18-1210_LAYNE CHRISTENSEN COMPANY_F10_Agenda Report 12110/2018
F10
City of San Juan Capistrano
Agenda Report
TO: Honorable Mayor and Members of the City Council
FROM: r enjamin Siegel, City Manager
SUBMITTED BY Steve May, Public Works & Utilities Director
PREPARED BY. Noreen Swiontek, Senior Management Analyst
DATE: December 10, 2018
SUBJECT: Ratification of Emergency Purchase for Lower Hunt
Club/Steeplechase Pump Station Repair (Layne Christensen
Company)
RECOMMENDATION:
Ratify an Emergency Purchase Authorization in the amount of $62,160 with Layne
Christensen Company for replacement of two pumps and components at the Lower
Hunt Club/Steeplechase Pump Station-
DISCUSSION/ANALYSIS,
In October 2018, the two vertical turbine pumps at the Lower Hunt Club/Steeplechase
Pump Station failed. This restricted water flow to the Upper Hunt Club reservoir. To
maintain operations, a rental pump was installed while the extent of the repairs was
evaluated. Both pumps and components were then replaced under the emergency
purchase authorization process in order to maintain water flow to the Upper Hunt Club
reservoir.
The City's purchasing policy permits the City Manager to authorize the purchase of
goods, supplies, equipment, materials, and services without following the Purchasing
Policy bidding procedures when the public health, safety, or welfare of the community
would be affected. Emergency purchases must be submitted to the City Council for
ratification. Accordingly, it is recommended that the City Council ratify the purchase
approved through the Emergency Purchase Authorization process in the total amount of
$62,160, as identified in the attached Emergency Purchase Authorization Form
(Attachment 1). As validation of the reasonableness of the cost of this purchase, two
other proposals for the replacement pumps were obtained, which were higher cost
proposals.
City Council Agenda Report
December 10, 2018
Page 2 of 2 _
FISCAL IMPACT:
Sufficient funds are available in the Water Fund Capital Improvement Project 19804
budget for Pump Station Component Replacements to cover the cost of the work.
ENVIRONMENTAL IMPACT:
The replacement work performed, and the recommended action of ratifying the
expenditure, are exempt from the California Environmental Quality Act (CEQA) per
Section 15061(b)(3), which is the general rule that CEQA applies only to activities that
have the potential for causing a significant effect on the environment. Where it can be
seen with certainty that there is no possibility that the activity in question may have a
significant effect on the environment, the activity is not subject to CEQA.
PRIOR CITY COUNCIL REVIEW:
There was no prior City Council review
COMMISSION/COMMITTEE/BOARD REVIEW AND RECOMMENDATIONS:
On November 20, 2018, the Utilities Commission recommended that the City Council
ratify the emergency purchase for the Steeplechase/Hunt Club pump station repairs.
NOTIFICATIONS:
Layne Christensen Company
Legend Pump and Well Service Inc.
General Pump Company
ATTACHMENT.
Attachment 1- Emergency Purchase Authorization (Layne Christensen Company)
' EMERGENCY PURCHASE
AUTHORIZATION FORM
As a Department Head, t have determined that an emergency condition exists that could
interrupt the public health, safety or welfare of the community if the normal bidding procedures
were followed. You are therefore authorized to proceed immediately to purchase, without the
bidding process, any necessary material, labor, equipment or supplies needed to normalize the
emergency condition. Both pumps at the Lower Hunt Club pump station have failed, and the
station is being operated with a temporary, rental pump. The operators
1. Describe this emergency are having difficulty keeping water in the reservoirs, and the neighbors has
complained about the noise at night time.
2. Location of this emergency :
The Lower Hunt Club pump station, at 30761 Steeple Chase Drive.
