3125 in. Thick Web
Bearing Stiffener Type : Horizontal
Bearing Stiffener at Knee : 2.7500 X 0.2500 in.
Column Cap Plate : 6.0000 X 0.3125 in.
Knee Panel Weld Sizes
=====================
Required (Due to Weld Shear) Min. Fillet Welds, around the Knee Web Panel are:
Column Cap Plate: 0.3125 in. x 17.500 in. GMAW on NEAR Side (STD. WELD)
Column Cap Plate: 0.3125 in. x 3.000 in. GMAW on FAR Side (STD. WELD)
Horizontal Stiffener: 0.2500 in. x 17.500 in. GMAW on NEAR Side (STD. WELD)
Horizontal Stiffener: 0.2500 in. x 3.000 in. GMAW on FAR Side (STD. WELD)
Column Outer Flange: 0.1875 in. x 18.000 in. SAW on NEAR Side (STD. WELD)
Column Outer Flange: 0.1875 in. x 18.000 in. GMAW on FAR Side (STD. WELD)
Column Connection Pl.: 0.2500 in. x 18.000 in. GMAW on BOTH Sides (STD. WELD)
Knee Stiffener to Connection Plate Weld
=======================================
0.1875 in. x 2.750 in. GMAW Fillet Weld on BOTH Sides of Stiff. (STD. WELD)
(STD. WELD)- Company Standard Weld was Designed and Checked as OK.
Metallic Building Systems User: mmfarahani Page: F5- 18
R-Frame Design Program - Version V8.15 Job : 31650A
Flange Brace Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
Girt Spaces - Vertical Measurements
Left Column Right Column
1 @ 20'0 @ FLOOR 1 @ 20'0 @ FLOOR
Purlin Spaces - Horizontal Measurements
Left Rafter Right Rafter
1 @ 19'8 @ EAVE
--------------------------------------------------------------------------------
Member Distance to Brace Points (feet)
- Left Rafter : Measured along T.F. from left steel line
- Right Rafter : Measured along T.F. from right steel line
- Ext. Columns : Measured along T.F. from base
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
Metallic Building Systems User: mmfarahani Page: F5- 19
R-Frame Design Program - Version V8.15 Job : 31650A
Primary Deflection Report File: p5(s).fra Date: 9/22/21
pf 19.667/20. main building at plane SWA Start Time: 18:21:27
--------------------------------------------------------------------------------
COLUMN TOP DEFLECTIONS for LOAD COMBS. (Positive = X: Right Y:Upward) (Inches)
==============================================================================
Ext. Left Col Ext Right Col
X-Def Y-Def X-Def Y-Def
------------------------------------------------------------------------------
Pos. Max 4.409 0.011 4.398 0.011
Load Comb 45 47 47 48
Defl. H/ 49 H/ 49
------------------------------------------------------------------------------
Neg. Max -4.409 -0.012 -4.398 -0.012
Load Comb 48 46 46 45
Defl. H/ 49 H/ 49
==============================================================================
MAX RAFTER DEFLECTIONS for SPAN #1. (Positive = Y:Upw ard)
==============================================================================
Max. Downward Deflection Max. Upward Deflection
Y-Def. X-Dist. from Left S.L. Y-Def. X-Dist. from Left S.L.
------------------------------------------------------------------------------
Max. Def -0.052 in. 4.86 ft. 0.049 in. 4.86 ft.
Load Comb 45 48
Defl. L/999 L/999
==============================================================================
PEAK DEFLECTIONS (Positive = Y:Upward)
====================
Y-Def
--------------------
Pos. Max 0.011 in.
Load Comb 48
Defl. L/999
--------------------
Neg. Max -0.012 in.
Load Comb 45
Defl. L/999
====================
Note: The reported horizontal deflections for the load combinations shown below
have been amplified by the value of Cd (deflection amplification factor).
LC# Cd Used
----- -------
45 3.0
46 3.0
47 3.0
48 3.0
Vertical Clearance at the Left Knee is 17.2865 feet
Vertical Clearance at the Right Knee is 17.2865 feet
Metallic Page: 27
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:47:45
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
***** TRANSVERSE BRACING DESIGN *****
STABILITY BRACING AT MAIN BUILDING ENDWALL PLANE EWB
Loading Condition Horizontal Force
--------------------------------------------- ------------------
1) Lateral Wind Load 1 from SWA to SWC 1.95
2) Lateral Wind Load 2 from SWA to SWC 2.32
3) Lateral Wind Load 1 from SWC to SWA 2.91
4) Lateral Wind Load 2 from SWC to SWA 2.53
5) Lateral Seismic from planes SWA to SWC 5.90
Weight (W)
6) Lateral Seismic from planes SWC to SWA 5.90
Weight (W)
--------------------------------------------- ------------------
kips
Using Max size 0.5000" RODS in endwall module [ 2] from left to right
Width= 10.00 feet Left Height= 26.67 feet Right Height= 26.67 feet
Load Active Rod Design Tensile Force Tensile Force
Cond Vert. Rise Length Applied Capacity
(feet) (feet) (kips) (kips)
---- ---------- ------- ------------- -------------
Tier 1
1) 13.50 16.80 3.27 4.79
2) 13.50 16.80 3.90 4.79
3) 13.50 16.80 4.88 4.79
4) 13.50 16.80 4.25 4.79
5) 13.50 16.80 4.04 5.74
6) 13.50 16.80 4.04 5.74
Tier bracing size:0.5000" ROD
---- ---------- ------- ------------- -------------
Tier 2
1) 13.17 16.53 3.08 4.79
2) 13.17 16.53 3.67 4.79
3) 13.17 16.53 4.59 4.79
4) 13.17 16.53 4.00 4.79
5) 13.17 16.53 3.80 5.74
6) 13.17 16.53 3.80 5.74
Tier bracing size:0.5000" ROD
---- ---------- ------- ------------- -------------
Strut Information:
Module 2
--------------------------
0.5000" ROD
@13.50 feet 8X2.5Z16
0.5000" ROD
--------------------------
Metallic Page: 28
Design Summary Report Version: 8.15.1 run01 Date: 09/23/21
Start Time: 05:47:46
R:\jobs\Active\Eng\18-B-31650\ver02-mmfarahani\BLDG-A\run01\
-------------------------------------------------------------------------------
***** TRANSVERSE BRACING DESIGN *****
STABILITY BRACING AT MAIN BUILDING ENDWALL PLANE EWD
Loading Condition Horizontal Force
--------------------------------------------- ------------------
1) Lateral Wind Load 1 from SWA to SWC 1.95
2) Lateral Wind Load 2 from SWA to SWC 2.32
3) Lateral Wind Load 1 from SWC to SWA 2.91
4) Lateral Wind Load 2 from SWC to SWA 2.53
5) Lateral Seismic from planes SWA to SWC 5.92
Weight (W)
6) Lateral Seismic from planes SWC to SWA 5.92
Weight (W)
--------------------------------------------- ------------------
kips
Using Max size 0.5000" RODS in endwall module [ 2] from left to right
Width= 10.00 feet Left Height= 26.67 feet Right Height= 26.67 feet
Load Active Rod Design Tensile Force Tensile Force
Cond Vert. Rise Length Applied Capacity
(feet) (feet) (kips) (kips)
---- ---------- ------- ------------- -------------
Tier 1
1) 13.50 16.80 3.27 4.79
2) 13.50 16.80 3.90 4.79
3) 13.50 16.80 4.88 4.79
4) 13.50 16.80 4.25 4.79
5) 13.50 16.80 4.05 5.74
6) 13.50 16.80 4.05 5.74
Tier bracing size:0.5000" ROD
---- ---------- ------- ------------- -------------
Tier 2
1) 13.17 16.53 3.08 4.79
2) 13.17 16.53 3.67 4.79
3) 13.17 16.53 4.59 4.79
4) 13.17 16.53 4.00 4.79
5) 13.17 16.53 3.81 5.74
6) 13.17 16.53 3.81 5.74
Tier bracing size:0.5000" ROD
---- ---------- ------- ------------- -------------
Strut Information:
Module 2
--------------------------
0.5000" ROD
@13.50 feet 8X2.5Z16
0.5000" ROD
--------------------------
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Bickel Group B20-0536
Kelly Johnson
31872 Paseo Adelanto
949 572-8030
kjohnson@bickelgrp.com
Please see attached memo.
05/17/22
✔
1
CSG
05/18/22
05/26/22
X XXXX
CSG 06/02/22
1
REVISIONS MEMO
Date: May 17, 2022
To: City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, CA 92675
Re: Revisions to Permit B20-0536
31872 Paseo Adelanto, San Juan Capistrano
Bickel Project #: 15091
Due to some coordination with SMWD, there are a few revisions to the approved set of plans.
Please see below an itemized list of the changes which are clouded.
P1.0 Detail E for sampling box added
Equipment Schedule revised to add sampling box and flow meter
P2.0 Grease Interceptor sizing notes added
P2.1 Waste and Vent Floor Plan revised per SMWD comments to add sampling box and flow
meter
P2.2 Waste and Vent Floor Plan revised to add additional vents per SMWD comments
E4.1 Single line revised to remove telephone board from switchgear to match power plan and
mark-ups on original switchgear submittal
Please feel free to contact me directly for any clarifications.
Regards,
Kelly Johnson, AIA, LEED AP | Director of Production
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 kjohnson@bickelgrp.com
Letter of Transmittal
3707 W Garden Grove Blvd. Suite 100, Orange, CA 92868
phone 714.568.1010 fax 714.568.1028 www.csgengr.com ORA – BPR - 160801
To: City of San Juan Capistrano Date Completed: 6/2/2022 Review #: PC01
32400 Paseo Adelanto Date Received:
San Juan Capistrano, CA 92675 CSG #: 426935
Attn: Building & Safety Division Agency Plan Check #: B20-0536
Job Address: 31872 Paseo Adelanto
Job Description:
Revision - River Street Hay Loft - Shell and T.I. permit for brewery/tasting facility
Status: Hours: (By Rate)
X Plan is approved. 1.0 1st Plan Check
Plan is approved with conditions. See remarks. 2nd Plan Check
Plan is approved with redlines. See remarks. 3rd Plan Check
Plan is approved with redlines and conditions. See remarks. 4th Plan Check
Plan requires corrections. See attached list. Total Hours
We have reviewed the following documents ( X Digital only):
X Plans Truss Calculations
Structural Calculations Energy Calculations
Soil Report Specifications
Geotechnical Review Letter Special Inspection Form(s)
Other:
Special items to note:
X Plan has been stamped and signed by CSG
Environmental Health Services approval required
Special inspection required for
Hardship Form included
Remarks:
Recommend for approval
From: Jensen Ku S.E. (ginsun@csgengr.com)
CSG Consultants Inc.