3. Estimated Cost of NMaterials/Suppiies/Equipment, $
$48,000
4. Selected Vendors
Layne Christensen Company
5. Estimated Cost of Laborlinstaliation$
$12,000
6, Selected Vendors
Layne Christensen Compay
All emergency purchases that would otherwise require the formal bidding procedure shall be
submitted to the City Manager for his presentation to the City Council for rat cation at the next
regular Council meeting.
Date to be ratified by City Council 12110/2018
Department Head Signature Date -�
City Manager Signat;11'
_ Date
Accounts Payable pay approve vendor invoices with an appropriate and valid
purchase order number issued from Finance_ If a purchase order number was not issued for
any reason other than those listed above prior to procurement, the department shall explain
below the circumstances regarding the need for payment without a City issued Purchase
Order.
7. Reason for executing purchase without Purchase Order:
We cannot keep sufficient water in the Upper Hunt Club reservoir is the temporary bypass pump.
Attachment 1
Page 1 of 10
Lare
A OWTM COMPAMY
11/g/2018 Quote;94616A
Tim O'Neal
City of San Juan Capistrano
32400 Paseo Adelanto
San Juan Capistrano,CA 92675
Re: Steeplechase Booster Station -Furnish and Install New Pump and Motor
Dear Tim,
We are pleased to present our project estimate for the referenced work to be performed at Steeplechase Booster Station.
Layne wi11 furnish and install new pumps as described below. Included is 25'of NSF fusion-bonded lined and coated steel
column,416 stainless shaft and shaft retainers for each pump,flexible coupling on discharge for each pump. New
fabricated steel discharge heads will be built to same dimensional design as on existing heads. We will need one of the
heads for obtaining all dimensional information. Prevailing Wage Rates apply to all on-site labor.This estimate assumes re-
using existing conduit and motor conductors from control panels. Bowl assembly will be fusion-bonded epoxy coated,
intermediate column assembly will be lined and coated.discharge head will be lined and coated NSF certiI"sed fusion-
bonded coating.See attached submittal for details.Bowl assembly impellers will be dynamically balanced.
Assumes no acetylene cutting and/or welding is required for installing the flex couplings.Option for new wear rings,
provided.
Our estimate is valid for 30 days. Applicable taxes,bonds,and special insurance requirements are included with this
estimate. Please contact your Layne Christensen Company representative if you have any questions.
Layne Christensen Company has been the industry Ieader in groundwater development since 1882. Our full range of water-
related service encompasses: initial site selection;well field design and development;well drilling and development;pump
installation and repair;water treatment;aquifer investigation and remediation;and well rehabilitation.
Thank you for choosing Layne Christensen Company and giving us the opportunity to be your water resource solution
provider.
Sincerely,
Layne Christensen Company
Cheyne W Is
Account Manager
(909)320-9001
WATER RESOURCES
1717 Park Ave, Redlands,CA 92373 1 Office:909-390-28331 Fax:909-390-60971 layne.com
Attachment 1
Page 2 of 10
LIM
A OAArui comm"Y
11/8/2018 Quote:94616A
Steeplechase Booster Station
L Mobilation-Demobilization Each $3,070.00
2. Labor to Install QTY(2)Pumps Each $10,980.00
3. Materials Qty Units Unit Price Ext Price
Booster pump and Motor w125'of Column(per submittal) 2 Each $21,728.00 $43,456.00
Motor electrical splice materials 2 Each $57.00 $114.00
Suction can NBG set 2 Each $80.40 $160.00
Discharge flange BBG set 2 Each $43.00 $86.00
4" Steel Flexible Coupling 2 Each $43.00 $186.00
Freight 1 Each $300.00 $300.00
Sub-Total $44,302.00
4. Bonds, Insurance, Special Requirements Each $500.00
Sub-Total $58,352.04
Tax $3,410.19
Consumables $182.81
Estimated Price $61,945.00
3a.(Optional)Wear Rings Qty Units Unit Price Ext Price
I Each $198-00 $198.00
Sub-Total $198.00
Tax $15.35
Option Total $213.35
Our estimate is valid for 30 days. Please contact your Layne representative if you have any questions.