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Bickel Group B20-0536
Kelly Johnson
31872 Paseo Adelanto
949 572-8030
kjohnson@bickelgrp.com
Please see attached memo.
08/31/22
✔
2
CSG/DAVID
08/31/2209/12/22
1
CSG 09/13/22
X
X X
X
X
REVISIONS MEMO
Date: August 31, 2022
To: City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, CA 92675
Re: Revisions to Permit B20-0536
31872 Paseo Adelanto, San Juan Capistrano
Bickel Project #: 15091
Due to tenant requirements, there are a few revisions to the approved set of plans. Please see
below an itemized list of the changes which are clouded.
A-1.0 Floor Plan: Counter and backbar re-designed, Lockable storage room added
RCP: Ceiling at Lockable storage added
Mezzanine Plan: Louvers added at low walls
Finish Schedule: Revised to add Lockable Storage and Mezzanine and clarify substrate
behind finishes
A-6.0 Door Schedule revised to add door 103 for Lockable Storage and revise door heights to 7’.
A-6.2 18 – Back Bar Elevation: Elevation revised
21 - Counter Detail: Added
E2.1 Lighting Plan: Lighting added at Lockable Storage room
Power Plan: Power added for fan at Lockable Storage
Brewery Power Plan: Power at front counter and backbar revised to match new kitchen,
convenience power added throughout and power added at Lockable Storage
E3.3 Motorized Equipment Schedule: Fan at Lockable Storage added
E4.2 Panel Schedules revised as clouded for equipment changes
M0.0 Exhaust fan added
M0.1 Transfer fan details added
M1.0 Fan added at Lockable Storage
P-1.0 Plumbing Fixture and equipment schedule: Revised as clouded
P-2.0 Plumbing Floor plan: Revised at counter/backbar and Lockable storage
P-2.1 Waste & Vent Plan: Revised as clouded to match latest kitchen and owner requests
Water & Gas Plan: Revised as clouded to match latest kitchen and owner requests
P-2.2 Waste & Vent Plan: Revised as clouded to match latest kitchen and owner requests
Water & Gas Plan: Revised as clouded to match latest kitchen and owner requests
K1.0 Equipment Plan: Revised for new bar tenant
August 31, 2022
Revisions Memo
B20-0537
Page 2
K2.0 Plumbing Rough-in Layout: Revised for new bar tenant
K3.0 Electrical Rough-in Layout: Revised for new bar tenant
Please feel free to contact me directly for any clarifications.
Regards,
Kelly Johnson, AIA, LEED AP | Principal
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 kjohnson@bickelgrp.com
Letter of Transmittal
3707 W Garden Grove Blvd. Suite 100, Orange, CA 92868
phone 714.568.1010 fax 714.568.1028 www.csgengr.com ORA – BPR - 160801
To: City of San Juan Capistrano Date Completed: 9/13/2022 Review #:PC01
32400 Paseo Adelanto Date Received:
San Juan Capistrano, CA 92675 CSG #: 4213107
Attn: Building & Safety Division Agency Plan Check #: B20-0536
Job Address: 31872 Paseo Adelanto
Job Description:
Revision - River Street Hay Loft - Shell and T.I. permit for brewery/tasting facility
Status: Hours: (By Rate)
X Plan is approved. 1.0 1st Plan Check
Plan is approved with conditions. See remarks. 2nd Plan Check
Plan is approved with redlines. See remarks. 3rd Plan Check
Plan is approved with redlines and conditions. See remarks. 4th Plan Check
Plan requires corrections. See attached list. Total Hours
We have reviewed the following documents ( X Digital only):
X Plans Truss Calculations
Structural Calculations Energy Calculations
Soil Report Specifications
Geotechnical Review Letter Special Inspection Form(s)
Other:
Special items to note:
X Plan has been stamped and signed by CSG
Environmental Health Services approval required
Special inspection required for
Hardship Form included
Remarks:
Recommend for approval
From: Jensen Ku S.E. (ginsun@csgengr.com)
CSG Consultants Inc.
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Construct & Maintain Corp dba CM Corp B20-0536
Andrew Barrett
31872 Paseo Adelanto
949 292-6462
abarrett@cmcorp.co
1-12 Deferred Submittal - AOR/Structural EOR Approved Truss Shop Drawings
Andrew Barrett Digitally signed by Andrew Barrett
Date: 2022.10.11 18:18:51 -07'00'10/11/2022
✔
4
CSG
10/11/22
10/20/22
X XXXX
1
CSG 10/20/22
Letter of Transmittal
3707 W Garden Grove Blvd. Suite 100, Orange, CA 92868
phone 714.568.1010 fax 714.568.1028 www.csgengr.com ORA – BPR - 160801
To: City of San Juan Capistrano Date Completed: 10/20/22 Review #:PC01
32400 Paseo Adelanto Date Received:
San Juan Capistrano, CA 92675 CSG #: 4214946
Attn: Building & Safety Division Agency Plan Check #: B20-0536
Job Address: 31872 Paseo Adelanto
Job Description:
Deferred submittal River street Red Barn Trusses shop Drawings– AOR/Structural EOR
Status: Hours: (By Rate)
X Plan is approved. 1st Plan Check
Plan is approved with conditions. See remarks. 2nd Plan Check
Plan is approved with redlines. See remarks. 3rd Plan Check
Plan is approved with redlines and conditions. See remarks. 4th Plan Check
Plan requires corrections. See attached list. Total Hours
We have reviewed the following documents ( X Digital only):
X Plans Truss Calculations
X Structural Calculations Energy Calculations
Soil Report Specifications
Geotechnical Review Letter Special Inspection Form(s)
Other:
Special items to note:
X Plan has been stamped and signed by CSG
Environmental Health Services approval required
Special inspection required for
Hardship Form included
Remarks:
Recommend for approval for deferred river street ed Barn roof trusses
From: Jensen Ku S.E. (ginsun@csgengr.com)
CSG Consultants Inc.
1
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Bickel Group B20-0536
Kelly Johnson
31872 Paseo Adelanto
949 572-8030
kjohnson@bickelgrp.com
Please see attached memo.
06/26/23
✔
5
CSG
07/03/23
X
XX
X
4
CSG 08/30/23
REVISIONS MEMO
Date: June 26, 2023
To: City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, CA 92675
Re: Revisions to Permit B20-0536
31872 Paseo Adelanto, San Juan Capistrano
Bickel Project #: 15091
Due to tenant requirements, there are a few revisions to the approved set of plans. Please see
below an itemized list of the changes which are clouded.
A-1.0 1-Floor Plan: Opening for cooler box widened. Counter/low wall and taps opening at back
bar revised.
2-Reflected Ceiling Plan: Lighting revised as clouded
4-Finish Schedule: Revised
Wall & Symbols Legend: Furring wall at backbar added
RCP Symbol Legend: Interior Light type added
Floor Notes: Note 8 and 9 added per Health Department
A-5.0 Detail 5: Finishes updated
Detail 10: Finishes updated
Detail 15: Finishes updated
A-6.2 Detail 18: Elevation updated
Detail 21: Bar Wall details revised
S-1.0 Foundation Plan: Opening at cooler box wall revised
Roof Framing Plan: Opening at cooler box wall revised
E-2.1 Lighting Plan: Lighting revised as clouded
E-3.2 Power Plan: Updated as clouded
E-3.3 Roof Plan: Lighting updated as clouded
E-4.2 Panel Schedules updated as clouded
E5.1 Lighting Fixture Schedule: Interior lighting fixtures revised as clouded
E5.2 T24 updated for lighting changes
M1.0 Background updated only
P-1.0 Plumbing Fixt. Schedule: HB-4 added
P-2.1 A- Enlarged Waste & Vent Plan: Updated as clouded
B- Enlarged Water & Gas Plan: Updated as clouded
June 26, 2023
Revisions Memo
B20-0536
Page 2
P-2.2 A- Mezzanine Waste & Vent Plan: Updated as clouded
B- Mezzanine Water & Gas Plan: Updated as clouded
K1.0 Food Service Equipment Plan and Schedule: Updated as clouded
K1.1 Sheet added
K2.0 Plumbing rough-in layout updated as clouded
K3.0 Plumbing rough-in layout updated as clouded
Please feel free to contact me directly for any clarifications.
Regards,
Kelly Johnson, AIA, LEED AP | Principal
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 kjohnson@bickelgrp.com
Letter of Transmittal
3707 W Garden Grove Blvd. Suite 100, Orange, CA 92868
phone 714.568.1010 fax 714.568.1028 www.csgengr.com ORA – BPR - 160801
To: City of San Juan Capistrano Date Completed: 8/30/2023 Review #:PC02
32400 Paseo Adelanto Date Received: 7/3/2023
San Juan Capistrano, CA 92675 CSG #: 439691
Attn: Building & Safety Division Agency Plan Check #: B20-0536
Job Address: 31872 Paseo Adelanto
Job Description:
River Street Hay Loft - Shell and T.I. permit for brewery/tasting facility
Status: Hours: (By Rate)
X Plan is approved. 3.0 1st Plan Check
Plan is approved with conditions. See remarks. 1.0 2nd Plan Check
Plan is approved with redlines. See remarks. 3rd Plan Check
Plan is approved with redlines and conditions. See remarks. 4th Plan Check
Plan requires corrections. See attached list. Total Hours
We have reviewed the following documents ( X Digital only):
X Plans Truss Calculations
X Structural Calculations Energy Calculations
Soil Report Specifications
Geotechnical Review Letter Special Inspection Form(s)
Other:
Special items to note:
X Plan has been stamped and signed by CSG
Environmental Health Services approval required
Special inspection required for
Hardship Form included
Remarks:
Recommend for approval
From: Jensen Ku S.E. (ginsun@csgengr.com)
CSG Consultants Inc.
JUN 22, 2023
CSG 08/30/23
B20-0536 REV 5 V2
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Bickel Group B20-0536
Kelly Johnson
31872 Paseo Adelanto
949 572-8030
kjohnson@bickelgrp.com
Please see attached memo.