WATER RESOURCES
1717 Park Ave,Redlands,CA 92373 1 Office:909-390-2833 1 Fax:909-390-6097 1 layne.com
Attachment 1
Page 3of10
La"
A GRAMM 4OMPANY
11/8/2018 Quote:94616A
Steeplechase Booster Station
CONFIRMING ORDER
The undersigned.Client instructs Layne Christensen Company to proceed with the work described with the understanding
that Layne's Standard Terms and Conditions and attached documents are hereby incorporated as part of this Confirming
Order.
Work to be performed per attached quote 94616A.
CLIENT CONTRACTOR
City of San duan Capistrano _ Lane Christensen Company
r
8y: ti : U--
Title:
`Title: Title:Account Manager
Date; Date- 1118118
WATER RESOURCES
1717 park Ave,Redlands,CA 92373 1 Office:809-390-2833 1 Fax:909-390-60971 laynexom
Attachment 1
Page 4 of 10
SUBMITTAL
Quote ID:9004-181016-001:0:1 QTY:1
VIC-F LTM 701-C.11 Stages
PERFORMANCE ON DESIGN CURVE AT 1750 RPM
Shut Off Design 121 Run Out 1`�I
Flory(USGPM) 0.0 200.0 0.0 (Beat Efficiency 81.30%at 184,0 USgpm
TDH-Bowl(ft) 373.0 257.0 0.0 ;Design Flow%REP 108.70%
TDH-01sch Flange(ft) -194.6 521.9 ;Pump Efficiency 79.57%
Bowl Efficiency J%) 80.50 Overall Efficiency 74.D0%
Power(Hp) 18.1 :Max Power(NOL) 16.7 Hp at 250.0 USgpm
NPSHr(ft)1 j - 5.4 - Max Power(NOL)at Max Trim 17.4 Hp at 253.0 USgpm
NPSH Margin(ft)1,j 42.2 Specified NPSH Ratio 1.1
Hydraulic Thrust(lb) 1305-5 899.5 0-0 Thrust Load Power Loss 0.12703 Hp
Thrust(Ib) 1349-4 827.0 0.0 'Total Flow Dente Factor 1,00
Pressure-Bowl(psi) 151.5 111.3 Total Head Derate Factor 1,00
Pressure-Disch Flange(psi) -84.2 225.9 - 'Total Efficiency Derate Factor 1.00
Min Submergence(Inch) I 16.84 Actual Submergence 960.00 In
Friction Lose(ft).•i; 0.29 Shaft Friction Power Loss 0.04 Hp
Lineshaft Elongation(Inch) 0.0D576 0.00397 - Min Flow(MCSF) 45.9 USgpm
Column Elongation(Inch) 0,00042 0-00042 jkWh per 1000 gal 1.09058
Late raI(Inch) 0.13534 0.13355 - impeller Running Clearance 0,13 in
(tI at Ist+rnpellel eye (21 rakW ValL,gs 131 from hotlam of pump JAI N-em ZOM to 11sch flange 151 ha sed an user enlefed TDH
OPERATING CONDITIONS FLUID CHARACTERISTICS
Specified Flow 200.00 USgpm Fluid Water
Design TDH(Bowl) 757.0 ft
Fluid Temperature 68.0°F
Rated Speed 1750 RPM Specific Gravity 1 0000
Atmospheric Pressure 15 psi Viscosity 1,0017 cP
TPL 16.00 tt Vapor Pressure 0.3393 psi
Can Length 183.13 in Density 62 ibslft°
NPSHa at 1st Impeller 47 6 R
NPSHa at Grade 33.9 it
Suction Pressure 1150 psi
Suction TDH 285,7 It
MATERIALS 8 DIMENSIONS
Bowl Oats Bowl Data
Bowl Material Cast Iron with Glass Enamel Tube Adapter Bearing Not Included
Bowl Material Derate Factor 1.013 Material
Impeller Material 316SS Impeller Trim 5.19 in
Additional Stage Impeller 316SS Max Impeller Trim 5.25 in
Material Thrust K-Factor 3,5 Lb/Ft
Impal ler Matt Derate Factor 1.00 Bowl Pressure Limit 350 psi
Bowl Shaft Material 416SS Available Lateral 0.50 in
Impeller Attachment Taper Lock Bowl Assembly Length(BL) 79.44 in
Taper Lock Material 416SS Disch Bowl Length OLS(LB) 3.75 In
Discharge Bowl Material Cast Iran Disch Bow]Length ELS(L2) 4.38 in
Suction Type lieu Bowl Shaft Diameter 1 3118"I30.2 mm]
Suction Material Cast iron Impeller Balance Dynamic Two Plane Balance
Bowl Belting Material 31655 Impeller Design Enclosed
Sand Collar 3048S Bowl Wear Ring Not Included
Pipe Plug lion impeller Wear Ring Not included
Suction Bearing Bronze Suction Pipe Diameter No Suction Pipe
Discharge Bowl Bearing Branze Bowl Diameter(D) 7.50 In
Intermediate Bawl Bearing Bronze Bowl Length(1.3) 6.38 in
Strainer Type Not Included Bowl Flange Diameter(A) 2 81 in
DO NOT USE FOR CONSTRUCTION UNLESS CERTIFIED
CertMed By
Project SJC Steeplechase
Tag - -
PO Number
Serial Number
Attachment 1
Page 5 of 10
SUBMITTAL
Quote 1119004-1610 1 B-001-0'I QTY:1
VIC-FLTM 7CLC,11 Stages
cT�L ata �owTF1+rla
Bowl F[on ge Thickness(E) 5.30 in Max Bowl Shaft Diameter 1.18 in
Floor Clearance(X) 5.75 In Bowl Shaft Length 85.80 in
Min Column Diameter 41n Bowl Shaft Power Llmlt 1.2.8.10 Hp__
Max Column Diameter Bin
Bowl Specials
Column Data Column Data
Column Type Threaded Column Retainer Design Separate
Column Diameter 5'[127mm] Maximum Bearing Spacing 5 R(1.5 m)Spacing
Lineshaft Diameter 7 in[25.4 mm] Max Column Section Length 60 in
Column Pipe Material Ca;bon Steei Number of Bearings 1
Lineshaft Material 41 BSS Fabrication Welding Option Not Included
Llneshaft Bearing Material Rubber[dog bone] Column Length(COL) 100.56 in
Llneshaft Coupling Type Threaded Column Wail Thickness 0.25 in
Lineshaft Coupling Material 416SS Column Load 804.0 Ito
Column Loss 0-19ft Lubrication Method Walor(Open Linestiall)
Column Velocity 3.27 ftls Lineshaft Length 100.56 in
Column Shaft Sleeve Not Included Head Sleeve Not Included
Column Bearing Retainer 3D4SS Li nes halt Power Limit 72 Hp
Column 8oprip g Options Not Included
Column Specials
Head&Can Data Head&Can Data
Head Type Type FL(Fabricated L-Head I Head Loss 0.10 N
Can with Suction) 150#DIsch Campanian Fig Not Inck)ded
Discharge Flange Rating 300# 300#Suct Convenience Fig No suction Range
Disch Flange Pressure Limit 740 psi Column Hanger Flange Not Included
Head Design One Piece head Head Sleeve Not Included
Discharge Head Material Carbon steel Head Bolting 316SS
Headshaft Material 416SS Split Gland 31555
Headshaft Coupling Type Threaded Motor Stand Not included
Headshaft Coupling Material 41685 Air Vacuum Valves Not included
Headshaft Dia motor(BX) 1.00 In Fabrication Welding Option Not Included
Discharge Head Size 6"[152mm] Can Diameter 10 inch[254mm)Can
Discharge Head BD 12"[305mm( Can Length 103.13 in
Sealing Method Mechanical Seal Can Material Carbon Steel
Stuffing Box Material Cast iron Can Bolting CaFbon Sleet
Tension Plate Not lnctuded Suction Flange Rating 160#
Mechanical Seal Chesterton 1551❑CW Suction Flange Pressure Limit 295.00 psi