12/12/23
✔
6
CSG/LAURA
12/12/23
12/21/23
XX XXX
1
CSG 12/14/23
Letter of Transmittal
3707 W Garden Grove Blvd. Suite 100, Orange, CA 92868
phone 714.568.1010 fax 714.568.1028 www.csgengr.com
To: City of San Juan Capistrano Date Completed: 12/14/2023 Review #:1
32400 Paseo Adelanto Date Received:
San Juan Capistrano, Ca. 92675 CSG #: 4317079
Attn: Building Division Agency Plan Check #: B20-0536
Job Address: 31872 Paseo Adelanto
Job Description:
REVISION TO APPROVED CSG 4309691 – ADD FIREPIT, REVISED RESTROOMS. MISC M/E/Ps – RIVER STREET
HAY LOFT
Status: Plan is ready for permit issuance for the following:
X Plan is approved. Architectural Energy
Plan is approved with conditions. See remarks. Structural Other:
Plan is approved with redlines. See remarks. Plumbing
Plan is approved with redlines and conditions. See remarks. Electrical
Plan requires corrections. See attached list. Mechanical
We have reviewed the following documents ( X Digital only):
X Plans Truss Calculations
Structural Calculations Energy Calculations
Soil Report Specifications
Geotechnical Review Letter Special Inspection Form(s)
X Other: Revision Narrative
Special items to note:
Plan has been stamped and signed by CSG
Environmental Health Services approval required
Special inspection required for
Hardship Form included
Remarks:
First plan check: Chi Yang 1.0 hour
From: Chi Yang
CSG Consultants Inc. (714) 568-1010
REVISIONS MEMO
Date: December 12, 2023
To: City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, CA 92675
Re: Revisions to Permit B20-0536
31872 Paseo Adelanto, San Juan Capistrano
Bickel Project #: 15091
Due to tenant requirements, there are a few revisions to the approved set of plans. Please see
below an itemized list of the changes which are clouded.
A-1.0 1- Floor Plan: Future Fire Pit added at covered dining per keyed note 47. Interior elevation
of bar added per tag 10/A-6.2. Keyed note 7 added to note swing gate at bar. Drywall to
stainless wall finish transitions shifted. Ice machine relocated to Lockable storage area.
Backbar furring and framed opening to cooler box modified.
2-RCP: Sconce lights at restroom sinks revised. Some back of house pendants revised to
monopoints as clouded.
3-Mezzanine Plan: Final equipment layout updated as clouded
4-Finish Schedule: Vinyl scrim at open ceilings revised to black. Restroom and dining floor
tile finish noted by tenant.
5-Responsibility matrix previously circulated added.
Keyed note 39: Revised to note plywood on bar wall face.
Keyed note 47 and 48 added.
A-5.0 Details 5, 10 and 15 updated.
A-6.1 8- Toilet Room Accessories: updated to interior designer specs
22-Lavatory section updated
A-6.2 1- Men’s Room elevation: Updated per latest interior design plans.
8-Toilet Room Accessories: updated to interior designer specs
10-Front bar counter elevation added
11-Women’s Room elevation: Updated per latest interior design plans.
18-Back bar elevation updated to match latest interior design plans
21-Back bar sections updated to match latest elevation
25-Backbar counter detail updated
E2.1 Lighting Plan: Sconce lights at restroom sinks revised. Some back of house pendants
revised to monopoints as clouded.
E3.1 Power Plan: Faucet power added at restrooms and power at janitor room for pump added.
E3.2 Brewery Power Plan: Updated throughout as clouded in final coordination with brewery
team.
E4.2 Schedules updated for power/lighting changes as clouded
E5.1 Lighting Fixture Schedule: Fixtures F3, H1 and H3 specs updated.
December 12, 2023
Revisions Memo
B20-0536
Page 2
E5.2 T24 updated for lighting revisions
P-1.0 Faucet spec for restrooms revised.
P-2.0 A-Plumbing Floor Plan: Gas line extended to future fire pit.
F- Gas pipe sleeve detail provided.
P-2.1 A- Waste & Vent Plan: Ice Machine moved
B- Water & Gas Plan: water to ice machine revised
Plumbing Plans: Updated to match final kitchen/health plans and update to move soft
water to ground level and remove from mezzanine
P-2.2 C- Gas riser diagram and loads added.
Plumbing Plans: Updated to match final kitchen/health plans and update to move soft
water to ground level and remove from mezzanine
K1.0 1- FS Equipment Plan: Ice machine and shelving relocated
K2.0 2- Plumbing Rough-in layout: Water to ice machine revised.
K3.0 3- Electrical Rough-in layout: Electrical to ice machine revised.
Please feel free to contact me directly for any clarifications.
Regards,
Kelly Johnson, AIA, LEED AP | Principal
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 kjohnson@bickelgrp.com
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Bickel Group B20-0536
Kelly Johnson
31872 Paseo Adelanto
949 572-8030
kjohnson@bickelgrp.com
Please see attached memo.