Seal Provided By Xylem Inlet Suction Size 8"(203mm]
Seat Mounted By customer Can Mounting Standard
Stu Ring Box 1 Seal Hsg Boit 316SS Inlet on Can Included
Stuffing Box 1 Seal Hag 8 r Bronze Fabrlcatloo Welding Option Not Included
Seal Housing Material Cast iron
Stool Sub Base Not included
Head&Can Specials
Motor Data Motor Data
Driver Typa Vertical Hallow Shaft Motor Motor Efflcis ncy 93.00%
Motor Manufacturer us Motor Frame 256TPH
Selectad Motor Power 20.00 Hp Motor Diameter(B D) 12,00 in
Motor Speed 1750 RPM Motor Diameter(BX) 1.00 in
Voltage 2301460 Thrust Level 100%
Phase I Frequency 3 PH 160 Hz Thrust Capacity 33001159.
Enclosure WPl Inverter Duty Yes
DO NOT USE FOR CONSTRUCTION UNLESS CERTIFIED
Certified By
Project SJC Steeplechase
Tag
PO Number
Serial Number
Attachment 1
Page 6 of 10
SUBMI rAL
"risleiistetz VtC-FLTM90 18107CI-C,11 Stages 1 QTY 1
Meter Data Motes Data
Steady Bushing Yes Mfg Catalog Number 11-1020V213LF
Motor Coupling NRR Motor Part Number H02US2A1FB-VWRU-
Insul0on Class F 000A0171000
Service Factor 1,15 Driver Size Criteria Max power on design curve
Motor Provided By Xylem (NOL)
(Rotor Mounted By Customer
Motor Specials
Coating Data Coating Data
Bowl OD Tnemec 141(NSF approved), Can❑D Standard Green Enamel
Expoxy applied at 16 mlls min Head ID Tnemec 141(NSF approved):
Column ID Tnemec 441 [NSF]:Epoxy Expoxy applied at 16 mils min
applied to 8 mils min Head OD Tnemec 141(NSF approved):
Column OD Tnemec.141 [NSF approvedy Expoxy applied at 16 miis min
Fxpoxy appiled at 16 mills min Enclosing Tube OD Not Included
Column Searing Retainer Not Included Steel Sub Base Not Included
Can ID Not Included
Testing Data
Miscellaneous Specials
Weight Data Weight Data
Total Bowl Weight 330 lbs Head Weight 353 lbs
Unit Bowl Weight 50 Ips 128 lbs Motor Weight 300 lbs
Total Column Weight 180 Itis Total Welght 1163lbs
Unit Column Weight 20lbs Total Rotating Weight 81 lbs
INFO,WARNING&ERROR MESSAGES _
Invalid s inva w
Our offer does not include speciflc review and in ccrporatJon of any Statutory or RegluIstory Requirements and the affer is IImIts d to the requirements of the
deatgn a pecifications,Should any Statutory or Regulatory raqulee ments need to ba rav[owed and 1n carpe rated then the Customer is responsible to ideolify those
and pravido coplas for review and revision of our offer.
Our quotation is offered in accordance with our comments and excaptlons identified in aur proposal and governed by our standard terms and conditlons of safe—
Xylem Americas attached hereafter.
For units requiring performance test,all performance tests will be condurto4 per ANSIIHI 14.6 standards unleas otherwise noted in the aelecton software
submittal documents.Teat results mooting with grade 28 tolerances for pumps with a rated shaft power of 134HP or less and grade 16 for grantor than 134HP will
ba considered passing.
Customer is res ponslhis for verifying that the recommendations made and the materials selected are aatIsfectory for tha Customer's intended anvwonmaat and
Customer's us of the selected pump.Customer I res pan alble far determining the auItobII Ty of Xylem recommendations for all operating conditions within
Customer's andlor End User's control.Xylem disclaims all warranties,express or implied warranties,including,but not limited ta,warranties of morchantablllty
and fitness for a particular purpose and ali express warranties other than the limited express warranty set forth in the attached standard terms and conditions or
Date—Xylem Americas attached ttareafter.
Xylam doaa not guarantee any pump Intake configuration.The hydraulic and structurat adequacies of these structures are the sole responsibility of the Customer
or h I a re pro 9antabyes.Further,Xylem accepts no liability arising autof un sail aractory pump{make flaId ape rating conditions.The Customer or bis
r a p res an to ti v as are referred to the Hydraulic Institute Standards for re c a m m endat lo no on pump intake design.Tn aplimixo the hydraulic design of a fleld pump
Intake configuration,tha Customer should strongly consider performing a detailed acais rne dot pump Intake study.However,the&doquscles of these
re commends lie na are the sole responsibility of the Customar
DO NOT USE FOR CONSTRUCTION UNLESS CERTIFIED
Certified By
Project SJC Steeplechase
Tag
PO Number
Serial Number
Attachment 1
Page 7 of 10
OUTLINE DRAWING
Quo le ID;9004-181016-001:0:1 OTV: 1
�.�li'iS�G'1tSL'lt VIC-FLTM 7CLC, 11 Stages
'J"MR rc Ptcs DIMENSIONS PUMP DATA
:EO sP oN"H"QC
J[Mounting Flange Hole 1.00 in Column Diameter 5"[127mm]
+- Dia] Llneshaft Diameter 1 In[25.4 mm]
a ` K[Mounting Hole Places] 12 Specified Flow 200.00 USgprn
an H[Mounting Flange Balt 14.25 In Specified TDH 250.00 ft
Circle] Motor Manutocturer U5
AG[Motor Height] 26.75 in
Driver Typo Vertical Hollow
Disc HEAP CD[M Olaf Coupling x3.38 in yp Shaft Molar
Height] Selected Motor Power 20,DD Hp
DD XC[Top HdshR to top VHS 3.25 in Motor Speed 1750 RPM Mgtorj
} xF BD{Motor Base Dia] 12,00 In Phase f Frequency 3 PH 160 Hz
Ao V BD Head[Discharge Head 12.00 in Voltage 2301460
g { ` Base Dia]
lL7l[ co HH[Head Height] 23.0D in WEIGHTS
E AD[Maunling Flange 1.13 in Total Bowl Weight 33016s
} ThicknesS] g
Unit Howl Weight 50 Ills 12a lbs
• � I � Db[Ditch Flange Stidcoul] 11,00 in g
DH[Dish Flange Heightl fi_QO in Total Wumn Weight 160 Ibs
• — S[Hanger Flange Unit Column Weight 20 Itis
►tN j by StIrkdown Length] 7.81 in Head We]ght 3531bs
F R[Hanger Flange OD] 7.50 in Motor Weight 300 Itis
1 a Dim UG[Underground 8.00 in Total Weight 11631bs
as Suction] Total Rotating Weight 81 lbs
Column Length(COL) 100.56 in
COL[Column Diameter) 5.00 in
TPL[Tolal Pump Length] 180.00 in
r MIN SUB[Minimum
I
Submergence] 16.84 in
MAX[Max Assembly OG] 7.50 in NOTES
_ CL[Can Length} 183.13 in 1 Tolal Pump Lengln t 1 0 inch
t CAN tCar Diameter] 10.00 in2 Tolerance on all dimensions is.12 or t 12
BL[Bowl Assembly 7BAd in inch per 5 ff_wh cnever is greater.