03/04/24
✔
7
JW
03/11/24
03/20/24
X XXXX
1
JAMES WIATRAK 03/20/24
REVISIONS MEMO
Date: March 4, 2024
To: City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, CA 92675
Re: Revisions to Permit B20-0536
31872 Paseo Adelanto, San Juan Capistrano
Bickel Project #: 15091
Per direction from the building department, we have updated the plans to include an anchor
detail for the installed switchgear. There are also two TVs that were moved from wall mounted
power to ceiling power. Please see below an itemized list of the changes which are clouded.
A-1.0 Keyed note 4 modified to reference added detail 3/A-1.1
A-1.1 Detail 3 for switchgear anchorage added.
Please feel free to contact me directly for any clarifications.
Regards,
Kelly Johnson, AIA, LEED AP | Principal
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 kjohnson@bickelgrp.com
From:James Wiatrak
To:Lisa La
Subject:RE: River Street - Revisions Submittal
Date:Wednesday, March 20, 2024 10:49:38 AM
Attachments:image001.png
image002.png
Lisa,
I have reviewed the attachments and they are ready to stamp approved and issue.
Regards,
James “JW” Wiatrak, CBO, CASp
Building Official
City of San Juan Capistrano
30448 Rancho Viejo Rd., Suite 110
San Juan Capistrano, CA 92675
(949) 234-4568
jwiatrak@sanjuancapistrano.org
www.sanjuancapistrano.org
** City Hall administrative offices have moved to 30448 Rancho Viejo Road**
From: Kelly Johnson <kjohnson@bickelgrp.com>
Sent: Wednesday, March 20, 2024 10:32 AM
To: James Wiatrak <JWiatrak@sanjuancapistrano.org>; Building Department
<building@sanjuancapistrano.org>; Lisa La <LLa@sanjuancapistrano.org>
Cc: Alex Osinski <AOsinski@almquist.com>; Andrew Barrett - CM Corp <abarrett@cmcorp.co>
Subject: RE: River Street - Revisions Submittal
[The e-mail below is from an external source. Please do not open attachments or click
links from an unknown or suspicious origin.]
Hi JW and Lisa,
I have updated the links below to address the last comment from JW for special inspection on each
anchorage detail and renumbered the revision number per Lisa’s last email. Please let us know if you
need anything else.
Greenhouse B20-0537 REV 7 V1
Hayloft B20-0536 REV 7 V1
Marketplace B20-0535 REV 8 V1
Mercantile B20-0539 REV 8 V1
Red Barn B20-0534 REV 5 V1
Site B20-0546 REV3 V1
Workshop B20-0538 REV 7 V1
Farmstead B20-0540 REV 5 V1
Kelly Johnson, AIA, LEED AP | Principal
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 | kjohnson@bickelgrp.com
From: James Wiatrak <JWiatrak@sanjuancapistrano.org>
Sent: Wednesday, March 13, 2024 8:17 AM
To: Kelly Johnson <kjohnson@bickelgrp.com>; Building Department
<building@sanjuancapistrano.org>; Lisa La <LLa@sanjuancapistrano.org>
Cc: Alex Osinski <AOsinski@almquist.com>; Andrew Barrett - CM Corp <abarrett@cmcorp.co>
Subject: RE: River Street - Revisions Submittal
Hi Kelley,
No, if these are interior locations, the structural slabs are noted on the foundations plan and
acceptable as is.
Regards,
James “JW” Wiatrak, CBO, CASp
Building Official
City of San Juan Capistrano
30448 Rancho Viejo Rd., Suite 110
San Juan Capistrano, CA 92675
(949) 234-4568
jwiatrak@sanjuancapistrano.org
www.sanjuancapistrano.org
** City Hall administrative offices have moved to 30448 Rancho Viejo Road**
Pacific Electric Inc
42640 Rio Nedo
Temecula CA, 92590
951-296-1562
3/6/24
REF: River Street Switchboard
To Whom It May Concern,
Pacific Electric switchboards leave the factory seismically braced, requiring no additional field bracing.
Please refer to the seismic anchoring page for guidance in floor mounting switchboard sections.
Sincerely,
Victor Herrada
Pacific Electric, Inc.
Manufacturer of Electrical Distribution Equipment
951-296-1562
951-296-1563 Fax
vherrada@pacificelectric.biz
www.pacificelectric.biz
B20-0536 REV 7
Pacific Electric, Inc.42640 Rio Nedo Temecula, Ca. 92590(951) 296-15621 A-AAASEISMIC BOLT DOWN INSTRUCTIONS (NEMA 3R SECTIONS)USE 1/2" OR 5/8" GR. 5 HEX HEAD BOLTS(FURNISHED BY OTHERS)TOP VIEWSIDE VIEWFRONT1/2" HIGH X 4" WIDE WET SILLSSWITCHBOARD FRAME1/2" HIGH X 4" WIDE WET SILLS*****DRAWING SBDI-N3RB20-0536 REV 7
g IE. ELEC TRICAL
Lockout Procedure
Lockout Procedure for:
River Street Marketplace - Hay Loft Building
31872 Paseo Adelanto
San Juan Capistrano, CA 9267 5
City of San Juan Capistrano Building Permit #820-0536
SDG&E Job Notification No: 3-366604
Siemens Main Switch Board (MSB-HL). 1000,4. Pull Section.
Main Circuit Breaker" Distribution Board (DB-l). Plaza Power
Pedestal & Sub Panel HPHL
Purpose
This procedure establishes the minimum requirements for the lockout of Siemens Main Switch Board (MSB-HL),
1000,{ Pull Section and corresponding Main Circuit Breaker to include Distribution Board (DB- l ), Plaza Power
Pedestal and sub panel HPHL to ensure equipment is isolated from all potentially hazardous energy sources and locked
out from unexpected energization.
Responsible Party
Millcreek Electrical, Inc. assumes full responsibility for the process of lockouts, tag outs and safe off of all equipment
denoted above.
Accessibility to Electrical Room/Equipment
Access to the electrical room, Siemens Main Switch Board (MSB-HL), 1000A Pull Section, Main Circuit Breaker,
Distribution Board (DB-1), Plaza Power Pedestal and sub panel HPHL will be limited to Millcreek Electrical, Inc.
employees only. Millcreek Electrical, Inc. will possess the lock out keys at all times and furthermore, will ensure that
locks are not be removed from any equipment/breakers until'approved by the City of San Juan Capistrano Electrical
Inspector.
Preparing Eqaipment for Energization
When the servicing is completed and the machine or equipment is ready for normal operating condition, the following' steps shall be taken.
( 1) Secure approval from City of San Juan Capistrano Electrical Inspector for removal of lock(s) from energy
isolating device(s) to include but not limited to the Siemens Main Switch Board (MSB-HL), 10004 Pull Section,
Main Circuit Breaker, Distribution Board (DB-1), Plaza Power Pedestal and sub panel HPHL.
(2) Check the machine or equipment and the immediate area around the machine to ensure that nonessential items
have been removed and that the machine or equipment components are operationallyintact.
(3) Check the work area to ensure that all employees have been safely positioned or removed from thearea.
(4) Verif that the controls are in neutral.
(5) Remove the lockout devices and energize the machine orequipment.
B20-0536 REV 7
MILLCREEK
California License Type: C1O-Electrical
California License Number: 101 1 154
California License Expiration : 212912024
B20-0536 REV 7
September 30, 2022
TO: CITY OF SAN JUAN CAPISTRANO
FROM: SAN DIEGO GAS & ELECTRIC
Subject: SECONDARY SHORT-CIRCUIT CURRENT
Project: 3-356495 RIVER STREET
The serving voltages for this project is as follows per each address:
1. Farmstead: 31904 Paseo Adelanto
1200 amps 4 wire. Three phase, 120/208 volts.
2. Greenhouse: 31880 Paseo Adelanto
2000 amps 4 wire. Three phase, 120/208 volts.
3. Hayloft: 31872 Paseo Adelanto
1200 amps 4 wire. Three phase, 120/208 volts.
4. Marketplace: 31864 Paseo Adelanto
2000 amps 4 wire. Three phase, 120/208 volts.
5. Mercantile: 31896 Paseo Adelanto
2500 amps 4 wire. Three phase, 120/208 volts.
6. Red Barn: 31856 Paseo Adelanto
2000 amps 4 wire. Three phase, 120/208 volts.
7. Workshop: 31888 Paseo Adelanto
1200 amps 4 wire. Three phase, 120/208 volts.
The ultimate available fault current (ISC) for this installation will not exceed 42,000
amperes at the point of connection of SDG&E’ s service conductors to the customer’s
facilities. This value is stated in RMS symmetrical amperes.
Victoria Cronk
SDG&E
Customer Project Planner – Orange County
(949) 361-8078
B20-0536 REV 7
B20-0536 REV 7
FRAMING . CONCRE tE. ELECTRICAL
tolsl2o23
Subject:
Torque Verification of Elebtrical Lugs
Project Address:
River Street Marketplace - Hayloft Building
3L872 Paseo Adelanto
San Juan Capistrano, CA92675
Permit Number: 820-0536
Electrical Gear: MSB-MP 1000AMP Switchgear, DB-L distribution panel, & HPHL house panel
To whom it may concern,
This letter is a statement of declaration that Millcreek Electrical lnc. has torqued the electrical landing
lugs inside the 1000AMP electrical switchgear, the 800AMP distribution panel, and the House panel at
the project address listed above to the manufacturer specified torque values.
California License Type: C10
California License Number: lOlLLS
California License Expiration: 2/28/2024
n Kehler, General Manager
B20-0536 REV 7
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Bickel Group B20-0536
Kelly Johnson
31872 Paseo Adelanto
949 572-8030
kjohnson@bickelgrp.com
Please see attached memo.
06/11/24
✔
8
CSG/LAURA
06/11/24
06/19/24
X
X X
X
X
REVISIONS MEMO
Date: June 11, 2024
To: City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, CA 92675
Re: Revisions to Permit B20-0536
31872 Paseo Adelanto, San Juan Capistrano
Bickel Project #: 15091
Ownership has elected to install a custom fire pit at the subject building. The gas line and
manual gas shutoff were previously approved in the set but the detailing of the match light fire pit
was not. Sheet A-1.0a has been added and included here detailed said fire pit for review and
approval.
Please feel free to contact me directly for any clarifications.