•
1 Length] 3 All dimensions shown are In inChes un;ess
DE[VII Suction Flange otherwise specified.
r iWlStIckout 11.00in
] d drawing not to sca'e.
axa V[Sub Base Thickness] 1.13 In 5 y, NPT—Gauge Conn(plugged)
W[Sub Base Overall Size] 1B.00 in 6 Driver may be rolaied at 901 intervals about
X[Center Line of Holes) 16.06 in vertical wtedinefor details refer to drlver
Y[Mounting Holes Base dimension drawing
Plate Dia] Q 8B to 7 Refer to product IOM for impeller setting
Z[Base Plate Opening or requirements.
Can 101 16.00 in 6 This assembly hag been designed so that
its ralwal frequency responses avoid the
specific aparaling speeds by an adequale
safety margin The design has assumed
NOTE: discharge heads will be the foundalion to be rigid
fabricated to the same dimensions
as the existing discharge heads
DO NOT USE FOR CONSTRUCTION UNLESS CERTIFIED
Certified By
Project SJC Steeplechase
Tag
PO Number
Serial Number
Attachment 1
Page 8 of 10
CROSS SECTION DRAWING
Cl�t1'1St�'7f.4L'J7 Quote ID:9064-181018-001:0.1 QTY:1
VIC-FLTM 7CLC,11 Stages
803
r°a BILL OF MATERIALS
ITEM PART NAME CODE MATERIAL ASTM
Head Assembly
608 Headshaft 2227 SST 418 A582 S4160D
in 600 Head-Discharge 9645 Carbon Sleet Fab A63
'— 602 Sub Base NIA Not Included NIA
Ug t 604 Nut–Adjusting 2242 Carbon Steel 1018 A106
805 Motor Stand NA NA NA
E2G 6ff4 616 Housing 1003 Cast Iran C130 A48 CLASS 3DB
779 - 617 Bee ingd-lousing 1616 Bronze Bismuth as"Modified
fi16 618 Gland-Spilt 1203 SST 316 A744M
825 Tension Plate MIA Not included NIA
617 826 Mechanical Seal 0000 Chsstedon 1551UCW
637 Hanger Flange NIR Not included NIA
677 648 Headshall Sleeve WA NIA NIA
,19
516 65F
608 HeadshaR Coupling 2285 SST 419 A682M
6 i
647 730 Key-Motor Gib 2242 CarbonSteel 1018 At08
760 Head Slung 2228 SST 3t8 A27e
656 779 Gasmi-Housing 5136 Acrylic4Nltnte 5136 REV 4
642 Column Assembly
600 642 Column Pipe 9501 Bieck Pipe Sch 40 A53
645 Column-Coupling 9845 Carton Steel Fab A53
iieM1 681 646 Llne8hr3H 2227 SST 416 A562 S41600
* 949 Line sharl-Coupling 2265 SST 416 A582M
652 Retainer-t3eanng 1205 SST 344 A744M
er7 656 LilleshattBow rig 5121 Rubber Epdm 03568
leu ;
Gro Bowl Assembly
B77 660 Shat!-Bolt 2227 SST 416 A582 S41600
672 661 Discharge Bowl 1003 Cast Iron C130 A48 CLASS 30B
392—
580 884 Bean ng-Disc haq a Bowl 1618 Bronze Bismuth 8584 Modified
968 Fearing Tube Adapt NIA Not Included NIA
_ 7417670 Bovet-Intermedlate 8911 Cast Iron C130 Enamel A40
872 13earivg-lntermediate Bowl Isle Bronze Bismuth B584 Modified
673 Impeller 1203 SST 316 A744M
673 Impeller 1203 SST 318 A744M
677 Taper Lack-Impeller 2217 SST 418 A502M