Regards,
Kelly Johnson, AIA, LEED AP | Principal
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 kjohnson@bickelgrp.com
PERMIT NUMBER
JOB ADDRESS
)252)),&(86(21/<
'(3$570(17$33529$/65(48,5('
%8,/',1*
PLANNING:
38%/,&:25.6:
60:':
2&)$
YES
YES
YES
<(6
<(6
NO
NO
NO
12
12
INSTRUCTIONS:
1.6XEPLWVHWVRIRQO\WKHUHYLVHGVKHHWVVWDSOHGLQWRVHWV
GRQRWVXEPLWFRPSOHWHVHWRISODQV
³&/28'´WKHSURSRVHGFKDQJHVRQWKHGUDZLQJV
1RWHWKHSDJHQXPEHUVRQZKLFKWKHUHYLVLRQVRFFXU
3URYLGHGHVFULSWLRQRISURSRVHGFKDQJHV
DESCRIPTION OF PROPOSED CHANGES:
3$*(
1 .
2 .
3 .
4 .
5 .
APPLICANT SIGNATURE DATE
BUILDING REVISION FEE:727$/3/$1&+(&.(5 REVIEW TIME:
$86.93/HOUR - 1 HOUR MINIMUM – Per table 3.A.1 HOURS
FOR OFFICE USE ONLY
APPROVED BY: DATE:
&203$1<1$0(
EMAIL ADDRESS
CONTACT PHONE #
$33/,&$17 NAME:
&LW\RI6DQ-XDQ&DSLVWUDQR
'H'HYHORSPHQW6HUYLFHV'HSDUWPHQW
3DVHR$GHODQWR
6DQ-XDQ&DSLVWUDQR&$
3KRQH
(PDLOEXLOGLQJ#VDQMXDQFDSLVWUDQRRUJ
ZZZVDQMXDQFDSLVWUDQRRUJEXLOGLQJ
5(9,6,21'()(55('68%0,77$/
$'',1*1(:0(3"
3&7*4*0/
1-"/3&7*&8&3
46#.*55"-%"5&
5"3(&5%"5&
YES 12
)252)),&(86(21/<
Bickel Group B20-0536
Kelly Johnson
31872 Paseo Adelanto
949 572-8030
kjohnson@bickelgrp.com
Please see attached memo.
09/12/24
✔
1
CSG/LAURA
09/12/24
09/22/24
XX XXX
3
CSG 10/14/24
REVISIONS MEMO
Date: September 12, 2024
To: City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano, CA 92675
Re: Revisions to Permit B20-0536
31872 Paseo Adelanto, San Juan Capistrano
Bickel Project #: 15091
Please see below an itemized list of revisions that are included and clouded with a delta 9.
A-1.0 1- Floor Plan: Ladder type to mezzanine revised per revised key note 26
A-5.0 Detail 5: Countertop revised to concrete and supports updated
Detail 10: Countertop revised to concrete and supports updated
A-6.2 Detail 25: Countertop revised to concrete and supports updated
A-7.0 Cutsheet for prefab ladder removed and detail of steel ladder added
M0.0 Air Curtain Schedule: Air curtains at front of house removed as not included on final
approved health plans
M1.0 Mechanical Floor Plan: Air curtains at front of house removed as not included on final
approved health plans
E3.1 Power Plan: Air curtains at front of house removed as not included on final approved health
plans
E3.3 Motorized Equipment Schedule: Air curtains at front of house removed as not included on
final approved health plans
E4.2 Panel HB: Air curtains at front of house removed as not included on final approved health
plans
Please feel free to contact me directly for any clarifications.
Regards,
Kelly Johnson, AIA, LEED AP | Principal
bg | Bickel Group Architecture
P: 949.757.0411 x224 | C: 949.572.8030 kjohnson@bickelgrp.com
Letter of Transmittal
3707 W Garden Grove Blvd. Suite 100, Orange, CA 92868
phone 714.568.1010 fax 714.568.1028 www.csgengr.com
To:City of San Juan Capistrano Date Completed:10/14/2024 Review #:PC2
32400 Paseo Adelanto Date Received:
San Juan Capistrano, Ca. 92675
Attn:Building Division
CSG #: 4411566
Agency Plan Check #: B20-0536 REV 9
Job Address:31872 Paseo Adelanto
Job Description:
Revision to approved “River Street” project
Status:Plan is ready for permit issuance for the following:
X Plan is approved.Architectural Energy
Plan is approved with conditions. See remarks.Structural Other:
Plan is approved with redlines. See remarks.Plumbing
Plan is approved with redlines and conditions. See remarks.Electrical
Plans require corrections. See attached list.Mechanical
We have reviewed the following documents (X Digital only):
X Plans Truss Calculations
X Structural Calculations Energy Calculations
Soil Report Specifications
Geotechnical Review Letter Special Inspection Form(s)
Other:
Special items to note:
X Plan has been stamped and signed by CSG
Environmental Health Services approval required
Special inspection required for
Hardship Form included
Remarks:
Recommend approval for revisions
1st P/C – 2.0 Hrs
2nd P/C –1.0 Hr
From:Khoa Duong, P.E.
CSG Consultants Inc. (714) 568-1010
10/01/2024
RIVER STREET HAYLOFT T.I.B20-0536 REV 9 V2 10/14/24CSG 10/14/24B20-0536 9
LADDER, COUNTERTOP, MECH & ELEC
B20-0536 REV 9 V2 10/14/24