B80 Weer Ring-Bawl NIA Not Ind uded NIA
Sal Weer Ring-impeller NA Nal Indude4 NA
Sae Suction 1003 Cast Inan C130 A48 CLASS 3013
590 Bearing-Suction 1109 Bronze I"i903M0"G"Mod 8594
692 Sandcoller 1205 SST304 A744M
747 Pipe Plug 1134E Malleable Iron A197
760 Capscrew-Hex 2229 SET 316 A278
DO NOT USE FOR CONSTRUCTION UNLESS CERTIFIED
Certified By
Project SJC Steeplechase
Tag
PO Number
Serial Number
Attachment 1
Page 9 of 10
PERFORMANCE CURVE
Quote ID:9004-191016-041:0:1 QTY:1
[:lirisfeiise>ra ViC-FLTM 7CLC,11 Stages
�in 95
55 05
74 7.1
77
320 80
4.25 tis gg
244 _ _. 77
C 46 `
,e 55 7d
TO 70
56
= 160
TO ss
45
8066
30
46
30
a 40 813 +2U 160 200 240 280
C 10
Z
N
!L
Z 0
20 40 so 120 160 200 240 20
10
# 0
40 6o 120 160 204 240 280
a
US gprn
CURVE DATA
Spectfled Flow 200,00 USgpm Design Pressure(01sch Flange) 225 9 psi NPS 14r at Dow 9a 5 4 rl
Specified TDH 250.00 1t Shut Off TDH IBowl) 373.0 it Speclfled NPSH Ratio 1.1
Motor Speed 1750 RPM Shut Off TDH(Disch Fl angel -194.6 It NPSH Margin at Design 42 2 ft
Atmospherlc Pressure 15 psi Shut Off Preasure(Bowl) 161.5 psi Min Submergence at Design 16.04 in
TPL 15.00 It Shut Off Pres aure(15isch Flange) -84 2 psi Actual Submergence 180 00 in
Can Length 183.13 in Bowl Efficiency at Design 80.50% Shaft Friction Power Loss 0.04 Hp
NPSHa at0rade 33.9 R Best Efficiency 81 30'% Thrust Load Power Loss 0 12703 Ho
NPSHa at 7st Impel lar 47 5 ft BEP Flow 184.0 USgpm Hydraulic Thrust at Des lgn 999-5113
Suction pressure 115.0 psi Design Flow k BEP 108 70% Thrust at Design 927 0 to
Suction TDH 265.1 It Pump Efflclancy 79S7% Hydraulic Thrust atShut Off 1305.5 lb
Fluid Water Motor Efficlsncy 9300% Thrust at Shut Off 1349.4 Ib
Fluid Temperature fib 0'F Overall Efficiency 74,00% Bowl Mateflai Cast Iron with Glass
Specific Gravity 1.0000 Friction Loss at Design 0 29 ft Enamel
Viscosity 1 0017 cP Power at Design 16 1 Hp Bowl Material Derato Factor 100
Vapor Pressure 0.3393 psi NOL Power 16.7 Hp Impeller Material 316SS
Density 62 Ibslft' Max Power(NOL)Flow 250-0 USgpm Impeller Matt Derate Factor 1 00
Deslgn Flow 200.0 USgpm Max Power;NOL)at Mair Trim 17 4 Hp Total Flow Dersts Factor 1.00
Min Flow IMCSF) 45 9 USgpm Max Power(NOLs Flow at Max 733.0 USgpm Total Head Derate Factor 1 0o
Design TOH(Bowl) 257.08 Trim Total Efflciancy Darate Factor 1 00
Design TDH(Disch Flange) 521.9 it Recommended Power 20 00 Hp Curve ID E6407CFPC1
Design Preasure lBowl) 111.3 psi kWh per 1000 gal 1.09058
DO NOT USE FOR CONSTRUCTION UNLESS CERTIFIED
Certified By
Project SJC Steeplechase
Tag
PO Number
Serial Number
Attachment 1
Page 10 of 10